61
11.2.4 Connect the cable to the Outdoor Unit
1 Remove the control board cover from the unit by loosening the screw.
2 Cable connection to the power supply through Isolating Devices (Disconnecting means).
o
Connect the approved polychloroprene sheathed
power supply cord
3 x 4.0 mm
2
(3.0HP) type
designation 245 IEC 57 or heavier cord to the terminal board, and connect the others end of the cord to
Isolating Devices (Disconnecting means).
o
Do not use joint power supply cord. Replace the wire if the existing wire (from concealed wiring, or
otherwise) is too short.
o
In unavoidable case, joining of power supply cord between isolating devices and terminal board of air
conditioner shall be done by using approved socket and plug rated 25A (3.0HP). Wiring work to both
socket and plug must follow to national wiring standard.
3
Connecting cable
between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 x 1.5
mm
2
flexible cord, type designation 245 IEC 57 or heavier cord. Do not use joint connection cable. Replace
the wire if the existing wire (from concealed wiring, or otherwise) is too short.
4 Connect the power supply cord and connection cable between indoor unit and outdoor unit according to the
diagram below.
5 Secure the power supply cord and connection cable onto the control board with the holder.
6 Attach the control board cover back to the original position with screw.
7 For wire stripping and connection requirement, refer to instruction
g
of the indoor unit.
•
Isolating Devices (Disconnecting means) should have minimum 3.0mm contact gap.
•
Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason.
11.2.5 Pipe
Insulation
1 Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation
Diagram. Please wrap the insulated piping end to prevent water from going inside the piping.
2 If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by
using POLY-E-FOAM with thickness 6mm or above.
Summary of Contents for CS-S12MKQ
Page 11: ...11 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control ...
Page 15: ...15 4 2 3 CU S18MKQ CU S24MKQ ...
Page 16: ...16 4 2 4 CU S28MKQ ...
Page 17: ...17 5 Refrigeration Cycle Diagram 5 1 CS S9MKQ CU S9MKQ CS S12MKQ CU S12MKQ ...
Page 18: ...18 5 2 CS S18MKQ CU S18MKQ CS S24MKQ CU S24MKQ CS S28MKQ CU S28MKQ ...
Page 19: ...19 6 Block Diagram 6 1 CS S9MKQ CU S9MKQ ...
Page 20: ...20 6 2 CS S12MKQ CU S12MKQ ...
Page 21: ...21 6 3 CS S18MKQ CU S18MKQ CS S24MKQ CU S24MKQ ...
Page 22: ...22 6 4 CS S28MKQ CU S28MKQ ...
Page 33: ...33 8 2 Outdoor Unit 8 2 1 CU S9MKQ ...
Page 37: ...37 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board ...
Page 38: ...38 9 1 2 Power Printed Circuit Board 9 1 2 1 CS S9MK CS S12MK 9 1 2 2 CS S18MK CS S24MK ...
Page 40: ...40 9 1 6 Comparator Printed Circuit Board 9 1 7 Human Activity Sensor Printed Circuit Board ...
Page 41: ...41 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU S9MK ...
Page 42: ...42 9 2 1 2 CU S12MK ...
Page 43: ...43 9 2 1 3 CU S18MK CU S24MK ...
Page 44: ...44 9 2 1 4 CU S28MK ...
Page 45: ...45 9 2 2 Noise Filter Printed Circuit Board 9 2 2 1 CU S9MKQ ...
Page 115: ...115 Figure 3 Figure 4 Figure 5 16 1 1 3 To remove discharge grille Figure 6 ...
Page 117: ...117 Figure 10 Figure 11 ...
Page 119: ...119 16 2 1 3 To remove power electronic controller Figure 14 Figure 15 Figure 16 Figure 17 ...
Page 121: ...121 Figure 21 Figure 22 Figure 23 ...