Outdoor Unit

5

Panasonic

Anti-reverse Protection

To protect the compressor from reverse

rotation when power off suddenly.

Overload Protector

The 2-step Overload Protector is to protect

the compressor when

1)Temperature of compressor reaches

2)High temperature or current enters into the

compressor

145

60-seconds Test Operation Control

Once the compressor is activated, it does not

stop for 60 seconds. It stops immediately with

remote control ON/OFF button.

Anti-freezing operation for outdoor unit(during

Heating Mode Operation only)

Temperature of the condenser is tested by TRS.

(For PA12DKD only)

Deicing Control

Overload Protection Control

When the temperature of evaporator

reaches 51

,outdoor fan stops,and will

restart when the temperature of evaporator

declines to 49

.

When the temperature of evaporator

reaches 65

,compressor will stop.

4-way Valve Control

If the unit is stopped during Heating

Operation,the 4-way valve will remain in

heating mode operation for 5 minutes.

(For PA12DKD only)

(For PA12DKDonly)

CS-PC12DKD / CU-PC12DKD / CS-PA12DKD / CU-PA12DKD

Summary of Contents for CU-PC12DKD

Page 1: ...nyone else could result in serious injury or death 1 Features 2 2 Functions 3 3 Product Specifications 6 4 Dimensions 10 5 Refrigeration Cycle Diagram 12 6 Block Diagram 13 7 Wiring Diagram 15 8 Opera...

Page 2: ...ncy Air Quality Indicator Comfort Environment Air filter with function to reduce dust and smoke Auto Restart Control Automatically restart after power failure 12 hour Timer Setting CS PC12DKD CU PC12D...

Page 3: ...emperature Setting Temperature Setting 16 to 30 Auto Operation Timer Operation Selection Stop Start Operation Control set the ON OFF Timer hourly later Set Cancel Timer Operation Set timer Cancel the...

Page 4: ...ssing this button for 15seconds to start or end the Demonstration Mode Auto Switch Button Air quality Green Orange Red Anti freezing Control for the Evaporator Cooling or Soft Dry Operation Warm Booti...

Page 5: ...h remote control ON OFF button Anti freezing operation for outdoor unit during Heating Mode Operation only Temperature of the condenser is tested by TRS For PA12DKD only Deicing Control Overload Prote...

Page 6: ...t Width Depth Type Motor Type Rated output type Motor type Fan Speed Low Med High Rated Output Input Inch Inch Inch Inch mm m mm mm mm kg W W W rpm rpm rpm CS PA12DKD CU PA12DKD 3 35 3 40 3 80 3 85 1...

Page 7: ...igerant Circulation Control Device Compressor Capacitor Fan Motor Capacitor Unit CS PA12DKD CU PA12DKD Length Circulation Inner Diameter mm c c g mm L min mm F V F V Evaporator Copper Slot type Plate...

Page 8: ...R Starting Current Inner Diameter Length Height Width Depth Type Motor Type Rated Output Type Motor Type Fan Speed Low Med High Rated Output Input Inch inch Inch inch mm m mm mm mm kg W W W rpm CS PC1...

Page 9: ...y Air Filter Refrigerant Circulation Control Device Compressor Capacitor Fan Motor Capacitor Unit CS PC12DKD CU PC12DKD Length Circulation Inner Diameter mm c c g mm L min mm F V F V Evaporator copper...

Page 10: ...61 165 49 420 50 Front View Back View Installation Plate Hook Gas Side Liquid Side Drain Port 790 Air intake 280 49 61 5 Side view 183 Air outlet Left Piping Hole Right Piping Hole 100 OFF MODE TEMP...

Page 11: ...Outdoor Unit Unit mm 11 CS PC12DKD CU PC12DKD CS PA12DKD CU PA12DKD More than 10cm More than 100 cm 780 48 570 34 5 289 540 18 320 352 16 291 274 INVERTER More than 10cm Front View Side View Top View...

Page 12: ...SENSOR INTAKE AIR SENSOR PIPING SENSOR PIPING SENSOR PIPING SENSOR PIPING SENSOR CS CU PC12DKD AIR QUALITY SENSOR 12 CS PC12DKD CU PC12DKD CS PA12DKD CU PA12DKD INTAKE AIR SENSOR PIPING SENSOR 4 way...

Page 13: ...M F M 2 CR201 3 4 1 RY HOT SSR202 SSR201 FUSE RY PWR OUTDOOR UNIT Receiver Remote Control F M 4 Valve Compressor Sensor Indicator Piping Sensor O L P INDOOR UNIT 13 POWER SUPPLY AC220V 230V 50Hz CS P...

Page 14: ...F M SSR201 SC FUSE RY PWR F M Compressor CS PC127DKD CU PC12DKD Receiver Remote Control Sensor Indicator 14 POWER SUPPLY AC220V 230V 50Hz CS PC12DKD CU PC12DKD CS PA12DKD CU PA12DKD O L P...

Page 15: ...SUPPLY CORD AC 220V 230V 50Hz AC 220V 230V 50Hz STEPPING MOTOR OUTDOOR UNIT TERMINAL BOARD 1 L 2 N 3 4 1 L 2 N 3 4 OUTDOOR UNIT R RED BL BLACK B BLUE BR BROWN O ORANGE GRY GREY G GREEN Y YELLOW W WHIT...

Page 16: ...G MOTOR FAN MOTOR O L P Y Y FAN MOTOR B R CAPACOTOR COMPRESSOR B B R Y G Y CAPACOTOR COMPRESSOR TERMINAL YELLOW RED S BLUE R C TRADE MARK R RED BL BLACK B BLUE BR BROWN O ORANGE GRY GREY G GREEN Y YEL...

Page 17: ...Freezing Control If temperature of evaporator is lower than 2 continuously for 4 minutes the compressor will cease to prevent the evaporator from freezing Fan speed setting will not be changed When t...

Page 18: ...erature reaches the set temp on remote control and then Soft Dry will be activated During Soft Dry Mode the fan of indoor unit will operate at super low speed The soft dry mode will run for less than...

Page 19: ...n Operation Indicator 6 6 6 1 6 1 1 4 Operation status Time Operate Stop Cooling mode operation Soft Dry Mode operation Super Low Super Low Super Low Super Low Low 1 5 Cooling mode operation activated...

Page 20: ...ion with the speed at super low Compressor Stops Compressor Restarts 4 minutes later Indoor Heat Exchanger 65 Compressor Stops Compressor Restarts 3 minutes later Compressor runs 5 min T 5 last for 2...

Page 21: ...select Auto Fan Speed mode Indoor Fan Speed is between Me and Slo Me Lo Lo S Lo S Lo 45 41 34 30 45 41 34 30 38 30 28 15 38 30 28 15 Temperature of heat exchanger Temperature of heat exchanger Stop Ti...

Page 22: ...ime Delay Td deicing won t ends immediately Deicing Operation Time T 3 min 3min T 7min 7 min T 9min T 9min Deicing Operation Time T 3 min 3min T 7min 7 min T 9min T 9min Td s 0 60 120 180 Td s 0 60 12...

Page 23: ...d deicing timer l m Warm booting control m r Overload control Out door fan stop for 60 accumulatively 20 20 51 Outdoor Heat Exchanger Outdoor Heat Exchanger 10 20 Basic time Compressor Indoor fan Outd...

Page 24: ...has been determined the mode does not change However Soft Dry mode operation includes cooling mode operation If automatic mode operation is started while the unit is operating operation will continue...

Page 25: ...r quality sensor is always on during the operation of the air conditioner When the air conditioner stops The air conditioner is on standby the air conditioner will provide power to the air quality sen...

Page 26: ...l 2 Red 0 1 2 G1 0 85 G2 0 60 Set the sensitivity number of the air quality sensor as 2 Standard A i r q u a l i t y becomes better A i r q u a l i t y becomes worse Detecting of air quality When the...

Page 27: ...ity control m ode 2 The previous sensitivity setting will be displayed in the temperature display 3 Press or button on the remote control to change the sensitivity 0 Turn off the air quality indicator...

Page 28: ...O N O F F ON OFF 5 seconds 5 seconds 5 seconds 5 seconds 5 seconds 5 seconds 5 seconds Red Orange green Orange Green Orange Red 10 seconds 20 seconds 8 8Ventilator Interlocking Unit Control Optional...

Page 29: ...FF TIMER SET TIMER OFF pressed For some reason Ex The signal of the remote control does not reach the signal receiver of the indoor unit the display of the remote control will not correspond with the...

Page 30: ...uver When temperature of indoor heat exchanger reaches 38 during heating mode operation if temperature falls to 35 airflow direction will change from the lower limit to horizontal Angles Of Airflow Di...

Page 31: ...ecified parts for installation Otherwise it will cause the set to fall water leakage fire or electrical shock 4 Install at a strong and firm location which is able to withstand the set sweight If the...

Page 32: ...e there is ease for access for the power disconnection in case of emergency In some countries permanent connection of this room air conditioner to the power supply is prohibited 1 Power supply connect...

Page 33: ...control Battery 1 5 1 2 5 Drain elbow 1 6 Connecting Wire Connector hr DELA Y OFF ON AUTO AUTO FAN SPEE D AIR SWIN G MOD E TEM P OFF ON TIM ER ON SET AIR SWIN G OFF CAN CEL FAN SPE ED AUT O COO L DRY...

Page 34: ...ding to the arrows marked on the lower left and right side of the installation plate The meeting point of the extended line is the centre of the hole Another method is by putting measuring tape at pos...

Page 35: ...CS PC12DKD CU PC12DKD CS PA12DKD CU PA12DKD 35...

Page 36: ...os are the same to the indoor s respectively Earth lead wire shall be longer than the other lead wires as shown in the figure for the electrical safety in case of the slipping out of the cord from the...

Page 37: ...occur at the tenth sec in order to indicate the ON OFF changed over of remote control receiving sound 9 3 OUTDOOR UNIT 9 3 1 SELECT THE BEST LOCATION Refer to Select the best location section 9 3 2 IN...

Page 38: ...r approximately ten minutes 4 Close the Low side valve of the charging set and turn off the vacuum pump Make sure that the needle in the gauge does not move after approximately five minutes Note BE SU...

Page 39: ...3 6 CONNECT THE CABLE TO THE OUTDOOR UNIT 1 Remove the control board cover from the unit by loosening the screw 2 Connecting cable between indoor unit and outdoor unit shall be approved polychloropren...

Page 40: ...ween the intake temperature and the discharge is more than 8 C during cooling operation or CHECK ITEMS Is there any gas leakage at flare nut connections Has the heat insulation been carried out at fla...

Page 41: ...clockwise With cap Pumping down Transferring Closed Open Open Clockwise Counter clockwise Connected manifold gauge Evacuation Servicing Open Open Open With vacuum pump Charging Servicing Open Open Ope...

Page 42: ...moves from 0 cmHg 0 Mpa to 76 cmHg 0 1 Mpa Then evacuate the air for approximately 10 minutes 4 Close the valve of the Low side of the charging set and turn off the vacuum pump Make sure that the nee...

Page 43: ...y to purge air from the charge hose 5 Set the 2 way valve to the close position 6 Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 2 G 0 1Mpa If the unit cannot be...

Page 44: ...LEAKAGE 7 Tighten the service port caps of both the 3 way valve and the 2 way valve at a torque of 18 N m with a torque wrench 8 Remove the valve caps of both the valves Position both of the valves to...

Page 45: ...he refrigerant until the needle indicates 0 no refrigerant is remaining 4 5 Open the valve Low side on the charge set and discharge the refrigerant until the gauge indicates 0 05 MPa 0 5 kg cm G to 0...

Page 46: ...uum of 4 mmHg or less 3 4 Vacuum oil If the vacuum pump oil becomes dirty or depleted replenish as needed Connect the vacuum pump to the charge set s centre hose Evacuation for approximately 1 hour Cl...

Page 47: ...e charged with the specified amount of refrigerant it can be charge with a little at a time approximately 150g each time while operating the air conditioner in the cooling cycle However one time is no...

Page 48: ...moval Procedure For Intake Grille 1 Remove the two caps at the discharge port right and left Fig 3 2 Release the two screws under the both caps Fig 4 Removal Procedure For Front Grille Cap Fixing Scre...

Page 49: ...plate Fig 10 Fig 10 2 Pull out the discharge grille slightly Fig 11 Fig 11 CS PC12DKD CU PC12DKD CS PA12DKD CU PA12DKD 3 Break off the earing release the holder slightly Be sure to avoid cracking of...

Page 50: ...12 Release the two fixing screws disassembly the fixing board from evaporator on the left side of the evaporator and pull out the whole evaporator 2 Loose the fixing screw of the cross flow fan Fig 1...

Page 51: ...rature More than 8 15 minutes afte an operation is started at the cooling mode Normal Measuring electric current during operation Measuring gas side pressure Less than 14 at the heating mode Value of...

Page 52: ...es approximately 80 lower than the normal level The discharge tube of the compressor becomes abnormally hot normally 70 90 The difference between high pressure and low pressure becomes almost zero Ele...

Page 53: ...difference Temperature setting Intake Air temperature 34 32 30 28 26 24 22 20 18 16 16 18 20 22 24 26 28 30 34 32 30 28 26 24 22 20 18 16 16 18 20 22 24 26 28 30 13 Technical Data Heating mode Only f...

Page 54: ...3 0 70 0 65 0 60 0 55 0 50 I Current A Q Cooling capacity kW LP Gas side piping pressure Mpa O Outlet air temp Outdoor temp Condition Room temp 27 19 Cooling operation at high speed Piping length 5m 2...

Page 55: ...35 1 3 4 37 2 27 34 17 5 25 10 32 33 29 26 31 33 32 30 11 13 9 12 28 22 19 15 8 23 14 20 21 24 16 OFF MODE TEMP OFF O N ON CANCEL SET STD TIMER FANSPEED AIR SWING 36 55 16 CS PC12DKD CS PC12DKD CU PC...

Page 56: ...CWH14C4487 15 CONTROL BOARD 1 CWH102265 CWH102265 16 PARTICULAR PIECE 1 CWD932493J CWD932493J 17 POWER SUPPLY CORD COMPLETE 1 CWA20C2362 CWA20C2362 19 MAIN PCB 1 CWA743751 CWA743750 20 INDICATOR COMPL...

Page 57: ...16 Exploded View CU PA12DKD 57 36 33 35 34 37 4 5 3 2 6 7 28 26 24 27 25 38 23 11 29 22 21 20 32 14 8 10 9 1 13 15 17 12 19 31 30 16 18 CU PC12DKD CS PC12DKD CU PC12DKD CS PA12DKD CU PA12DKD...

Page 58: ...2 WAY VALVE 1 CWB021247 CWB021260 17 3 WAY VALVE 1 CWB011312 CWB011323 19 STRAINER 1 CWB111026 CW B111026 20 OVER LOAD PROTECTOR 1 CWA121218 CWA121218 21 TERMINAL COVER 1 CWH17006 CWH17006 22 NUT TERM...

Page 59: ...CN STM1 PH5 WHT CN STM2 PH5 YLW L1 A431036 C17 0 047u 250VAC ECQ 1 1 2 2 26 ZNR3 ERZV10D511 SSR1 D11 R44 D10 C23 24 30 31 32 33 34 35 36 37 10 11 12 13 14 15 16 B1HBGFF0000 49 2SC3441 R37 270 2WS 48 R...

Page 60: ...D1 A54D5 1MTB1 IC6 B1HBGFF00005 R54 10K 16IC6A 151C6B 141C6C 131C6D 121C6E 111C6F 101C6G RY HOT 1 2 3 4 5 6 7 127 126 125 121 122 123 124 1 4 4 4 SSR3 SSR2 SSR1 3 3 3 4 12V R53 33K 1K R52 BZ A48TFM25E...

Page 61: ...NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE A56G3MC202PL K6B1AGA00073 NONE NONE NONE NONE NONE NONE NONE NONE ERJ3EKF1582V ERJ3GEYJ102V A431090 A67C5001 NONE NONE NONE NONE A67C3830 A67C3843 BOA...

Page 62: ...62 CS PC12DKD CU PC12DKD CS PA12DKD CU PA12DKD...

Page 63: ...63 CS PC12DKD CU PC12DKD CS PA12DKD CU PA12DKD...

Reviews: