8.4.5. Compressor Reverse Rotation Protection Control
•
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and
indoor heat exchanger is 4.5°F or less for continuous 2 minutes, compressor will stop and restart automatically.
•
Time Delay Safety Control is activated before the compressor restart.
T = Intake air temperature - Indoor heat exchanger temperature
•
This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
8.4.6. Starting Current Control
•
When the compressor, outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will start to
operate at 1.6 second later.
•
The reason of the difference is to reduce the starting current flow.
8.4.7. Anti-Dew Formation Control
•
Purpose is to prevent dew formation on indoor unit air discharge area.
•
When room temperature is constant (±1.8°F) the following conditions occur for 30 minutes continuously, anti-dew formation will
activate:
−
Remote Control setting temperature is less than 77°F.
−
Compressor is on.
−
Cooling operation mode.
−
Indoor Fan motor operate at Low fan speed or QLo.
•
This control is cancelled immediately when above condition is changed.
•
Anti-Dew formation is control by:
1. Increasing Air Flow Volume
a. Lo fan speed
Lo fan speed is changed to Lo+ after 30 min to prevent dew formation.
b. QLo fan speed
Dew formation may occurs at QLo cool, therefore QLo cool is operated only 1 hr 30 min (1 hr QLo, 30 min QLo +100
rpm). After that, it operates at QLo +180rpm (However Quiet LED remains on).
21
CS-C18DKU CU-C18DKU / CS-C24DKU CU-C24DKU
Summary of Contents for CSC18DKU - AIR CONDITIONER - SPLIT
Page 3: ...2 Functions 3 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...
Page 4: ...4 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...
Page 5: ...5 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...
Page 11: ...4 2 Outdoor Unit 4 2 1 CU C18DKU 11 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...
Page 12: ...4 2 2 CU C24DKU 12 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...
Page 13: ...5 Refrigeration Cycle Diagram 13 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...
Page 14: ...6 Block Diagram 14 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...
Page 15: ...7 Wiring Diagram CS C18DKU CU C18DKU CS C24DKU CU C24DKU 15 ...
Page 16: ...CS C18DKU CU C18DKU CS C24DKU CU C24DKU 16 ...
Page 29: ...9 Operating Instructions 29 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...
Page 30: ...30 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...
Page 31: ...31 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...
Page 32: ...32 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...
Page 33: ...33 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...
Page 34: ...34 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...
Page 39: ...39 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...
Page 58: ...14 Technical Data 14 1 Thermostat characteristics 58 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...
Page 59: ...14 2 Operation characteristics CS C18DKU CU C18DKU 59 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...
Page 60: ...60 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...
Page 61: ... CS C24DKU CU C24DKU 61 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...
Page 62: ...62 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...
Page 74: ...19 2 Remote Control 74 CS C18DKU CU C18DKU CS C24DKU CU C24DKU ...