Comp. Frequency
73Hz
92Hz
Total Running
Current
1.51 A and
2.15 A
1.51 A and
2.30 A
Indoor Heat
Exchanger Temp.
15
or above
30
or below
Operation
Cooling / Soft Dry
Heating
Note:
The above conditions are not valid during Deice operation.
●
this conditions are continuous for 5 minutes.
7. Minimum Frequency Operation Protection
∙
When the compressor operates at less than 37Hz for 60 minutes, the operating frequency will increase to 37Hz for 2
minutes.
8. Low Frequency Operation Protection
∙
When the following conditions occur, the compressor will operate at minimum 37 Hz.
Indoor intake temp.(
)
30
or
15
28
or
19
Outdoor air temp.(
)
38
or
16
24
or
4
Indoor heat exchanger temp.(
)
30
30
Operation
Cooling / Soft Dry
Heating
9. DC Peak Current Control
∙
When the electric current to the power transistor exceeds the set value, DC 35±4A, the compressor stops. The compressor
restarts after 3 minutes.
∙
If within 30 seconds the set value exceeds again after start of the compressor, all indoor and outdoor relays will be turned
off and all the LEDs will blink.
10. DC Reset
∙
When the voltage supply (DC) to power transistor is below the set value i.e, 178±5V, the compressor is stopped. The
compressor will restart after 3 minutes.
∙
If within 30 seconds the voltage supply (DC) is below the set value again after start of the compressor, all indoor and outdoor
relays will be turned off and all the LEDs will blink.
11. High Power Supply Voltage Protection
∙
When the voltage supply (AC) exceeds 295 ± 15V(T ), the air conditioner stops and restarts automatically when the voltage
supply (AC) is below (T -5)V. However, waiting for 3 minutes is necessary for re-operation.
33
CS-VG120KE / CU-VG120KE
Summary of Contents for CS-VG120KE
Page 3: ...2 Functions 2 1 REMOTE CONTROL 3 CS VG120KE CU VG120KE ...
Page 4: ...2 2 INDOOR UNIT 4 CS VG120KE CU VG120KE ...
Page 5: ...5 CS VG120KE CU VG120KE ...
Page 6: ...2 3 OUTDOOR UNIT 6 CS VG120KE CU VG120KE ...
Page 9: ...4 Dimensions 4 1 CS VG120KE INDOOR UNIT 9 CS VG120KE CU VG120KE ...
Page 10: ...4 2 CU VG120KE OUTDOOR UNIT 10 CS VG120KE CU VG120KE ...
Page 12: ...6 Block Diagram CS VG120KE CU VG120KE 12 ...
Page 49: ...11 3 INDOOR OUTDOOR UNIT INSTALLATION DIAGRAM 49 CS VG120KE CU VG120KE ...
Page 62: ...13 Technical Data 13 1 OPERATION CHARACTERISTICS 62 CS VG120KE CU VG120KE ...
Page 68: ...CS VG120KE CU VG120KE 68 ...
Page 69: ...15 Printed Circuit Board 15 1 CS VG120KE INDOOR UNIT 69 CS VG120KE CU VG120KE ...
Page 70: ...70 CS VG120KE CU VG120KE ...
Page 71: ...15 2 CU VG120KE OUTDOOR UNIT POWER SUPPLY 71 CS VG120KE CU VG120KE ...
Page 72: ...MAIN INDICATOR 72 CS VG120KE CU VG120KE ...
Page 75: ...16 2 CU VG120KE 16 2 1 Exploded View 75 CS VG120KE CU VG120KE ...
Page 78: ...MEMO ...
Page 79: ...MEMO ...
Page 80: ...Printed in Japan MS1299SO ...