16.1.3.
Wiring Error check
• The unit capable to correct the wiring error automatically by following procedures.
- Confirm the valve on the liquid side and gas side is open.
- Press WIRING CHECK button (SW3) on the Service PCB inside the outdoor unit for more than 10 seconds to start wiring
check operation.
- Wiring check process will complete in approximately 20 - 25 minutes. However, wiring check operation will not start within 3
minutes after compressor is stopped. When outdoor air temperature is less than 5
°
C or unit has abnormality, wiring check will
not start. (See NOTE 2)
• The LED 2 to LED 6 in Service PCB inside the outdoor unit indicate the possibility of the correction as shown in the table below:
• If automatic correct is impossible, check the indoor unit
wiring and piping manually.
NOTE:
1. For two rooms connection, LED 4 and 5 are not illuminated and for three rooms connections, LED 5 is not illuminated after
wiring operation complete.
2. If the outdoor air temperature is less than 5
°
C or unit has abnormality, wiring operation will not start.
3. After wiring check operation is complete, LED indication will illuminated until normal operation starts.
4. Follow the product diagnosis procedure.
5. When LED 1 only illuminate, indicates that outdoor unit is operating normally.
16.1.4.
Power Save Mode
• Power Save Mode can be enabled by pushing POWER SAVE switch (SW4) to ON before power supply ON.
• When Power Save Mode is ON, the unit can be operate at lower running current where the breaker capacity not achieve the
requirement.
16.1.5.
Mode priority function
• Mode priority function can be enabled by pushing MODE PRIORITY switch (SW5) to ON before power supply ON.
• When Mode Priority Function is ON, the mode priority is given to higher capacity indoor units.
16.1.6.
Cooling only function
• The unit capable to limit the operation mode to Cooling Mode only (Heating mode disabled) by cutting JP1 (COOL ONLY) before
power supply ON.
• This function prevent wrong operation during the unit installed in server room.
• This function could be disabled again by short the JP1 (COOL ONLY) before power supply ON.
LED
2
3
4
5
6
Message
Room
A
B
C
D
-
S
tatus
All flashing
Automatic correction impossible
LED2, 4, 6 and LED 3, 5
alternatively flashing
Wiring check in progress
Flashing one after another
Automatic correction completed
Other than above
Unit has abnormality (NOTE 4)
Summary of Contents for CU-2E15LBE
Page 11: ...11 Outdoor Unit CU 2E15LBE Outdoor Unit CU 2E18LBE ...
Page 12: ...12 Outdoor Unit CU 3E18LBE ...
Page 13: ...13 Outdoor Unit CU 4E23LBE ...
Page 14: ...14 ...
Page 15: ...15 Outdoor Unit CU 4E27CBPG ...
Page 16: ...16 ...
Page 17: ...17 3 Dimensions 3 1 CU 2E15LBE CU 2E18LBE 3 2 CU 3E18LBE CU 4E23LBE ...
Page 18: ...18 4 Refrigeration Cycle Diagram 4 1 CU 2E15LBE CU 2E18LBE ...
Page 19: ...19 4 2 CU 3E18LBE ...
Page 20: ...20 4 3 CU 4E23LBE ...
Page 21: ...21 5 Block Diagram 5 1 CU 2E15LBE CU 2E18LBE ...
Page 22: ...22 5 2 CU 3E18LBE ...
Page 23: ...23 5 3 CU 4E23LBE ...
Page 24: ...24 6 Wiring Connection Diagram 6 1 CU 2E15LBE CU 2E18LBE ...
Page 25: ...25 6 2 CU 3E18LBE ...
Page 26: ...26 6 3 CU 4E23LBE ...
Page 27: ...27 7 Electronic Circuit Diagram 7 1 CU 2E15LBE CU 2E18LBE ...
Page 28: ...28 7 2 CU 3E18LBE ...
Page 29: ...29 7 3 CU 4E23LBE ...
Page 30: ...30 8 Printed Circuit Board 8 1 Main Printed Circuit Board 8 1 1 CU 2E15LBE CU 2E18LBE ...
Page 31: ...31 8 1 2 CU 3E18LBE CU 4E23LBE ...
Page 32: ...32 8 2 Noise Filter Printed Circuit Board 8 3 Display Printed Circuit Board ...
Page 35: ...35 9 3 CU 3E18LBE 9 3 1 Check Points ...
Page 36: ...36 9 4 CU 4E23LBE 9 4 1 Check Points ...
Page 68: ...68 ...
Page 69: ...69 19 1 2 Two Indoor Unit Operation ...
Page 70: ...70 ...
Page 71: ...71 19 2 Operation Characteristics CU 2E18LBE 19 2 1 One Indoor Unit Operation ...
Page 72: ...72 ...
Page 73: ...73 19 2 2 Two Indoor Unit Operation ...
Page 74: ...74 ...
Page 75: ...75 19 3 Operation Characteristics CU 3E18LBE 19 3 1 One Indoor Unit Operation ...
Page 76: ...76 ...
Page 77: ...77 ...
Page 78: ...78 ...
Page 79: ...79 ...
Page 80: ...80 ...
Page 81: ...81 19 3 2 Two Indoor Unit Operation ...
Page 82: ...82 ...
Page 83: ...83 ...
Page 84: ...84 ...
Page 85: ...85 19 3 3 Three Indoor Unit Operation ...
Page 86: ...86 ...
Page 87: ...87 19 4 Operation Characteristics CU 4E23LBE 19 4 1 One Indoor Unit Operation ...
Page 88: ...88 ...
Page 89: ...89 ...
Page 90: ...90 ...
Page 91: ...91 ...
Page 92: ...92 ...
Page 93: ...93 19 4 2 Two Indoor Unit Operation ...
Page 94: ...94 ...
Page 95: ...95 19 4 3 Three Indoor Unit Operation ...
Page 96: ...96 ...
Page 97: ...97 19 4 4 Four Indoor Unit Operation ...
Page 98: ...98 ...