3 Refrigeration Cycle Diagram
3.1. CW-A90VE & CW-A120VE
Note: Indoor temperature at 27°C (DB), 19°C (WB) and Outdoor at 35°C (DB), 24°C (WB) for Cooling & indoor temperature at
20°C (DB), 15.5°C (WB) and Outdoor at 7°C (DB), 6°C (WB) for Heating.
3.1.1. Cooling
CW-A90VE
CW-A120VE
Item
Pressure (MPa)
Temperature (°C)
Pressure (MPa)
Temperature (°C)
A
1.81 ~ 2.01
67 ~ 82
2.09 ~ 2.28
67 ~ 82
B
1.76 ~ 1.96
38 ~ 48
2.04 ~ 2.23
37 ~ 47
C
0.51 ~ 0.57
7 ~ 12
0.53 ~ 0.59
8 ~ 13
D
0.48 ~ 0.54
10 ~ 17
0.50 ~ 0.56
8 ~ 15
3.1.2. Heating
CW-A90VE
CW-A120VE
Item
Pressure (MPa)
Temperature (°C)
Pressure (MPa)
Temperature (°C)
A
0.40 ~0.46
0 ~ 5
0.37 ~ 0.43
-1 ~ 4
B
0.43 ~ 0.49
-1 ~ 4
0.40 ~ 0.46
0 ~ 5
C
1.52 ~ 1.72
31 ~ 41
1.51 ~ 1.71
31 ~ 41
D
1.57 ~ 1.76
42 ~ 52
1.56 ~ 1.75
41 ~ 51
4