8.1.16.2. Ionizer Operation case study
Case 1
8.2. PROTECTION CONTROL FEATURES
8.2.1. Protection Control For All Operations
8.2.1.1. Time Delay Safety Control
1. The compressor will not start for three minutes after stop of operation.
2. This control is not applicable if the power supply is cut off and on again or after 4-way valve deices condition.
8.2.1.2. 30 Seconds Forced Operation
1. Once the compressor starts operation, it will not stop its operation for 30 seconds.
2. However, it can be stopped using remote control or Auto Switch at indoor unit.
8.2.1.3. Total Running Current Control
1. When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor operation will be
decreased.
2. If the running current does not exceed X value for five seconds, the frequency instructed will be increased.
3. However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for three minutes.
XE12CK
XE9CK
Operation Mode
X (A)
Y (A)
X (A)
Y (A)
Cooling/Soft Dry (A)
6.5
17.0
4.5
17.0
Cooling/Soft Dry (B)
6.0
17.0
4.0
17.0
Heating
9.2
17.0
6.1
17.0
30
CS-XE9CKE CU-XE9CKE / CS-XE12CKE CU-XE12CKE
Summary of Contents for CS-XE9CKE
Page 10: ...4 Dimensions 10 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE...
Page 11: ...11 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE...
Page 12: ...5 Refrigeration Cycle Diagram 12 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE...
Page 13: ...6 Block Diagram 13 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE...
Page 14: ...7 Wiring Diagram 14 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE...
Page 91: ...13 Technical Data 91 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE...
Page 92: ...92 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE...
Page 104: ...104 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE...
Page 105: ...How to use electronic circuit diagram 105 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE...
Page 106: ...18 1 REMOTE CONTROL 106 CS XE9CKE CU XE9CKE CS XE12CKE CU XE12CKE...