![Panasonic CU-5E36QBU-5 Service Manual Download Page 35](http://html.mh-extra.com/html/panasonic/cu-5e36qbu-5/cu-5e36qbu-5_service-manual_1508347035.webp)
35
Outdoor Unit Installation Guidelines
Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the installation
guidelines below.
For any of the below installation patterns, the wall height on the exhaust side should be 47-1/4" (1200 mm) or
less.
10.2 Install The Outdoor Unit
After selecting the best location, start installation
to Indoor/Outdoor Unit Installation Diagram.
1. Fix the unit on concrete or rigid frame firmly
and horizontally by bolt nut (ø13/32"
(ø10 mm)).
2. When installing at roof, please consider strong
wind and earthquake.
Please fasten the installation stand firmly with
bolt or nails.
Model A
B
C
D
CU-5E36***
24-13/32"
(620 mm)
6-11/16"
(170 mm)
25/32"
(20 mm)
14-31/32"
(380.5 mm)
10.3 Connect The Piping
Remove the cabinet side plate (metal) from the
unit by loosening six screws.
Connecting The Piping To Outdoor Unit
Decide piping length and then cut by using pipe
cutter.
Remove burrs from cut edge. Make flare after
inserting the flare nut (locate at valve) onto the
copper pipe.
Align center of piping to valves and then tighten
with torque wrench to the specified torque as
stated in the table.
Do not over tighten, over tightening may cause gas leakage
Piping size
Torque
1/4" [6.35 mm]
[18 N•m (1.8 kgf.m)]
3/8" [9.52 mm]
[42 N•m (4.3 kgf.m)]
1/2" [12.7 mm]
[55 N•m (5.6 kgf.m)]
5/8" [15.88 mm]
[65 N•m (6.6 kgf.m)]
3/4" [19.05 mm]
[100 N•m (10.2 kgf.m)]
Gas Leak Checking
Pressure test to system to 400 PSIG with dry nitrogen,
in stages.
Thoroughly leak check the system.
If the pressure holds, release the nitrogen and
proceed to section 10.4.
Summary of Contents for CU-5E36QBU-5
Page 26: ...26 3 Dimensions ...
Page 27: ...27 4 Refrigeration Cycle Diagram ...
Page 28: ...28 5 Block Diagram ...
Page 30: ...30 7 Electronic Circuit Diagram ...
Page 31: ...31 8 Printed Circuit Board 8 1 Main Printed Circuit Board ...
Page 32: ...32 8 2 Noise Filter Printed Circuit Board 8 3 Display Printed Circuit Board ...
Page 33: ...33 9 Installation Information 9 1 Check Points ...
Page 50: ...50 ...
Page 51: ...51 ...