10
Zone address switches
Use these to set the zone addresses.
ON/OFF controller main/sub selection switch
This is normally used at the main (OFF) setting.
When the ON/OFF controller is to be used by a main
unit and a sub unit (2 units) in one zone, set one unit to
main (OFF) and the other unit to sub (ON).
OFF: ON/OFF controller operates as main controller.
ON: ON/OFF controller operates as sub-controller.
Central control main/sub selection switch
(OFF: main, ON: sub)
This is normally used at the main (OFF) setting.
Set it to sub (ON) when a communication adapter,
intelligent controller or system controller is to be used
concurrently.
Group inhibited/all indoor unit control permitted
selection switch
Use these to switch between the group inhibited and
all indoor unit control permitted statuses for each of the
four groups.
All indoor run/stop selection switch
Use this to select the units to be run or stopped when
the ALL ON. or ALL OFF.O button has been pressed.
OFF : All indoor unit
ON: inhibited indoor unit
*All switches are OFF position at shipment.
1
2
3
4
5
6
7
8
DIPSW1
DIPSW1
ON
OFF
Fig. 5
1
2
1(Central Adress 1-16)
OFF
OFF
2(Central Adress 17-32)
ON
OFF
3(Central Adress 33-48)
OFF
ON
4(Central Adress 49-64)
ON
ON
NOTE
Set the zone address switch of the sub ON/
OFF controller to the same address as the
main ON/OFF controller.
One ON/OFF controller must always be set
as the main ON/OFF controller.
•
•
5
6
7
All indoor unit control permitted
OFF
OFF
OFF
1-16 Group inhibited
ON
OFF
OFF
5-16 Group inhibited
OFF
ON
OFF
9-16 Group inhibited
ON
ON
OFF
13-16 Group inhibited
OFF
OFF
ON
CZ-ANC2̲eng.indd 10
CZ-ANC2̲eng.indd 10
2010/12/27 19:03:33
2010/12/27 19:03:33