Power Supply Wiring

•  Power supply voltage : AC24 V 60 Hz 1-PH
• Voltage 

fl

 uctuation : ±10 % or less

•  Electric power consumption : 20 W
•  Be sure to use a dedicated line for power source.

 

Type of wiring

• Use a 

fl

 exible wiring of AWG #17 - AWG #14

 

Total Wire Length

•  99 ft. (30 m) or less

 

Inter-Unit Control Wiring

 

Type of wiring

• Use a 

fl

 exible wiring of AWG #20 - AWG #14

• No polarity

 

Total Wire Length : 

3280 ft. (1000 m) or less

 

Number of connectable units and devices :

(

 P.1 “Speci

fi

 cations”)

Attention

•  When using the unit at a location susceptible to electrical 

noise, use a 

fl

 exible shield wiring (one side grounding).

 

Communication Adaptor Control Wiring

(When connecting a Communication Adaptor)

 

Polarity (

+

/

-

) present

 

Number of connectable Communication Adaptor

•  up to 7 units

 

For the type of wiring and total wiring length, 
see “Installation Instructions” supplied with the 
Communication Adaptor.

 

External I/O Wiring

(When connecting external equipment)

 

Type of wiring

• Use a 

fl

 exible wiring of AWG #20 - AWG #14

 

Wire Length : 

66 ft. (20 m) or less

Attention

•  When using the unit at a location susceptible to electrical 

noise, use a 

fl

 exible shield wiring (one side grounding).

 

LAN Cable 

(When connecting to a network)

 

Type of wiring

•  Category 5 or above straight cable

 

Wire Length : 

328 ft. (100 m) or less

Preparations for Wiring

Basic Wiring Diagram

U1 U2

U1

U2

+

U1 U2

U1 U2

L

N

U1 U2

U1 U2

+

N

L

Power source

(AC 120 V 60 Hz)

Outdoor unit

This unit

Power trans

*3

(AC 24 V 60 Hz)

[

fi

 eld supplied item]

Power supply wiring 

Communication 

Adaptor

Communication 

Adaptor

control wiring

• Polarity 

present

Inter-unit control 

wiring
• No polarity

Outdoor 

unit

Indoor unit

Indoor unit

1-1

Indoor unit

1-2

*3:  The AC 24 V power from an energy limited Class II 

power source must be provided to the equipment.

1.  Turn the circuit breaker off before connecting the wiring
2.  How to Attach the Ring Pressure Terminal

 

For power supply wiring 

Process the end of each wiring, and 
attach the ring pressure terminal (

fi

 eld 

supplied item).

 

For shield wiring 

Process the end of the each wiring and attach the ring 
pressure terminal (

fi

 eld supplied item).

 Remove wiring coat.

Shield mesh

 Cover with the tape. 

Strip

Shield mesh

Insulation tape

  Attach ring pressure 

terminal.

Ring pressure 

terminal

3. Remove the 

power switch 
cover

4. Wiring

 Connect the power supply wiring.

• Do not over-tighten. (The screw may be damaged.)

 Connect the inter-unit control wiring.

 

When using the shield wiring, connect the shield part 
of the shield wiring to No. 0 (FG

*4

) of the signal terminal 

board (TB2).

*4: Functional Ground

• Do not over-tighten. (The screw may be damaged.)

 

There is no polarity.



Connect the Communication Adaptor control wiring.

 

Make sure the polarities (+/-) are correct.

Attention

• Read the “Installation Instructions” supplied with the 

Communication Adaptor.



Connecting external equipment.

Attention

• See “Connecting to External Equipment”  (P.4).



Fix the power supply wiring and other communication 
wirings with the clamper (supplied) securely.

(Do not apply tensile force on the terminal connection part.)



Connect the LAN cable.

 After all wiring arrangements are complete, turn 

the circuit breaker on.

• Before power on, measure the voltage of the power supply 

terminal board, and check it for the speci

fi

 ed voltage. 

Turning the power on with a voltage other than the 
speci

fi

 ed one may blow the fuse. If this occurs, no power 

is supplied, and this unit may need to be replaced.

Strip

Ring 

pressure 

terminal

Screw

Screw

Power switch cover

Power-in port

Wiring 

CZ-256ESMC2U̲工説北米̲冊子.indd   3

CZ-256ESMC2U̲工説北米̲冊子.indd   3

2016/08/03   16:16:50