Maintenance

If the Fault LED is not displaying according to section 7.4 when error occurs, check 
the  following  list  to  make  sure  that  the  present  state  of  the  installation  allows 
proper operation of the unit.

— Is the inverter located in a clean, dry, adequately ventilated place?
— Have the DC input breakers been opened? 
— Are the cables adequately sized and short enough?
— Are the input and output connections and wiring in good condition?
— Are the configurations settings correct for your particular installation?
— Are the communications cable properly connected and undamaged?

Troubleshooting

Contact  the  Panasonic  customer  support  for  further  assistance.  Be  prepared  to 
describe details of your system installation and provide model and serial number of 
the unit.

Inverters do not need any maintenance or correction in most condition, but if the 
inverter often loses power due to overheating, the cooling fans on the rear of 
house may be covered by dirt.
Clean the cooling fans with a soft dry cloth or brush if necessary.
Only trained and authorized professional personnel who are familiar with the 
requirements of safety should perform servicing and maintenance work.

Ø

Safety checks

Safety checks should be performed at least every 12 months. Please contact the 
manufacturer (Panasonic) to arrange a qualified person with adequate training, 
knowledge, and practical experience to perform these tests. (Note: this action is 
not covered by warranty). The data should be recorded in an equipment log. If the 
device is not functioning properly or fails any test, the device has to be repaired. 
For safety check details, refer to Section 2 Safety instruction of this manual.

Recommended Periodic Maintenace

Ø

Only qualified people should perform the following tasks.
While using the inverter, the user should examine the machine regularly:

10 Maintenance

73

72

Ÿ

Check if the indicators of the inverter are in normal state, check if the keys of 
the  inverter  are  in  normal  state.  This  check  should  be  performed  at  least 
every 6 months.

Ÿ

Check  that  if  the  input  and  output  wires  are  damaged  or  aged.  This  check 
should be performed at least every 6 months.

For DC Switch, the user should:

Ÿ

1.  Check  the  installation  for  signs  of  overload,  overheating,  and  that  the 
terminals do not exceed the limit of 167

/75°C under full load.

Ÿ

By  operating  the  switch  a  few  times  (5x),  the  contacts  will  clean  themselves 
and the switch will have a longer life.

SW OCP Fault

Battery Charge and Discharge Over Current Fault or PV Over Current 

Fault or Inverter Over Current

Ÿ

Please contact Panasonic Technical Support

RCD Fault

Residual Current Device Sensor Fault

Ÿ

Please contact Panasonic Technical Support

Rtc Fault

SoftVerFault

Program Write Fails or Incorrent Program Written in

Ÿ

Re-write the program

Ÿ

Or contact Panasonic Technical Support

Rtc Fault

Ÿ

Please contact Panasonic Technical Support

Faults

Diagnosis and solution

Grid Lost Fault

Grid Lost Fault 

Ÿ

System will reconnect if the utility is back to normal

Ÿ

Check if the grid is normal

TZ Protect Fault

The Firmware of PV or Inverter or Battery Over Current Fault

Ÿ

Please contact Panasonic Technical Support

Summary of Contents for EVERVOLT EVHB-I7

Page 1: ...320101067100...

Page 2: ...NNECTION 6 3 GROUND CONNECTION 4 TECHNICAL DATA 4 1 DC INPUT 4 2 AC LOAD 4 3 GENERAL DATA 4 4 BATTERY INPUT OUTPUT 4 5 EFFICIENCY SAFETY AND PROTECTION 4 6 ENVIRONMENT LIMIT 5 2 SELECTION FOR INSTALLA...

Page 3: ...l contains important instructions that shall be followed during installation and maintenance of the unit EVHB I7 Note EVERVOLT Hybrid Inverter series means PV grid supported storage inverter The assem...

Page 4: ...uring installation and operation of the EVERVOLT Hybrid inverter to reduce the risk of personal injury and to ensure a safe installation Installation commissioning service and maintenance of EVERVOLT...

Page 5: ...onductors may be ungrounded and energized or normally ungrounded conductors may be grounded WARNING Safety Safety Keep away from flammable and explosive materials to avoid fire Do not install or store...

Page 6: ...heavy Use of lift equipment is recommended NOTE Make sure that existing wiring is in good condition and that wire is not undersized NOTE Measure the voltage between terminals UDC and UDC with a multi...

Page 7: ...tomatic disconnect of residential or small commercial PV systems fully compliant with the rapid shutdown requirements of National Electric Code NEC ANSI NFPA 70 Sections 690 12 Battery The EVERVOLT Hy...

Page 8: ...When the power of PV is sufficient The power generated from PV will be used to supply the local loads first then proceed to charge the battery bank If the battery is fully charged the excess power wi...

Page 9: ...ensure the battery a minimum capacity for grid to reserve outage In this work mode the battery will be charged at the set time and will never discharge when the grid is on ou can also choose whether t...

Page 10: ...inverter D Conduit plugs There are four 1 inch openings for wiring connection Each conduit opening is fitted with a conduit plug which needs to be removed before installation and wiring connection A...

Page 11: ...1 ZZZ will be cleared for next work order Model Parameter Serial NumberIdentification PV INPUT EVERVOLT HYBRID INVERTER Model EVHB I7 Max DC Voltage Operating Voltage range No of MPPT String per MPPT...

Page 12: ...a Max inverter backfeed current to the array A 27 A rms 1 cycle 400 A peak 0 02 ms Maximum output overcurrent protection A P 40 2 4 4 Battery Input Output 4 5 Efficiency Power Consumption and Standard...

Page 13: ...ance EVERVOLT Hybrid Inverter has the NEMA 4X ingress protection which allows it to be installed outside the door The installation position shall be convenient for wiring connection operation and main...

Page 14: ...the inverter at a maximum back tilt of 5 degrees and avoid forward tilted excessive backward tilted side tilted or upside down 5 2 3 Installation Angle Required To ensure good heat dissipation and co...

Page 15: ...inverters and ensure an adequate fresh air supply if possible Mechanical Installation Mechanical Installation 25 24 51 18 in 1300 mm 19 68 in 500 mm 19 68 in 500 mm 19 68 in 500 mm 5 3 Tools Preparat...

Page 16: ...J H F G K L Inverter X1 Name N O P Description Product Mental cover X1 Bracket X1 Self tapping screw X12 Washer X12 Expansion bolt X12 Communication dongle X1 Optional PE cable X1 Cable protective gua...

Page 17: ...B C X2 WB 32 E X2 The scheme of hole punch differs from different wall with different characteristics Introduction of schemes Scheme A Studs at regular intervals spaced at 12 and 24inch Punch the hole...

Page 18: ...unting the inverter the mechanical installation of the whole battery must be completed NOTE M4 4 4 lbf in 0 5 N m b Use the bracket as the template to mark the screw hole location on the wall c Unscre...

Page 19: ...0 N m 10 mm Step 2 Hang and fix the inverter on the bracket b Place the cable protective guard on the correct position of battery s BMS prior to the wiring connection between inverter and battery and...

Page 20: ...just the whole system inverter and battery to be leveled NOTE Before mounting the metal cover the wiring connection between battery and inverter must be completed For detailed information about how to...

Page 21: ...6 WARNING Damage to seals on the enclosure lids in subfreezing condition If you open the enclosure lids of the wiring box when temperatures are below freezing the enclosure lid seal could be damaged A...

Page 22: ...2 RS485_MLPE_A Pin 3 RS485_MLPE_B Type CAT5 or better CAT5 or better CAT5 or better CAT5 or better Cross sectional Area Range 24 18 AWG 24 18 AWG 18 16 AWG 24 18 AWG 18 16 AWG 24 18 AWG 7 COMM in ter...

Page 23: ...DC switch is in ON position WARNING Before inverter wiring connection Make sure no live voltages are present on PV input and AC output circuits and make sure that the DC switch is in OFF position mea...

Page 24: ...d of DC wire and the AC wire Step 3 Insert the end of wires into the Cord End Terminal and then use the crimping tool to crimp the Cord End Terminal tightly the shape will be square Step 4 Use the slo...

Page 25: ...C terminals may carry current even without connected wires WARNING Ensure maximum protection against hazardous contact voltages while assembling PV panel installations Both the positive and negative l...

Page 26: ...ker not included in the EVERVOLT Hybrid inverter is required to protect each AC line L1 and L2 of the inverter The circuit breaker should be able to handle the rated maximum output voltage and current...

Page 27: ...nection Electrical Connection 49 48 As a Lithium ion battery will be connected with EVERVOLT Hybrid inverter the battery communication should be compatible with EVERVOLT Hybrid inverter and the BMS mu...

Page 28: ...and insert the stripped section into the grounding terminal For the specific requirement of power cable please refer to section 6 1 Overview of All Electrical Wiring Methods c Crimp it with crimping...

Page 29: ...diagram NOTE In the first inverter in the communication chain plug the 8 pin female block with the terminating 120 Ohm resistor into the 8 pin male block Maximum four inverters can be communicated vi...

Page 30: ...ires and leave six wires for connection Remove 0 24 in 6 mm of insulation from the end of the six wires Pin 7 Pin8 Select two 18 16AWG wires and remove 0 24 in 6 mm of insulation from the end of the t...

Page 31: ...for communication connection steps between inverter and EV SB 8 pin Step 1 Strip Length Conduit 0 24 in 6 mm Step 2 24 18 AWG 18 16 AWG Step 3 Step 4 Electrical Connection Electrical Connection 57 56...

Page 32: ...er rapid shutdown mode when the Transmitter PLC 1P is switched off and resume energy production when power is restored to the Transmitter PLC 1P This solution complies with NEC 690 12 specifications f...

Page 33: ...es not allow running standalone mode 2 The Primary also needs to set the number of parallel machines 3 Primary communication lost system down waiting for human intervention to recover 4 Loss of Second...

Page 34: ...battery POWER button to start the battery Install the outer cover of the EV SB The system will start up Check the status of indicators on inverter battery and EV SB for more information on the codes...

Page 35: ...e inverter is in waiting or checking status Off when the inverter has a fault Operation LED Primary Green for 2s and then quick flashing green for 1s 0 2s on 0 2s off when the inverter is in normal or...

Page 36: ...rt to get the update les and extract it into your U disk as follow update ARM 618 00515 00_EVERVOLT_Hybrid_Inverter_Manager_V1 87_0427 usb update DSP_Primary 618 00513 00_EVERVOLT_Hybrid_Inverter_Prim...

Page 37: ...gnosis and solution Update File Fail File Upgrade Fault Check if the file and the folder are correct Please contact Panasonic Technical Support Udisk Update Fault U Disk Upgrade Fault Check if the U d...

Page 38: ...ort Faults Diagnosis and solution Inter Com Fault Internal Communication Fault Check the connection between inverter and Smart Box connects normally Or contact Panasonic Technical Support Isolation Fa...

Page 39: ...recorded in an equipment log If the device is not functioning properly or fails any test the device has to be repaired For safety check details refer to Section 2 Safety instruction of this manual Re...

Page 40: ...Transportation Decommissioning The inverters shall be transported used and operated under restricted conditions Panasonic will not provide any service technical support or compensation in case of the...

Page 41: ...imum 24 AWG conductors to connect Pin 7 and Pin 8 labeled 12V and STOP_NO to a suitable emergency stop switch For installing EPO on the inverter follow the below installation instructions Appendix A E...

Page 42: ...Electric meter Grid Backup panel Backup load Combiner box Smart load EVERVOLT Home Battery System 1 Non_backup panel Non_essential load EVERVOLT Home Battery System N N 4 EVERVOLT Home Battery System...

Page 43: ...ric meter Grid Backup panel Backup load Combiner box Smart load Non_backup panel Non_essential load CT EVERVOLT Home Battery System 1 EVERVOLT Home Battery System N N 4 EVERVOLT Home Battery System 2...

Reviews: