
86
14.4.2 Horizontal
Airflow
Automatic horizontal airflow direction can be set using remote control; the vane swings left and right within the
angles as stated below. For heating mode operation, the angle of the vane depends on the indoor heat
exchanger temperature as Figure 1 below. It does not swing during fan motor stop.
Operation Mode
Vane Angle (°)
Heating, with heat exchanger temperature
A
65 ~115 (Z20/25/35/42TK & XZ20/25/35TK)
70 ~ 110 (Z50/71TK & XZ50TK)
B 90
Cooling and soft dry
65 ~115 (Z20/25/35/42TK & XZ20/25/35TK)
70 ~ 110 (Z50/71TK & XZ50TK)
Manual horizontal airflow direction can be set using remote control; the angles of the vane are as stated below
and the positions of the vane are as Figure 2 above.
Z20/25/35/42TK & XZ20/25/35TK
Pattern
1 2 3 4 5
Airflow Direction
Patterns at Remote
Control
Vane Angle (°)
90
65
77.5
102.5
115
Z50/71TK & XZ50TK
Pattern
1 2 3 4 5
Airflow Direction
Patterns at Remote
Control
Vane Angle (°)
90
70
80
100
110
* The vertical vane angle tolerance is /- 5 degree.
AMP Air Conditioning
www.ampair.co.uk | [email protected]