Outdoor Unit
5
Anti-reverse Protection
To protect the compressor from reverse
rotation when power off suddenly.
Overload Protector
60-seconds Test Operation Control
Once the compressor is activated, it does not
stop for 60 seconds. It stops immediately with
remote control ON/OFF button.
Anti-freezing operation for outdoor unit(during
Heating Mode Operation only)
Temperature of the condenser is tested by sensor.
Deicing Control
Overload Protection Control
When the temperature of evaporator
reaches 51 ,outdoor fan stops,and will
restart when the temperature of evaporator
declines to 49 .
When the temperature of evaporator
reaches 65 ,compressor will stop.
4-way Valve Control
If the unit is stopped during H eating
O peration,the 4-way valve w ill remain in
heating mode operation for 5 minutes.
CS-UW9GKE / CU-UW9GKE / CS-UW12GKE / CU-UW12GKE
CU-UW9GKE
CU-UW12GKE
The 2-step Overload Protector is to protect
the compressor when
1)Temperature of compressor reaches
2)High temper ature or current enters into the
compressor
150