6
Refrigerant Oil
cm
3
ATMOS NM56 OR SUNISO 4GDID (350)
Refrigerant Type
g (oz)
R22, 900 (31.7)
Height(I/D / O/D)
mm (inch)
283 (11-5/32)
530(20-7/8)
Width (I/D / O/D)
mm (inch)
803 (31-5/8)
650(25-19/32)
Dimension
Depth (I/D / O/D)
mm (inch)
214 (8-7/16)
230 (9-1/16)
Weight
Net (I/D / O/D)
kg (lb)
8.0 (18)
26 (57)
Pipe Diameter (Liquid / Gas)
mm (inch)
6.35 (1/4) / 12.70 (1/2)
Standard length
m (ft)
5.0 (16.4)
Length range (min – max)
m (ft)
3 (9.8) ~15 (49.2)
I/D & O/D Height different
m (ft)
5.0 (16.4)
Additional Gas Amount
g/m (oz/ft)
20 (0.2)
P
ip
in
g
Length for Additional Gas
m (ft)
5.0 (16.4)
Inner Diameter
mm
16
Drain Hose
Length
mm
500
Fin Material
Pre coated
Fin Type
Slit Fin
Row x Stage x FPI
2 x 16 x 21
Indoor Heat
Exchanger
Size (W x H x L)
mm
610 x 336 x 25.4
Fin Material
Pre coated
Fin Type
Slit Fin
Row x Stage x FPI
2 x 24 x 18
Outdoor Heat
Exchanger
Size (W x H xD)
mm
565.2(545.3) x504.0 x 12.7
Material
P.P.HONEY COMB
Air Filter
Type
One-touch
Power Supply
Indoor
Power Supply Cord
A
10
Thermostat
-
Protection Device
-
DRY BULB
WET BULB
Maximum
32
23
Indoor Operation Range
Minimum
16
11
Maximum
43
26
Outdoor Operation Range
Minimum
16
11
1.
Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB
(66°F WET BULB) and outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F
WET BULB)
Summary of Contents for CS-YC12NKV-6
Page 8: ...8 4 Dimensions 4 1 Indoor Unit Unit mm Unit mm Unit mm Unit mm ...
Page 9: ...9 4 2 Outdoor Unit ...
Page 10: ...10 5 Refrigeration Cycle Diagram Evaporator Condenser ...
Page 11: ...11 6 Block Diagram POWER SUPPLY AC 220V 60 Hz SINGLE PHASE ...
Page 12: ...12 7 Wiring Connection Diagram ...
Page 15: ...15 8 2 3 Indoor Unit Installation ...
Page 32: ...32 Cooling Characteristics at Different Piping Length ...