
11
DAILY USER´S MANUAL
•
EBL128 VERSION 2.2.X
•
DOCUMENT NUMBER: MEW01786
•
REVISION: 1
Continued
B6
Re-enable zone-address
Select an alarm point (zone-address).
To re-enable the selected alarm point press "A".
B7
Re-enable output
Only disabled types will be shown.Use the keypad to select type of
output:
- 0 = Loop unit output.
- 1 = C.i.e. output S0 or S1.
- 2 = C.i.e. output R0.
- 3 = C.i.e. expansion board output.
Press "A".
Select the output to re-enable. Press "A".
B8
Re-enable all control,
ventilation, exting or
interlocking outputs
Only disabled types will be shown.Use the keypad to select type of
output:
- 0 = Outputs type Control.
- 1 = Outputs type Ventilation.
- 2 = Outputs type Extinguishing.
- 3 = Output type Interlocking.
Press "A".
B9
Disable / re-enable alarm
devices
Select “Alarm devices in normal condition” or “Alarm devices
disabled”.
Press "A". The status is changed.
B10
Disable / re-enable outputs
for routing equipment
The actual status for the output FIRE and FAULT respectively will be
shown. Use the keypad to select:
- 1 = enabled or
- 0 = disabled for the output respectively.
Step right / left with the arrow keys.
Press "A". The status is changed.
B11
Disable / re-enable alert
annunciation function
“Alert annunciation function is in normal operation” or “Alert
annunciation function turned off” will be shown.
Press "A". The status is changed.
The AA function will stay disabled until re-enabled again via this
menu.
NOTE!
Disabled Alert Annunciation function is indicated by LED
"Fault / Disablements Fire brigade tx delay" turned off.