54
15.8. Deice Control
• When outdoor pipe temperature and outdoor air temperature is low, deice operation starts where indoor fan motor and outdoor
fan motor stop, indoor unit horizontal vane close and operation LED blink with compressor ON.
15.9. Time Delay Safety Control (Restart Control)
• The compressor will not restart within three minutes after compressor is stopped.
• This control is not applicable if the power supply reset or after deice condition.
15.10. 30 seconds Force Operation
• Once the compressor starts operation, it will not stop its operation for 30 seconds in order to cycle back compressor oil.
• However, it can be stopped using remote control or Auto OFF/ON button at indoor unit.
15.11. Total Current Control
• By referring to table below, during normal (default) operation, the running current refer to Hi values and during Power Save
Mode, the running current refer to Lo values.
• When the outdoor unit total running current (AC) exceeds X value, compressor frequency will decrease.
• If the running current does not exceed X value for 5 seconds, compressor frequency will increase.
• However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for 3 minutes.
15.12. IPM (power transistor) Protection Control
• Overheating Prevention Control
- If IPM temperature rises to 80
°
C, outdoor fan speed will be increased.
- When the IPM temperature rises to 95
°
C, compressor operation will stop immediately.
- Compressor operation restarts when temperature decreases to 90
°
C.
- If IPM temperature detected less than -30
°
C, IPM is judged as open circuit (“F96” is indicated).
• DC peak current control
- When IPM DC current exceeds set value of 30.0 ± 3.0 A, the compressor will stop.
- If the DC peak current detected within 30 seconds after operation starts, compressor will restart after 1 minute.
- If the DC peak current detected 30 seconds or more after operation starts, compressor will restart after 2 minute.
- Within 30 seconds after compressor restarts, if the DC peak current is exceeded set value continuously for 7 times, all indoor
and outdoor relays will be cut off (“F99” is indicated).
• Error reset can be done by power supply reset.
15.13. Compressor Protection Control (Gas leak detection control 1)
• Control start conditions
- For 5 minutes, the compressor continuously operates and total current is low.
- During Cooling or Soft Dry operation:
Indoor intake temperature — indoor piping temperature is below 4
°
C.
- During Heating operation:
Indoor pipe temperature — indoor intake temperature is below 3
°
C.
- Not during deice control.
- Compressor ON with maximum frequency.
• Control content
- Compressor stops (and restart after 3 minutes)
- If the conditions above happen 4 times within 60 minutes, the unit will stop operation (“F91” is indicated).
Operation Mode
CU-4E23LBE
CU-3E18LBE
X (A)
Y (A)
X (A)
Y (A)
Cooling/Soft Dry (A)
Hi
14.0
17.5
14.0
17.5
Lo
9.8
17.5
9.8
17.5
Cooling/Soft Dry (B)
Hi
14.0
17.5
14.0
17.5
Lo
9.8
17.5
9.8
17.5
Heating
Hi
14.0
17.5
14.0
17.5
Lo
9.8
17.5
9.8
17.5
Summary of Contents for CU-2E15LBE
Page 11: ...11 Outdoor Unit CU 2E15LBE Outdoor Unit CU 2E18LBE ...
Page 12: ...12 Outdoor Unit CU 3E18LBE ...
Page 13: ...13 Outdoor Unit CU 4E23LBE ...
Page 14: ...14 ...
Page 15: ...15 Outdoor Unit CU 4E27CBPG ...
Page 16: ...16 ...
Page 17: ...17 3 Dimensions 3 1 CU 2E15LBE CU 2E18LBE 3 2 CU 3E18LBE CU 4E23LBE ...
Page 18: ...18 4 Refrigeration Cycle Diagram 4 1 CU 2E15LBE CU 2E18LBE ...
Page 19: ...19 4 2 CU 3E18LBE ...
Page 20: ...20 4 3 CU 4E23LBE ...
Page 21: ...21 5 Block Diagram 5 1 CU 2E15LBE CU 2E18LBE ...
Page 22: ...22 5 2 CU 3E18LBE ...
Page 23: ...23 5 3 CU 4E23LBE ...
Page 24: ...24 6 Wiring Connection Diagram 6 1 CU 2E15LBE CU 2E18LBE ...
Page 25: ...25 6 2 CU 3E18LBE ...
Page 26: ...26 6 3 CU 4E23LBE ...
Page 27: ...27 7 Electronic Circuit Diagram 7 1 CU 2E15LBE CU 2E18LBE ...
Page 28: ...28 7 2 CU 3E18LBE ...
Page 29: ...29 7 3 CU 4E23LBE ...
Page 30: ...30 8 Printed Circuit Board 8 1 Main Printed Circuit Board 8 1 1 CU 2E15LBE CU 2E18LBE ...
Page 31: ...31 8 1 2 CU 3E18LBE CU 4E23LBE ...
Page 32: ...32 8 2 Noise Filter Printed Circuit Board 8 3 Display Printed Circuit Board ...
Page 35: ...35 9 3 CU 3E18LBE 9 3 1 Check Points ...
Page 36: ...36 9 4 CU 4E23LBE 9 4 1 Check Points ...
Page 68: ...68 ...
Page 69: ...69 19 1 2 Two Indoor Unit Operation ...
Page 70: ...70 ...
Page 71: ...71 19 2 Operation Characteristics CU 2E18LBE 19 2 1 One Indoor Unit Operation ...
Page 72: ...72 ...
Page 73: ...73 19 2 2 Two Indoor Unit Operation ...
Page 74: ...74 ...
Page 75: ...75 19 3 Operation Characteristics CU 3E18LBE 19 3 1 One Indoor Unit Operation ...
Page 76: ...76 ...
Page 77: ...77 ...
Page 78: ...78 ...
Page 79: ...79 ...
Page 80: ...80 ...
Page 81: ...81 19 3 2 Two Indoor Unit Operation ...
Page 82: ...82 ...
Page 83: ...83 ...
Page 84: ...84 ...
Page 85: ...85 19 3 3 Three Indoor Unit Operation ...
Page 86: ...86 ...
Page 87: ...87 19 4 Operation Characteristics CU 4E23LBE 19 4 1 One Indoor Unit Operation ...
Page 88: ...88 ...
Page 89: ...89 ...
Page 90: ...90 ...
Page 91: ...91 ...
Page 92: ...92 ...
Page 93: ...93 19 4 2 Two Indoor Unit Operation ...
Page 94: ...94 ...
Page 95: ...95 19 4 3 Three Indoor Unit Operation ...
Page 96: ...96 ...
Page 97: ...97 19 4 4 Four Indoor Unit Operation ...
Page 98: ...98 ...