38
13.2.2 Freeze Prevention Control
1 .Frequency of the compressor
For prevention of freezing of the indoor evaporator, the frequency of the compressor will be changed according
to the indoor piping temperature.
2 .Indoor Fan Control
Indoor fan speed changes according to the indoor piping temperature.
13.2.3 Dew Prevention Control
• To prevent dew formation at indoor unit discharge area.
• This control starts if all conditions continue for 20 minutes:
- Operated with Cooling or Soft Dry Mode.
- Indoor intake temperature is between 25
к
and 29
к
.
- Outdoor air temperature is less than 30
к
.
• This control stopped then receive air swing change signal from Remote Control.
13.2.4 Overload Protection For Cooling Operation
The frequency for the compressor will change according to the outdoor piping temperature.
13.3 Indoor Piping Air Temperature Control (Heating)
13.3.1 Indoor Fan Control
1. Indoor fan is controlled by the indoor piping temperature.
ϥ
Manual Fan Speed
Piping Temperature(
к
)
K0 K1 K2 K3 K4 K5 K6
K7 K8 K9 K10
K11
16 19 24 32 32 36 36 39 54 54 57 60
63
к
.
Outdoor pipe Temp.
61
к
60
к
56
к
RE9JKE, RE12JKE
RE15JKE
58
к
9
к
.
8
к
.
6
к
.
0
к
.
Max:40 Hz Min 30Hz
Summary of Contents for CS-RE9JKE
Page 14: ...14 5 2 Outdoor Unit Unit mm...
Page 15: ...15 6 Refrigeration Cycle Diagram CS CU RE9JKE CS CU RE12JKE CS CU RE15JKE COOLING HEATING...
Page 16: ...16 7 Block Diagram CS CU RE15JKE CS CU RE9 12JKE...
Page 17: ...17 8 Wiring Diagram 6 8 5 6 8 5...
Page 18: ...18 6 8 5...
Page 19: ...19 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board TOP VIEW...
Page 20: ...20 BOTTOM VIEW...
Page 21: ...21 9 1 2 Indicator receiver TOP VIEW BOTTOM VIEW...
Page 22: ...22 9 2 Outdoor Unit 9 2 1 CU RE9JKE CU RE12JKE TOP VIEW BOTTOM VIEW...
Page 25: ...25 10 2 3 Indoor Unit Installation...
Page 42: ...42 14 2 3 Error Codes Table...
Page 46: ...46 16 Exploded View and Replacement Pars List 16 1 Indoor Unit CS RE9JKE CS RE12JKE CS RE15JKE...
Page 48: ...48 16 2 Outdoor Unit CU RE9JKE CU RE12JKE...
Page 50: ...50 CU RE15JKE...