16
DAILY USER´S MANUAL
•
EBL128 VERSION 2.2.X
•
DOCUMENT NUMBER: MEW01786
•
REVISION: 1
12.
INTERLOCKING OUTPUTS AND INPUTS (H9)
a)
Log on to the c.i.e.
b)
Navigate to menu H9.
c)
Press "A". The sub menu consists of a list (C1 - C5) in which you can scroll. C1 is displayed.
d)
Select a sub menu and press “A”.
12.1.
SUB MENU LIST (C1 – C5)
C1
Activated interlocking outputs /
inputs
This is a list in which you can scroll. Read only.
C2
Activate interlocking output
Use the keypad to specify Area – Point (AA and PP) for the
interlocking output to be activated.
Press "A". The status is changed.
C3
Reset interlocking output
This is a list in which you can scroll. Select the Area – Point for
the interlocking output to be reset.
Press "A" The status is changed.
NOTE!
For the following the output
must
be reset via this menu:
- Interlocking output activated via its control expression and with
latching output selected in EBLWin.
- Interlocking output activated via menu C2.
C4
Disable interlocking output
Press "A". Use the keypad to specify Area – Point (AA and PP)
for the interlocking output to be disabled.
Press "A". The status is changed.
C5
Re-enable interlocking output
This is a list in which you can scroll. Select the Area – Point for
the interlocking output to be re-enabled.
Press "A". The status is changed.
13.
CHANGE PASSWORD (H10)
You can only change the password for the user that is currently logged on to the control unit.
a)
Log on to the c.i.e.
b)
Navigate to menu H10.
c)
Press "A". The user that is currently logged on to the control unit is shown.
d)
Use the keypad to type the old password.
e)
Type the new Password. (Six digits. * * * * * *)
f)
Verify the new password.