background image

6

Indoor unit (I/D) and Outdoor (O/D) unit are included in Air conditioner 
(A/C unit).

 

The setting contents 
described on pages 6 to 
7 can be set on the main 
menu. 

Adaptor Setting

1

Press 

 .

1

4
5

6

2

3

2

Enter the time for the cloud adaptor to determine the 
communication with the air conditioner has failed.

(Possible input range: 5 to 99 minutes)

3

Enter [Communication interval with A/C unit].

(Possible input range: 5 to 99 minutes)

4

Select either [enable] or [disable] for [Link No.1] and 
[Link No.2] respectively.

5

Select [Minimum pulse input detection time setting].

(30ms,100ms)

6

Press 

 .

• Dialogue will be shown to con

fi

 rm restart.

 

To cancel

Press 

 .

• The input screen will be discarded, and go to the main menu.

Note

• Please take note of the input contents displayed when the OK 

button is pressed.

7

Press 

 .

• The settings are 

applied, and the 
cloud adaptor 
restarts.

7

Attention

• After a certain period of time, a login screen is displayed in the 

web browser. Enter the user name and password again, and go 
to the main menu.

Air Conditioner Setting

1

Press 

 .

1

2

Press 

 .

• Air conditioners connected to the cloud adaptor are detected, and 

the A/C unit list is updated.

 

To change 
the link no. to 
display

Select the link 
no. for

3

2

5

4

3

Check if the connected indoor units are all displayed, 
and con

fi

 rm that the number of the connected outdoor 

units and the number of detected units correspond 
with each other.

 

If some of the indoor units are not displayed/ 
unexpected indoor units are displayed.

Check if wiring is properly done, or the address setting for air 
conditioners is correct.

After correction, redo from step 2.

4

Enter the central address.

 

To assign manually

Select the central address text 
box of the indoor unit on the   
[A/C Unit List] screen, and 
enter it.

 

To assign automatically

Press

 

 .

• Values that have been unused 

within the same link no. are 
input in the blank 

fi

 eld in 

ascending order.

5

Press 

 .

• The input central address is applied to all the indoor units.

Attention

• Be sure to set the central 

address for the indoor unit to 
control and monitor using the 
cloud adaptor.

Note

• If the text box is blank or any 

duplication is present between 
main indoor units, an alarm is 
displayed.

Air Conditioner Test Operation

1

Check if 

 

and 

 

properly work. 

2

3

1

2

Press 

 .

• Check if pressing the button switches the ON/OFF display in the 

control 

fi

 eld of the corresponding indoor units and the ON/OFF 

operation of the actual indoor units.

• Check all the indoor units for proper operation.
• Check the status while communicating over a radio device with 

the PC operator.

3

Press 

 .

• The main menu is displayed.
• If [Con

fi

 rm central address] button is not pressed after changing 

the central address, a con

fi

 rmation screen is displayed.

Selecting [YES] discards the changed contents.

Setting 

(continued)

CZ-CFUSCC1̲工説̲E.indd   6

CZ-CFUSCC1̲工説̲E.indd   6

2016/02/17   15:50:55

2016/02/17   15:50:55

Summary of Contents for CZ-CFUSCC1

Page 1: ...or death This controller is strongly recommended to be installed with Earth Leakage Circuit Breaker ELCB or Residual Current Device RCD Otherwise it may cause electrical shock and fire in case of equipment breakdown or insulation breakdown Earth Leakage Circuit Breaker ELCB must be incorporated in the fixed wiring in accordance with the wiring regulations The Earth Leakage Circuit Breaker ELCB mus...

Page 2: ...od consult the network administrator Installation Precautions Installation Location Avoid the following locations for installation Under direct sunlight Location near heat source Location where the controller will be splashed with water or affected by dampness or humidity Uneven surface Location that is subject to excessive vibration or physical impacts Fixing screws may come off and the controlle...

Page 3: ...H05RN F or H07RN F which conform to CENELEC HAR rating specifications or use the wiring based on IEC standard 60245 IEC57 60245 IEC66 Total Wire Length 30 m or less Inter Unit Control Wiring Type of wiring Use a flexible shield wiring of 0 5 to 2 mm2 Total Wire Length 1000 m or less Number of connectable units and devices Up to total of 100 units and devices can be connected Indoor unit Up to 64 u...

Page 4: ...oltage DC5 V 10 Contact allowable current Max 10 mA Pulse input 1 Pi1 8 Pulse input 2 Pi2 9 Pulse input 3 Pi3 10 Common COM 7 COM Pulse width 30 msec or more 100 msec or more Pulse interval 1 sec or more Connecting Wiring When connecting external equipment refer to the Connecting to external equipment section below U1 U2 0 1 2 3 4 5 6 20 U1 U2 TB1 TB2 Power supply wiring Power supply terminal boar...

Page 5: ...tion section back cover page 5 Start up the PC and set if the network settings as follows IP address 192 168 1 100 Subnet mask 255 255 255 0 Default gateway 192 168 1 254 6 Enter the following URL in the Web browser and access the cloud adaptor https 192 168 1 1 Recommended Web browser specifications Internet Explorer IE 11 The login screen appears If the login screen does not appear Check if the ...

Page 6: ... and the number of detected units correspond with each other If some of the indoor units are not displayed unexpected indoor units are displayed Check if wiring is properly done or the address setting for air conditioners is correct After correction redo from step 2 4 Enter the central address To assign manually Select the central address text box of the indoor unit on the A C Unit List screen and...

Page 7: ...ctions 1 2 When DHCP is used in the network environment Add a check mark for DHCP Enabled When other than the above Remove the check mark for DHCP Enabled and enter IP address Subnet mask and Default gateway of the cloud adaptor 2 3 When the DNS server information can be automatically obtained in the current environment Add a check mark for Obtain DNS server address automatically When other than t...

Page 8: ...Orange Red Green Lighting Blinking slow once per about 2 seconds Blinking fast once per about 1 second Off LED Status and Solution The cloud adaptor is in the maintenance mode page 7 After maintenance change it to the operation mode Communication failure Both Link 1 and 2 Check if the inter unit control wiring between the air conditioners and the cloud adaptor is correct Both Link 1 and 2 Communic...

Reviews: