13.15 Valve close detection control
This control detects 3-way valve close condition to prevent damage to refrigerant cycle.
Start
conditions:
o
For all connected indoor units, if Indoor intake temperature — indoor piping temperature are between 28.4°F
(-2°C) and 35.6°F (2°C) continuously for 5 minutes after compressor ON at first cooling operation.
o
The first cooling operation is defined as cooling operation is ON for less than 8 minutes after new installation
or after pump down.
Control
content
o
During this control, compressor stop, indoor units’ Timer LED will blink. (“F91” is indicated at indoor units)
Error reset can be done by power supply reset or reset by using remote control.
13.16 Compressor discharge high pressure protection control
This control protect by using high pressure switch during operation.
Start
conditions
o
High pressure switch is activated (from normally close to open) when outdoor operation mode is cooling or
heating during compressor running.
Control 1 content
o
Compressor stop when high pressure switch is opened and restart after high pressure switch closed. If this
condition happen 4 times within 30 minutes, “F94” is indicated.
o
After 30 minutes, counter is reset if this condition does not happen for 4 times.
Control 1 stop conditions
o
Power supply reset
o
Reset by using remote control
Summary of Contents for CU-5E36QBU-5
Page 26: ...26 3 Dimensions ...
Page 27: ...27 4 Refrigeration Cycle Diagram ...
Page 28: ...28 5 Block Diagram ...
Page 30: ...30 7 Electronic Circuit Diagram ...
Page 31: ...31 8 Printed Circuit Board 8 1 Main Printed Circuit Board ...
Page 32: ...32 8 2 Noise Filter Printed Circuit Board 8 3 Display Printed Circuit Board ...
Page 33: ...33 9 Installation Information 9 1 Check Points ...
Page 50: ...50 ...
Page 51: ...51 ...