background image

859

Leak Detection Sensor 

EX-F70

 

SERIES 

 

EX-F60

 

SERIES

FIBER

SENSORS

LASER

SENSORS

PHOTO-

ELECTRIC

SENSORS

MICRO

PHOTO-

ELECTRIC

SENSORS

AREA

SENSORS

LIGHT

CURTAINS

PRESSURE / 

FLOW

SENSORS

INDUCTIVE

PROXIMITY

SENSORS

PARTICULAR

USE 

SENSORS

SENSOR

OPTIONS

SIMPLE

WIRE-SAVING

UNITS

WIRE-SAVING 

SYSTEMS

MEASURE-

MENT

SENSORS

STATIC 

CONTROL

DEVICES

ENDOSCOPE

LASER

MARKERS

PLC /

TERMINALS

HUMAN 

MACHINE 

INTERFACES

ENERGY 

CONSUMPTION 

VISUALIZATION 

COMPONENTS

FA 

COMPONENTS

MACHINE 

VISION 

SYSTEMS

UV 

CURING 

SYSTEMS

Selection 

Guide
Wafer 

Detection

Liquid Leak 

Detection

Liquid Level 

Detection

Water 

Detection

Color Mark 

Detection

Hot Melt Glue 

Detection

Ultrasonic

Small / Slim 

Object Detection

Obstacle 

Detection

Other 

Products

SQ4

EX-F70/

EX-F60

PRECAUTIONS FOR PROPER USE

Refer to General precautions.

EX-FC1

Mounting

• When mounting the unit, be sure to use the unit mounting 

base (

MS-SL-2

) (accessory).

• When installing the unit mounting base to the unit, insert 

the base aligned with the grooves of the unit and move 
until the unit stopper is locked.

• Two installation positions are available for the unit 

mounting base so that the unit direction can be changed. 
Install the base at one of them.

Mounting position 1

Mounting position 2

˂In case of using a DIN rail or the mounting bracket (MS-DIN-3) 

(optional)˃

  

Fit the rear part of the unit 

mounting base on a 35 mm 

1.378 in

 width DIN rail or 

the mounting bracket  

(

MS-DIN-3

) (optional).

  

Press down the front part 

of the unit mounting base 

on the 35 mm 

1.378 in

 

width DIN rail and fit the 

front part of the base on 

the DIN rail. 

 

*  For removal, insert a 

flathead screwdriver into 

the DIN rail stopper and 

pull towards yourself.

Designation

Function

Normal indicator

(Green LED × 8)

Lights up when sensors are connected to each channel 

and the connection setting switch is set to ON.

Error indicator

(Red LED × 8)

Lights up when leak is detected by any sensor 

connected or any sensor is mounted improperly.
(For details, refer to “

Connection setting switch

”.)

Output indicator

(Orange LED)

Lights up when the output relay is ON (Normal).

Connection setting 

switch

Set the switch to ON when the leak detection 

sensor is connected, set to OFF when the leak 

detection sensor is not connected.

Connector

Connect the leak detection sensors.

Part description

Grooves

Unit stopper

Unit

Unit mounting base

Din rail stopper

7

6

5

4

3

2

1

0

Unit

Unit mounting base

Din rail stopper

DIN rail stopper

35 mm 

1.378 in

 width DIN rail or the 

mounting bracket (

MS-DIN-3

) (Optional) 

Flathead screwdriver

DIN rail stopper

Unit stopper

Unit mounting 

base

Unit

(

Purchase 

separately.

M4 pan head screw

)

④ 

① 

③ 

② 

Connection method

• Make sure to connect or disconnect the snap male 

connector (

SL-CP1

) in the power supply off condition.

• Take care that wrong wiring will damage the product.

• The terminal No. 4 of the snap male connector  

(

SL-CP1

) is not used. 

Take care not to connect to the terminal No. 4 by 

mistake. Further, if there are unused wires, please 

insulate them.

1 2 3 4

1 2 3 4

Content

+V

0 V

IN

No connected

• For details of the hook-up method of the snap male 

connector (

SL-CP1

), refer to the Instruction Manual 

enclosed with 

SL-CP1

.

• By holding the 

SL-CP1

 with 

the cable connected, insert it 
into the connector of the 

EX-FC1

 reliably till it stops.

Disconnection method

• 

By holding 

SL-CP1

, pull it 

from the 

EX-FC1

  horizontally.

Note:  Do not pull out by holding the 

cable, as this can result in cable 

disconnection.

7

6

5

4

3

2

1

0

EX-FC1

SL-CP1

 (Accessory)

Cable of the leak 

detection sensor

Connection

˂In case of using screws˃

• Mount using M4 pan head 

screws with a tightening 

torque of 0.8 N·m or less. 

However, in case of side 

mounting, make sure to 

mount the unit such that 

the unit stopper faces 

front.

Summary of Contents for EX-F70 SERIES

Page 1: ...ly and a FAULT indicator red which lights up when sensing the leaked liquid or when mounted incorrectly forgetting to mount exclusive mounting bracket So the operation can be checked easily PVC mounti...

Page 2: ...m 16 404 ft cable length type of EX F71 PN is EX F71 PN C5 Simple wire saving unit for leak detection sensor Appearance Model No Output EX FC1 Relay contact 1 a 5 m 16 404 ft cable length type PFA en...

Page 3: ...0 V or less at 50 mA source current 0 4 V or less at 16 mA source current Utilization category DC 12 or DC 13 Output operation In normal state ON When leak detected or the sensor is mounted improperly...

Page 4: ...chanical lifetime 50 million switching operations or more switching frequency 180 operations min Utilization category DC 12 or DC 13 Output operation The output relay is ON when the input signal from...

Page 5: ...sistor Users circuit Internal circuit 50 mA max Blue 0 V Brown V Black Output Color code 12 to 24 V DC 10 Tr D ZD Load Sensor circuit Blue Brown Black 12 to 24 V DC 10 Load Blue Brown Black 12 to 24 V...

Page 6: ...thick the sensor body cannot be fitted to the mounting bracket How to fit the sensor body to the exclusive mounting bracket Match the notch in the sensor body with the projection of the exclusive moun...

Page 7: ...to each channel and the connection setting switch is set to ON Error indicator Red LED 8 Lights up when leak is detected by any sensor connected or any sensor is mounted improperly For details refer t...

Page 8: ...ke sure that the power supply is off while wiring Verify that the supply voltage variation is within the rating Take care that if a voltage exceeding the rated range or an AC power supply is directly...

Page 9: ...ing bracket for EX F72 PN MS EX F7 3 For two point fixing MS EX F7 2 For adhesive fixing Note A M4 stud bolt has been welded to this unit M4 nut is not supplied with the sensor Purchase it separately...

Page 10: ...6 26 1 024 2 5 0 098 cable 3 m 9 843 ft long NORMAL indicator Green FAULT indicator Red 19 0 748 9 0 354 3 0 188 14 0 551 19 0 748 FAULT indicator Red NORMAL indicator Green 2 4 2 0 165 4 5 0 177 17 0...

Reviews: