background image

Panasonic Eco Solutions Nordic AB 

 

MEW01603  Rev:  - 

EBL512 G3 version 2.0.x, Daily user's manual 

 

Perform monthly test  (H1) 

Not possible for access level / type "Information only". 

 

  Press the Soft key "

Menu

". 

  With the keypad select 0, 1, 2 - - 8 or 9 for a 

User name

  Type the 

Password

 for that user name.  (Six digits.    * * * * * *) 

H1  Perform monthly test 

  Press 

(

 )

.  

    Press 

(

 )

.    The  c.i.e.  buzzer  sounds,  all  the  dots  in  the  display  are 

shown  and  all  LEDs  on  the  front  are  turned  on.    If  the  c.i.e.  has  a 
printer it has made a print out:  

ABC..........Z   abc.........z

.  

  Press 

(

 )

.  Up to four zones can be set in test mode.  Use the keypad 

to type the zone numbers.  

  Press 

(

 )

.  Perform the test.  To end the test, press 

(

 )

.  

    If  the  routing  equipment 

shall  not  be  tested

  press 

(

 )

  and  see 

 

below.  

If  the  routing  equipment 

shall  be  tested

  press  ( 

 )  to  highlight 

  

Yes

    and  press 

(

 )

.    Started  test  is  indicated  by  LED  "Fault  tx 

activated" and after 30 seconds also LED "Fire brigade tx".  After 60 
seconds  (in  total)  the  routing  equipment  test  is  ended  and  the  LEDs 
are turned off.   

 

Press 

(

 )

.   

  Monthly test is completed.  Press 

(

 )

.  

  To leave a menu press 

ESC

.     

  To leave the menu system press the Soft key "

Escape menu

". 

 

 

Menu

Escape

menu

Summary of Contents for EBL512 G3 5000

Page 1: ...User manual MEW01603 Revision Fire alarm system EBL512 G3 EBL512 G3 version 2 0 x Daily user s manual Author Jan Pettersson Date of issue 2013 01 10 Date of rev...

Page 2: ...This page has deliberately been left blank...

Page 3: ...____ 14 7 Present system status H4 __________________ 15 7 1 Disablement U1 _________________________________ 16 7 2 Disablement by time channel U2 ____________________ 16 7 3 Open doors U3 __________...

Page 4: ...ailed and shorter than the Operating Instruction MEW01552 NOTE In the left margin are pictures of the buttons soft keys used in the menu respectively Each picture is only shown one time in each menu n...

Page 5: ...3 Rev EBL512 G3 version 2 0 x Daily user s manual 3 2 Front Front upper light grey part Fire Brigade Panel FBP Front lower dark grey part LEDs and keypad Soft keys Information will be visible above th...

Page 6: ...ccess levels access types Information only will give access to the menus H4 H6 H9 and H10 Building officer will give access to the menus H1 H2 H3 H4 H6 H7 H9 and H10 Described in this document Service...

Page 7: ...rform monthly test H2 Disable or re enable H3 Set calendar and clock H4 Present system status H5 Service H6 FAULT Acknowledge H7 Perform ZONE TEST H8 Maintenance H9 Interlocking outputs and inputs H10...

Page 8: ...has a printer it has made a print out ABC Z abc z Press Up to four zones can be set in test mode Use the keypad to type the zone numbers Press Perform the test To end the test press If the routing equ...

Page 9: ...isablements also the LED Alarm devices and or Fire brigade tx Press the Soft key Menu With the keypad select 0 1 2 8 or 9 for a User name Type the Password for that user name Six digits H1 Perform mon...

Page 10: ...blement to toggle between Zone 000 Zone 000 address 00 Use the keypad to type the Zone or Zone Address Press If Automatically re enablement shall be used press and to highlight Yes accept the suggeste...

Page 11: ...l unit 00 S0 Control unit 00 R0 Control unit 00 expansion board output 0 Use the keypad to type the required data Press A successful disablement is indicated by a beep and a It will also be shown in t...

Page 12: ...Ventilation outputs Extinguishing outputs Interlocking outputs Press and type the control unit number if not All outputs shall be disabled Press A successful disablement is indicated by a beep and a I...

Page 13: ...le see below By default is All alarm devices selected Press A successful disablement is indicated by a beep and a It will also be shown in the Re enable list A not successful disablement is indicated...

Page 14: ...highlight Fault After Fire or Fault is selected press A successful disablement is indicated by a beep and a It will also be shown in the Disabled routing equipment list A not successful disablement is...

Page 15: ...from page 7 B1 Zone or Zone Address Press five times B6 Alert annunciation function Press Disable NOTE To Re enable see below By default is Alert annunciation selected Press A successful disablement...

Page 16: ...ave the menu Press the Soft key Menu With the keypad select 0 1 2 8 or 9 for a User name Type the Password for that user name Six digits H1 Perform monthly test Press two times to highlight menu H3 H3...

Page 17: ...ge back to Print but the printing might continue for a few seconds If the list in the selected menu is empty List is empty will be shown Press the Soft key Menu With the keypad select 0 1 2 8 or 9 for...

Page 18: ...or Fire brigade tx Press The list is dynamic i e you can scroll in the list with or If a printer is available the Soft key Print is shown and can be used to start a print out To leave a menu press ESC...

Page 19: ...4 Sensor values U4 Cont from page 15 U1 Disablement Press three times U4 Sensor values Press Use the keypad to enter the technical number and or press This is a list i e you can scroll in the list wit...

Page 20: ...inter is available the Soft key Print is shown and can be used to start a print out To leave a menu press ESC To leave the menu system press the Soft key Escape menu NOTE Sensors activating SERVICE si...

Page 21: ...rinter is available the Soft key Print is shown and can be used to start a print out Print items from latest hour day week month All Scroll in the list with or and select Press To leave a menu press E...

Page 22: ...Menu With the keypad select 0 1 2 8 or 9 for a User name Type the Password for that user name Six digits H1 Perform monthly test Press five times to highlight menu H6 H6 FAULT Acknowledge Press This...

Page 23: ...cept the fire door outputs The test mode alarm will be automatically reset after approx 10 seconds Press the Soft key Menu With the keypad select 0 1 2 8 or 9 for a User name Type the Password for tha...

Page 24: ...of test mode for a zone is indicated by a beep and it will also disappear from the End test mode list To leave a menu press ESC To leave the menu system press the Soft key Escape menu NOTE After one h...

Page 25: ...a User name Type the Password for that user name Six digits H1 Perform monthly test Press eight times to highlight menu H9 H9 Interlocking outputs and inputs Press A sub menu list C1 C3 will be displ...

Page 26: ...ed deactivated via menu C2 If an interlocking output is activated via its control expression and with latching output selected in EBLWin the output has to be deactivated via this menu Cont from page 2...

Page 27: ...page 23 C1 Activated interlocking outputs inputs Press two times C3 Disable re enable interlocking output Press Disable By default is Interlocking output area 000 point 00 shown Use the keypad to type...

Page 28: ...ith the keypad select 0 1 2 8 or 9 for a User name Type the Password for that user name Six digits H1 Perform monthly test Press nine times to highlight menu 10 H10 Change password Press The User name...

Page 29: ...Panasonic Eco Solutions Nordic AB MEW01603 Rev EBL512 G3 version 2 0 x Daily user s manual 27 12 Revision history...

Page 30: ...This page has deliberately been left blank...

Page 31: ...Panasonic Eco Solutions Nordic AB Jungmansgatan 12 SE 211 19 Malm Sweden Tel 46 0 40 697 70 00 Fax 46 0 40 697 70 99 info pesn eu panasonic com http pesn panasonic se...

Reviews: