23
11.4.3.
EVACUATION OF THE EQUIPMENT
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the
following procedure.
1. Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way valve.
• Be sure to connect the end of the charging hose with the push pin to the service port.
2. Connect the center hose of the charging set to a vacuum pump with check valve, or vacuum pump and vacuum pump
adaptor.
3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 cmHg (0 MPa) to
-76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4. Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not
move after approximately five minutes.
Note: BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valve at a torque of 18 N
O
m with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” using a hexagonal
wrench (4 mm).
8. Mount valve caps onto the 2-way valve and the 3-way valve.
• Be sure to check for gas leakage.
11.4.4.
CONNECT THE CABLE TO THE OUTDOOR UNIT
1. Remove the control board cover from the unit by loosening the screw.
2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 x 1.5 mm
2
flexible
cord, type designation 245 IEC 57 (H05RN-F) or heavier cord.
3. Secure the cable onto the control board with the holder (clamper).
4. Attach the control board cover in its original position with the screw.
CAUTION
• If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step
above take the following measure:
• If the leak stops when the piping connections are tightened further, continue working from step
.
• If the leak does not stop when the connections are retightened, repair the location of leak.
• Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may cause frostbite.
Summary of Contents for CS-TE12HKE
Page 8: ...8 5 Dimensions 5 1 Indoor Unit ...
Page 9: ...9 5 2 Outdoor Unit ...
Page 10: ...10 6 Refrigeration Cycle Diagram ...
Page 11: ...11 7 Block Diagram ...
Page 12: ...12 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 13: ...13 8 2 Outdoor Unit ...
Page 14: ...14 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 15: ...15 9 2 Outdoor Unit ...
Page 16: ...16 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Printed Circuit Board ...
Page 17: ...17 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 43: ...43 16 1 2 Removal of Electronic Controller ...
Page 44: ...44 16 1 3 Removal of Control Board ...
Page 45: ...45 16 1 4 Removal of Fan Motor and Cross Flow Fan ...
Page 46: ...46 ...
Page 48: ...48 17 Technical Data 17 1 Operation Characteristics ...
Page 49: ...49 ...
Page 50: ...50 ...
Page 51: ...51 ...