Panasonic CS- U12WKY Series Operating Instructions Manual Download Page 5

9

10. Decommissioning

• Before carrying out this procedure, it is 

essential that the technician is completely 
familiar with the equipment and all its details.

• It is recommended good practice that all 

refrigerants are recovered safely.

• Prior to the task being carried out, an oil 

and refrigerant sample shall be taken in 
case analysis is required prior to re-use of 
reclaimed refrigerant.

• It is essential that electrical power is 

available before the task is commenced.
a)  Become familiar with the equipment and 

its operation.

b) Isolate system electrically.
c) Before attempting the procedure ensure 
that:
• mechanical handling equipment is 

available, if required, for handling 
refrigerant cylinders; 

• all personal protective equipment is 

available and being used correctly;

• the recovery process is supervised at all 

times by a competent person;

• recovery equipment and cylinders conform 

to the appropriate standards.

d)  Pump down refrigerant system, if 

possible.

e)  If a vacuum is not possible, make a 

manifold so that refrigerant can be 
removed from various parts of the system.

f)  Make sure that cylinder is situated on the 

scales before recovery takes place.

g)  Start the recovery machine and operate 

in accordance with manufacturer’s 
instructions.

h)  Do not over fi ll cylinders. (No more than 

80 % volume liquid charge).

i)  Do not exceed the maximum working 

pressure of the cylinder, even temporarily.

j)  When the cylinders have been fi lled 

correctly and the process completed, make 
sure that the cylinders and the equipment 
are removed from site promptly and all 
isolation valves on the equipment are 
closed off.

k)  Recovered refrigerant shall not be 

charged into another refrigeration system 
unless it has been cleaned and checked.

• Electrostatic charge may accumulate and 

create a hazardous condition when charging 
or discharging the refrigerant.
To avoid fi re or explosion, dissipate static 
electricity during transfer by grounding and 
bonding containers and equipment before 
charging/discharging.

11. Labelling

• Equipment shall be labelled stating that it 

has been de-commissioned and emptied of 
refrigerant.

• The label shall be dated and signed.
• Ensure that there are labels on the 

equipment stating the equipment contains 
fl ammable refrigerant.

12. Recovery

• When removing refrigerant from a system, 

either for servicing or decommissioning, 
it is recommended good practice that all 
refrigerants are removed safely.

• When transferring refrigerant into cylinders, 

ensure that only appropriate refrigerant 
recovery cylinders are employed.

• Ensure that the correct number of cylinders 

for holding the total system charge are 
available.

• All cylinders to be used are designated for 

the recovered refrigerant and labelled for 
that refrigerant (i.e. special cylinders for the 
recovery of refrigerant).

• Cylinders shall be complete with pressure 

relief valve and associated shut-off valves in 
good working order.

• Recovery cylinders are evacuated and, if 

possible, cooled before recovery occurs.

• The recovery equipment shall be in good 

working order with a set of instructions 
concerning the equipment that is at hand 
and shall be suitable for the recovery of 
fl ammable refrigerants.

• In addition, a set of calibrated weighing 

scales shall be available and in good 
working order.

• Hoses shall be complete with leak-free 

disconnect couplings and in good condition.

• Before using the recovery machine, check 

that it is in satisfactory working order, has 
been properly maintained and that any 
associated electrical components are 
sealed to prevent ignition in the event of a 
refrigerant release.
Consult manufacturer if in doubt.

• The recovered refrigerant shall be returned 

to the refrigerant supplier in the correct 
recovery cylinder, and the relevant Waste 
Transfer Note arranged.

• Do not mix refrigerants in recovery units and 

especially not in cylinders.

• If compressors or compressor oils are to 

be removed, ensure that they have been 
evacuated to an acceptable level to make 
certain that fl ammable refrigerant does not 
remain within the lubricant.

• The evacuation process shall be carried 

out prior to returning the compressor to the 
suppliers.

• Only electric heating to the compressor 

body shall be employed to accelerate this 
process.

• When oil is drained from a system, it shall be 

carried out safely.

8

4. Repair to intrinsically safe components

• Do not apply any permanent inductive or 

capacitance loads to the circuit without 
ensuring that this will not exceed the 
permissible voltage and current permitted for 
the equipment in use.

• Intrinsically safe components are the only 

types that can be worked on while live in the 
presence of a fl ammable atmosphere.

• The test apparatus shall be at the correct 

rating.

• Replace components only with parts 

specifi ed by the manufacturer. Unspecifi ed 
parts by manufacturer may result ignition of 
refrigerant in the atmosphere from a leak.

5. Cabling

• Check that cabling will not be subject 

to wear, corrosion, excessive pressure, 
vibration, sharp edges or any other adverse 
environmental effects.

• The check shall also take into account the 

effects of aging or continual vibration from 
sources such as compressors or fans.

6. Detection of fl ammable refrigerants

• Under no circumstances shall potential 

sources of ignition be used in the searching 
or detection of refrigerant leaks.

• A halide torch (or any other detector using a 

naked fl ame) shall not be used.

7. Leak detection methods

• Electronic leak detectors shall be used 

to detect fl ammable refrigerants, but the 
sensitivity may not be adequate, or may 
need re-calibration.
(Detection equipment shall be calibrated in a 
refrigerant-free area.)

• Ensure that the detector is not a potential 

source of ignition and is suitable for the 
refrigerant used.

• Leak detection equipment shall be set at 

a percentage of the LFL of the refrigerant 
and shall be calibrated to the refrigerant 
employed and the appropriate percentage of 
gas (25 % maximum) is confi rmed.

• Leak detection fl uids are suitable for use with 

most refrigerants but the use of detergents 
containing chlorine shall be avoided as the 
chlorine may react with the refrigerant and 
corrode the copper pipe-work.

• If a leak is suspected, all naked fl ames shall 

be removed/extinguished.

• If a leakage of refrigerant is found which 

requires brazing, all of the refrigerant shall 
be recovered from the system, or isolated 
(by means of shut off valves) in a part of the 
system remote from the leak. Oxygen free 
nitrogen (OFN) shall then be purged through 
the system both before and during the 
brazing process.

8. Removal and evacuation

• When breaking into the refrigerant circuit to make 

repairs – or for any other purpose – conventional 
procedures shall be used.
However, it is important that best practice is 
followed since fl ammability is a consideration.
The following procedure shall be adhered to:
remove refrigerant -> purge the circuit with inert 
gas -> evacuate -> purge again with inert gas -> 
open the circuit by cutting or brazing

• The refrigerant charge shall be recovered into 

the correct recovery cylinders.

• The system shall be “fl ushed” with OFN to 

render the unit safe.

• This process may need to be repeated several times.
• Compressed air or oxygen shall not be used 

for this task.

• Flushing shall be achieved by breaking the 

vacuum in the system with OFN and continuing 
to fi ll until the working pressure is achieved, 
then venting to atmosphere, and fi nally pulling 
down to a vacuum.

• This process shall be repeated until no 

refrigerant is within the system.

• When the fi nal OFN charge is used, the system 

shall be vented down to atmospheric pressure 
to enable work to take place.

• This operation is absolutely vital if brazing 

operations on the pipe work are to take place.

• Ensure that the outlet for the vacuum pump is 

not close to any ignition sources and there is 
ventilation available.

9. Charging procedures

• In addition to conventional charging procedures, 

the following requirements shall be followed.

 

- Ensure that contamination of different 

refrigerants does not occur when using 
charging equipment.

 

- Hoses or lines shall be as short as possible to 

minimize the amount of refrigerant contained 
in them.

 

- Cylinders shall be kept upright.

 

- Ensure that the refrigeration system is earthed 

prior to charging the system with refrigerant.

 

- Label the system when charging is complete 

(if not already).

 

- Extreme care shall be taken not to over fi ll the 

refrigeration system.

• Prior to recharging the system it shall be 

pressure tested with OFN (refer to #7).

• The system shall be leak tested on completion 

of charging but prior to commissioning.

• A follow up leak test shall be carried out prior to 

leaving the site.

• Electrostatic charge may accumulate and 

create a hazardous condition when charging 
and discharging the refrigerant.
To avoid fi re or explosion, dissipate static 
electricity during transfer by grounding and 
bonding containers and equipment before 
charging/discharging.

Safety precautions

 ( 5 / 8 )

A C I 2 P R 0 9 2 0 1 

Summary of Contents for CS- U12WKY Series

Page 1: ...this equipment uses a flammable refrigerant If the refrigerant is leaked together with an external ignition source there is a possibility of ignition This symbol shows that the Operation Instructions should be read carefully This symbol shows that a service personnel should be handling this equipment with reference to the Installation Instructions This symbol shows that there is information include...

Page 2: ...g instructions 12 Troubleshooting 13 BEE Regulation 1 4 Information 15 2 8 FAN DRY Operating the unit at 24 C or higher degrees may save energy Better comfort condition at 24 C or higher degrees A C I 2 P R 0 9 2 0 1 PM 2 5 Filter Ag Clean Filter 8m ...

Page 3: ... parts may cause injury Do not switch ON the indoor unit when waxing the floor After waxing aerate the room properly before operating the unit Do not install the unit in oily and smoky areas to prevent damage to the unit Do not dismantle the unit for cleaning purpose to avoid injury Do not step onto an unstable bench when cleaning the unit to avoid injury Do not place a vase or water container on t...

Page 4: ...mage to cables excessive number of connections terminals not made to original specification damage to seals incorrect fitting of glands etc Ensure that apparatus is mounted securely Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmospheres Replacement parts shall be in accordance with the manufacturer s speci...

Page 5: ...nductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere The test apparatus shall be at the correct rating Replace components only with parts specified by the manufacturer Unsp...

Page 6: ...use curtains to screen off sunlight and outdoor heat Unit operates at auto fan speed to give a gentle cooling operation FAN To operate Air Con in Fan Only mode Indoor unit temp display will show set temp for AUTO COOL DRY mode and room temp for FAN mode Only indoor unit fan operates as per remote settings Outdoor is OFF so no cooling acheived Provides air circulation in the room SL will be displaye...

Page 7: ...the dust filters thoroughly under shade away from fire or direct sunlight Replace any damaged filters Ag Clean Filter PM 2 5 filter Clean the filter whenever necessary Don t wash rinse the filter with water The surface of the filter shouldn t be rubbed with any object The filter shouldn t be pulled with strong force as it may get damaged 12 7 8 A C I 2 P R 0 9 2 0 1 Front Panel Dust Filters Ag Clean filter...

Page 8: ... number http www panasonic com in corporate sustainability panasonic india i recycle program html S No 1 All electrical and electronic products are required to be handed over only to the Authorized recycler 2 The product should be handed over only to authorized recycler for disposal 3 4 5 6 Keep the product in isolated area after it becomes non functional un repairable so as to prevent its acciden...

Reviews: