12.8 Timer Control
•
There are 2 sets of ON and OFF timer is available to turn the unit ON or OFF at different preset time.
•
If more than one timer had been set, the upcoming timer will be display and will activated in sequence.
12.8.1 ON
Timer
Control
ON Timer 1 and ON Timer 2 can be set using remote control, where the unit with timer set will start operation earlier
than the setting time. This is to provide a comfortable environment when reaching the set ON time.
60 minutes before the set ON time, indoor (at fan speed of Lo-) and outdoor fan motor start operation for 30 seconds
to determine the indoor intake air temperature and outdoor air temperature in order to judge the operation starting
time.
From the above judgment, the decided operation will start operation earlier than the set time as shown below.
12.8.2 OFF Timer Control
OFF Timer 1 and OFF Timer 2 can be set using remote control, where the unit with timer set will stop at set OFF time.
Notes:
1 By pressing ON/OFF operation button, the ON Timer or OFF Timer setting will not be cancelled.
2 To cancel the previous timer setting, press CANCEL button.
3 To activate the previous timer setting, press SET button.
4 If main power supply is switched off, the Timer setting will be cancelled.
12.9 Random Auto Restart Control
•
When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within
three to four minutes. There are 10 patterns to be selected randomly after power supply resumes.
•
This control is not applicable during OFF/ON Timer setting.
•
This control can be omitted by open the circuit of JP1 at indoor unit printed circuit board.
12.10 Indication Panel
LED POWER TIMER
QUIET POWERFUL e-ion
PATROL
Color
Green Orange Orange Orange Blue
Blue
Orange
Red
Light ON
Operation ON Timer Setting ON Quiet Mode ON Powerful Mode ON
e-ion ON
Air Clean Moderate
Dirty
Light OFF
Operation OFF Timer Setting OFF Quiet Mode OFF Powerful Mode OFF
e-ion OFF
PATROL OFF
Note:
•
If POWER LED blinks, the possible operation of the unit is operation mode judgment, or ON timer sampling.
•
If TIMER LED blinks, there is an abnormal operation occurs.
•
If e-ion LED blinks, there is an abnormal e-ion operation occurs.
•
If PATROL LED blinks, there is gas sensor error detection.
15 min
10 min
5 min
Indoor intake air
temperature (°C)
30
25
30
35
Outdoor air
temperature (°C)
Cooling / Soft Dry
Summary of Contents for CS-S12MKQ
Page 11: ...11 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control ...
Page 15: ...15 4 2 3 CU S18MKQ CU S24MKQ ...
Page 16: ...16 4 2 4 CU S28MKQ ...
Page 17: ...17 5 Refrigeration Cycle Diagram 5 1 CS S9MKQ CU S9MKQ CS S12MKQ CU S12MKQ ...
Page 18: ...18 5 2 CS S18MKQ CU S18MKQ CS S24MKQ CU S24MKQ CS S28MKQ CU S28MKQ ...
Page 19: ...19 6 Block Diagram 6 1 CS S9MKQ CU S9MKQ ...
Page 20: ...20 6 2 CS S12MKQ CU S12MKQ ...
Page 21: ...21 6 3 CS S18MKQ CU S18MKQ CS S24MKQ CU S24MKQ ...
Page 22: ...22 6 4 CS S28MKQ CU S28MKQ ...
Page 33: ...33 8 2 Outdoor Unit 8 2 1 CU S9MKQ ...
Page 37: ...37 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board ...
Page 38: ...38 9 1 2 Power Printed Circuit Board 9 1 2 1 CS S9MK CS S12MK 9 1 2 2 CS S18MK CS S24MK ...
Page 40: ...40 9 1 6 Comparator Printed Circuit Board 9 1 7 Human Activity Sensor Printed Circuit Board ...
Page 41: ...41 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU S9MK ...
Page 42: ...42 9 2 1 2 CU S12MK ...
Page 43: ...43 9 2 1 3 CU S18MK CU S24MK ...
Page 44: ...44 9 2 1 4 CU S28MK ...
Page 45: ...45 9 2 2 Noise Filter Printed Circuit Board 9 2 2 1 CU S9MKQ ...
Page 115: ...115 Figure 3 Figure 4 Figure 5 16 1 1 3 To remove discharge grille Figure 6 ...
Page 117: ...117 Figure 10 Figure 11 ...
Page 119: ...119 16 2 1 3 To remove power electronic controller Figure 14 Figure 15 Figure 16 Figure 17 ...
Page 121: ...121 Figure 21 Figure 22 Figure 23 ...