11.3. Indoor Unit
11.3.1.
HOW TO FIX INSTALLATION PLATE
The mounting wall is strong and solid enough to prevent it from
the vibration.
The centre of installation plate should be at more than 550 mm
at right and left of the wall.
The distance from installation plate edge to ceiling should more
than 67 mm.
From installation plate left edge to unit’s left side is 47 mm.
From installation plate right edge to unit’s right is 73 mm.
1. Mount the installation plate on the wall with 5 screws or
more.
(If mounting the unit on the concrete wall consider using
anchor bolts.)
• Always mount the installation plate horizontally by
aligning the marking-off line with the thread and using a
level gauge.
2. Drill the piping plate hole with ø70 mm hole-core drill.
• Line according to the left and right side of the installation
plate. The meeting point of the extended line is the
centre of the hole. Another method is by putting
measuring tape at position as shown in the diagram
above. The hole centre is obtained by measuring the
distance namely 150 mm and 125 mm for left and right
hole respectively.
• Drill the piping hole at either the right or the left and the
hole should be slightly slanted to the outdoor side.
11.3.2.
TO DRILL A HOLE IN THE WALL
AND INSTALL A SLEEVE OF
PIPING
1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes about 15 mm from the
wall.
4. Finish by sealing the sleeve with putty or caulking
compound at the final stage.
11.3.3.
INDOOR UNIT INSTALLATION
1. For the right rear piping
2. For the right and right bottom piping
: For left side piping, piping connection for liquid should be about
126 mm from this line.
: For left side piping, piping connection for gas should be about
174 mm from this line.
: For left side piping, piping connection cable should be about
984 mm from this line.
Caution
When the wall is hollow, please be sure to use the
sleeve for tube ass’y to prevent dangers caused by
mice biting the connecting cable.
Summary of Contents for CS-PW18GKE
Page 8: ...8 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 9: ...9 5 Dimensions 5 1 Indoor Unit Remote Control ...
Page 10: ...10 5 2 Outdoor Unit ...
Page 11: ...11 6 Refrigeration Cycle Diagram ...
Page 12: ...12 7 Block Diagram ...
Page 13: ...13 8 Wiring Connection Diagram ...
Page 14: ...14 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 2 Outdoor Unit ...
Page 15: ...15 10 Printed Circuit Board 10 1 Indoor Unit ...
Page 16: ...16 ...
Page 17: ...17 10 2 Outdoor Unit ...
Page 18: ...18 10 3 Indicator Receiver ...
Page 21: ...21 3 For the embedded piping This can be used for left rear piping left bottom piping also ...
Page 33: ...33 a Normal Deicing Time Diagram b Overload Deicing Time Diagram ...
Page 44: ...44 16 Technical Data 16 1 Thermostat Characteristics 16 1 1 CS PW18GKE ...
Page 46: ...46 16 3 Operation Characteristics 16 3 1 CS PW18GKE CU PW18GKE ...
Page 47: ...47 ...
Page 48: ...48 ...
Page 49: ...49 ...