15.5.18. F91 (Refrigeration Cycle Abnormality)
Malfunction Decision Conditions
• During cooling, compressor frequency = Fcmax.
• During heating, compressor frequency > Fhrated.
• During cooling and heating operation, running current: 0.65A < I < 1.65A.
• During cooling, indoor intake - indoor pipe < 4
q
C.
• During heating, indoor pipe - indoor intake < 5
q
C.
Multi Models Only
- Gas shortage detection 1: A gas shortage is detected by checking the CT-detected input current value and the compressor
running frequency. During startup and operating of cooling and heating, input current < 8.78/256 (A/Hz)
u
compressor
running fre 0.25.
- Gas shortage detection 2: A gas shortage is detected by checking the difference between indoor pipe temperature and indoor
intake air temperature during cooling and heating.
Malfunction Caused
• Refrigerant shortage (refrigerant leakage).
• Poor compression performance of compressor.
• 2/3 way valve closed.
• Detection error due to faulty indoor intake air or indoor pipe temperature sensors.
Troubleshooting
Summary of Contents for CS-RE18JKE
Page 9: ...9 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control...
Page 10: ...10 5 Dimensions 5 1 Indoor Unit Remote Control...
Page 11: ...11 5 2 Outdoor Unit 5 2 1 CU RE18JKE...
Page 12: ...12 5 2 2 CU RE24JKE...
Page 13: ...13 6 Refrigeration Cycle Diagram...
Page 14: ...14 7 Block Diagram 7 1 CS RE18JKE CU RE18JKE...
Page 15: ...15 7 2 CS RE24JKE CU RE24JKE...
Page 16: ...16 8 Wiring Connection Diagram 8 1 Indoor Unit...
Page 17: ...17 8 2 Outdoor Unit 8 2 1 CU RE18JKE...
Page 18: ...18 8 2 2 CU RE24JKE...
Page 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit...
Page 20: ...20 9 2 Outdoor Unit 9 2 1 CU RE18JKE...
Page 21: ...21 9 2 2 CU RE24JKE...
Page 22: ...22 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board...
Page 23: ...23 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Printed Circuit Board...
Page 24: ...24 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board 10 2 1 1 CU RE18JKE...
Page 25: ...25 10 2 2 Main Printed Circuit Board 10 2 2 1 CU RE24JKE...
Page 26: ...26 10 2 3 Power Printed Circuit Board 10 2 3 1 CU RE24JKE...
Page 76: ...76 16 1 3 To remove power electronic controller...
Page 77: ...77 16 1 4 To remove discharge grille 16 1 5 To remove control board...
Page 78: ...78 16 1 6 To remove cross flow fan and indoor fan motor...
Page 79: ...79...
Page 90: ...90 18 Exploded View and Replacement Parts List 18 1 Indoor Unit...