Trouble
Check
Result
Cause
Remedy
Compressor won’t run
(Fan run).
•
•
•
•
Temperature
setting.
•
•
•
•
RESISTANCE
between Terminal
and the
Compressor Body.
•
•
•
•
RESISTANCE
between Terminals.
•
•
•
•
Overload Protector.
•
•
•
•
Capacitor
Compressor.
•
•
•
•
Thermostat.
•
•
•
•
Main Control
Switch.
•
•
•
•
Higher than room
temp.
•
•
•
•
Shorted.
•
•
•
•
Shorted.
•
•
•
•
Infinity between
Terminals.
•
•
•
•
OHM Meter doesn’t
deflect.
•
•
•
•
No click heard.
•
•
•
•
No contacts at
Position Shown.
•
•
•
•
Winding Coil touched to
the compressor shell.
•
•
•
•
Rear Shorted or Burnt out.
•
•
•
•
Rear Shorted or Burnt out.
•
•
•
•
Overload Protector defect.
•
•
•
•
Capacitor defect.
•
•
•
•
Thermostat defect.
•
•
•
•
Main Control Switch defect.
•
•
•
•
Set it lower.
•
•
•
•
Replace Compressor.
•
•
•
•
Replace Compressor.
•
•
•
•
Replace Overload
Protector.
•
•
•
•
Replace Capacitor
Compressor.
•
•
•
•
Replace Thermostat.
•
•
•
•
Replace Main Control
Switch.
Air Swing won’t run.
•
•
•
•
Air Swing Switch.
•
•
•
•
Resistance
between wires.
•
•
•
•
OFF position.
•
•
•
•
No contact at
position.
•
•
•
•
OHM Meter doesn’t
deflect.
•
•
•
•
Open circuit.
•
•
•
•
Shorted or open circuit.
•
•
•
•
Set it ON.
•
•
•
•
Replace Air Swing Switch.
•
•
•
•
Replace Air Swing Motor.
Insufficient cooling or
heating.
•
•
•
•
Temperarute
Setting.
•
•
•
•
Ventilation door
open.
•
•
•
•
Air filter dirty.
•
•
•
•
Location of
installation.
•
•
•
•
Evaporator /
Condenser Coil
obstructed.
•
•
•
•
Unit capacity for
the room too small.
•
•
•
•
Temperature
difference and
running current.
•
•
•
•
Higher than room
temperature
•
•
•
•
Open.
•
•
•
•
Clogged or dirty.
•
•
•
•
Sunlight hitting
outdoor side.
•
•
•
•
Obstacles.
•
•
•
•
Clogged or dirty.
•
•
•
•
Not satisfied.
•
•
•
•
REFER TO
PERFORMANCE
EVALUATION.
•
•
•
•
Reduces capacity.
•
•
•
•
Restricted air circulation.
•
•
•
•
Restricted Heat Exchanger.
•
•
•
•
Restricted Heat Exchanger.
•
•
•
•
Restricted air circulation.
•
•
•
•
Leakage of refrigerant or
refrigeration system is
blocked.
•
•
•
•
Set it lower.
•
•
•
•
Close Ventilation door.
•
•
•
•
Clean or replace Air Filter.
•
•
•
•
Consider building an
AWNING.
•
•
•
•
Remove obstacles or
reinstall unit.
•
•
•
•
Clean the coils.
•
•
•
•
Replace the unit with
bigger one.
•
•
•
•
Locate repair leak.
•
•
•
•
Flush refrigeration cycle.
Noise.
•
•
•
•
Source of Noise
•
•
•
•
Vibration.
•
•
•
•
Intermittent Noise.
•
•
•
•
Faulty installation.
•
•
•
•
Fan hitting objects.
•
•
•
•
Refrigerant tubing touching
each other.
•
•
•
•
Fan splashing Drain Water
•
•
•
•
Reinstall unit or Reinforce
the installation.
•
•
•
•
Adjust Fan position or
remove foreign materials.
•
•
•
•
About 1/2” Clearance
needed.
•
•
•
•
Remove drain plug and
mount a drain pan to
remove the water.
•
•
•
•
Set the Drain outlet
downward, so that the
Drain water can run off
Water dripping inside
room.
•
•
•
•
Unit installation.
•
•
•
•
Drain Tray-
Styrofoam pieces
blocking drain
channel.
•
•
•
•
Tilted to inside room.
•
•
•
•
Clogged.
•
•
•
•
Restricted run off.
•
•
•
•
Clogged or blocked.
•
•
•
•
Tilt unit to outside slightly.
•
•
•
•
Remove the foreign
materials.
Frozen Evaporator
•
•
•
•
Temperature
setting.
•
•
•
•
Air filter /
Evaporator.
•
•
•
•
Temperature
difference and
running current.
•
•
•
•
Set too low for
ambient conditions.
•
•
•
•
Clogged or Dirty.
•
•
•
•
REFER TO
PERFORMANCE
EVALUATION.
•
•
•
•
Outdoor temperature low
(Night time).
•
•
•
•
Restricted air circulation.
•
•
•
•
Leakage of refrigerant or
refrigeration system is
blocked.
•
•
•
•
Set the Main Control Knob
to Fan to melt ice and set
the Temperature control to
higher temperature.
•
•
•
•
Clean Air filter /
Evaporator.
•
•
•
•
Locate and repair leak.
•
•
•
•
Flush refrigeration cycle.
No
heating
(Fan
and
Compressor run).
•
•
•
•
Reversing
valve
coil.
•
•
•
•
Reversing valve.
•
•
•
•
Infinity between coil.
•
•
•
•
Resistance
between
reversing valve coil.
•
•
•
•
Replace
reversing
valve
coil.
•
•
•
•
Replace reversing valve.
Frozen Condenser
•
•
•
•
Outdoor
ambient
temperature
•
•
•
•
Heating operation at
low outdoor ambient
temperature
•
•
•
•
Outdoor
ambient
temperature is low.
•
•
•
•
Set Main Control Switch to
Fan to melt ice.
7
CW-A90VE / CW-A120VE