36
13. Protection
control
13.1 Protection Control For All Operations
13.1.1 Time Delay Safety Control
ϥ
The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on
again by pressing OFF/ON button at remote control within this period.
ϥ
This control is not applicable if the power supply is cut off and on again.
ϥ
This phenomenon is to balance the pressure inside the refrigerant cycle.
13.1.2 30 Seconds Forced Control
ϥ
Once the air conditioner is turned on, the compressor will not stop within 30 seconds in a normal operation
although the intake air temperature has reached the thermo-off temperature. However, force stop by pressing the
OFF/ON button at the remote control is permitted or the Auto OFF/ON button at indoor unit.
ϥ
The reason for the compressor to force operation for minimum 30 seconds is to allow the refrigerant oil run in a
full cycle and return back to the outdoor unit.
13.1.3 Total running current control
1. If the outdoor unit total running current is detected exceeding I
1
(A), the frequency instructed for compressor
operation will be decreased.
2. If the running current does not exceed I
1
(A) for 5 seconds, the frequency instructed will be increased.
RE9JKE RE12JKE RE15JKE
Operation mode
I
1
(A) I
1
(A) I
1
(A)
Cooling/ Soft Dry /Fan A*
5.03
6.35
8.98
Cooling/ Soft Dry /Fan B
4.89
6.22
8.00
Heating
4.75
6.22
9.31
*The first 30 minutes of cooling operation, A will be applied.
(For RE9JKE,RE12JKE) (RE15JKE)
13.1.4 IPM (Power transistor) Protection Control.
1. DC Peak Current Control
ϥ
When electric current to IPM exceeds set value of DC17.3 1A, the compressor will stop. It will restart after
three minutes.
ϥ
If the set value is exceeded again within 30 seconds, the operation will restart after one minute.
ϥ
If this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.
ϥ
Error code [F99] will be displayed.
2. Overheating protection control
When the IPM temperature rises to 112
к
, compressor will stop immediately.
Compressor restarts after three minutes if the temperature decreases to 97
к
13.1.5 Compressor Overheating Prevention Control
Instructed frequency for compressor operation will be regulated compressor discharge temperature. The change of
frequency is as below.
39
ć
39
ć
39
ć
38
ć
Outdoor temperature
112
ć
RE9/12JKE
112
ć
110
ć
100
ć
RE15JKE
Summary of Contents for CS-RE12JKE
Page 14: ...14 5 2 Outdoor Unit Unit mm ...
Page 15: ...15 6 Refrigeration Cycle Diagram CS CU RE9JKE CS CU RE12JKE CS CU RE15JKE COOLING HEATING ...
Page 16: ...16 7 Block Diagram CS CU RE15JKE CS CU RE9 12JKE ...
Page 17: ...17 8 Wiring Diagram 6 8 5 6 8 5 ...
Page 18: ...18 6 8 5 ...
Page 19: ...19 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board TOP VIEW ...
Page 20: ...20 BOTTOM VIEW ...
Page 21: ...21 9 1 2 Indicator receiver TOP VIEW BOTTOM VIEW ...
Page 22: ...22 9 2 Outdoor Unit 9 2 1 CU RE9JKE CU RE12JKE TOP VIEW BOTTOM VIEW ...
Page 25: ...25 10 2 3 Indoor Unit Installation ...
Page 42: ...42 14 2 3 Error Codes Table ...
Page 48: ...48 16 2 Outdoor Unit CU RE9JKE CU RE12JKE ...
Page 50: ...50 CU RE15JKE ...