Panasonic Eco Solutions Nordic AB
MEW01603 Rev: -
EBL512 G3 version 2.0.x, Daily user's manual
9
5.2
Output (B2)
Up to 200 outputs can be individually disabled via menu B2.
Cont. from
, page 7.
B1 Zone or Zone / Address
Press (
).
B2 Output
Press
(
)
.
Disable output
NOTE!
To Re-enable, see
➓
below.
By default is
Loop unit 000000 output 0
selected. Press the Soft
key "
Change type of disablement
" to toggle between:
Loop unit 000000 output 0
Control unit 00 S0
Control unit 00 R0
Control unit 00 expansion board output 0
.
Use the keypad to type the required data. Press
(
)
.
A
successful
disablement is indicated by a beep and a
"
√
".
It will also be
shown in the
Re-enable list
.
A
not
successful
disablement is indicated by another beep and a
"
X
".
Re-enable
➓
Press the Soft key
"
⇥
"
to toggle between:
Disable output
Re-enable list
.
Press (
) to highlight the output that shall be Re-enabled.
⓫
Press
(
)
. A successful Re-enablement is indicated by a beep and it
will also disappear from the
Re-enable list
.
⓬
To leave a menu press
ESC
.
To leave the menu system press the Soft key "
Escape menu
".
Escape
menu