Panasonic CS-PU24XKH Operating Instructions Manual Download Page 9

9

Safety Precautions

3. Repairs to sealed components

• During repairs to sealed components, all 

electrical supplies shall be disconnected from 
the equipment being worked upon prior to any 
removal of sealed covers, etc.

• If it is absolutely necessary to have an 

electrical supply to equipment during 
servicing, then a permanently operating 
form of leak detection shall be located at the 
most critical point to warn of a potentially 
hazardous situation.

• Particular attention shall be paid to the 

following to ensure that by working on 
electrical components, the casing is not 
altered in such a way that the level of 
protection is affected. This shall include 
damage to cables, excessive number of 
connections, terminals not made to original 
speci

fi

 cation, damage to seals, incorrect 

fi

 tting 

of glands, etc.

• Ensure that apparatus is mounted securely.
• Ensure that seals or sealing materials have 

not degraded such that they no longer serve 
the purpose of preventing the ingress of 

fl

 ammable atmospheres.

• Replacement parts shall be in accordance 

with the manufacturer’s speci

fi

 cations.

NOTE: The use of silicon sealant may inhibit 
the effectiveness of some types of leak 
detection equipment.
Intrinsically safe components do not have to be 
isolated prior to working on them.

4. Repair to intrinsically safe components

• Do not apply any permanent inductive or 

capacitance loads to the circuit without 
ensuring that this will not exceed the 
permissible voltage and current permitted for 
the equipment in use.

• Intrinsically safe components are the only 

types that can be worked on while live in the 
presence of a 

fl

 ammable atmosphere.

• The test apparatus shall be at the correct 

rating.

• Replace components only with parts speci

fi

 ed 

by the manufacturer. Unspeci

fi

 ed parts by 

manufacturer may result ignition of refrigerant 
in the atmosphere from a leak.

5. Cabling

• Check that cabling will not be subject 

to wear, corrosion, excessive pressure, 
vibration, sharp edges or any other adverse 
environmental effects.

• The check shall also take into account the 

effects of aging or continual vibration from 
sources such as compressors or fans.

6. Detection of 

fl

 ammable refrigerants

• Under no circumstances shall potential 

sources of ignition be used in the searching or 
detection of refrigerant leaks.

• A halide torch (or any other detector using a 

naked 

fl

 ame) shall not be used.

7. The following leak detection methods 

are deemed acceptable for all refrigerant 
systems

• No leaks shall be detected when using 

detection equipment with a sensitivity of 
5 grams per year of refrigerant or better 
under a pressure of at least 0.25 times the 
maximum allowable pressure (>1.04 MPa, 
max 4.15 MPa), for example, a universal 
sniffer.

• Electronic leak detectors may be used 

to detect 

fl

 ammable refrigerants, but the 

sensitivity may not be adequate, or may need 
re-calibration.
(Detection equipment shall be calibrated in a 
refrigerant-free area.)

• Ensure that the detector is not a potential 

source of ignition and is suitable for the 
refrigerant used.

• Leak detection equipment shall be set at a 

percentage of the LFL of the refrigerant and 
shall be calibrated to the refrigerant employed 
and the appropriate percentage of gas (25 % 
maximum) is con

fi

 rmed.

• Leak detection 

fl

uids are also suitable for use 

with most refrigerants, for example, bubble 
method and 

fl

uorescent method agents. The 

use of detergents containing chlorine shall 
be avoided as the chlorine may react with the 
refrigerant and corrode the copper pipe-work.

• If a leak is suspected, all naked 

fl

 ames shall 

be removed/extinguished.

• If a leakage of refrigerant is found which 

requires brazing, all of the refrigerant shall 
be recovered from the system, or isolated 
(by means of shut off valves) in a part of the 
system remote from the leak. The precautions 
in #8 must be followed to remove the 
refrigerant.

English

Summary of Contents for CS-PU24XKH

Page 1: ...nditioner 2 20 Before operating the unit please read these operating instructions thoroughly and keep them for future reference Before installation the installer should Read the Installation Instructi...

Page 2: ...he back cover of remote control 2 Insert AAA or R03 batteries 3 Close the cover A Clock setting 1 Press then press to set the time Press for approximately 5 seconds to show the time as 12 hour am pm o...

Page 3: ...only and may differ from the actual unit They are subject to change without notice B Basic operation 2 Press MODE to select the desired mode DRY AUTO COOL 1 Press OFF ON OFF ON to start stop the oper...

Page 4: ...supervised to ensure that they do not play with the appliance Please consult an authorised dealer or specialist to clean the internal parts repair install remove disassemble and reinstall the unit Im...

Page 5: ...nit is not going to be used for a long period of time New batteries of the same type must be inserted following the polarity stated Power supply Do not disconnect the plug by pulling the cord to preve...

Page 6: ...l the opening by pinching taping etc Handling of R32 is similar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use of...

Page 7: ...he precautions in 12 and comply with national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised a...

Page 8: ...ernally into the atmosphere 2 7 Checks to the refrigerating equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the...

Page 9: ...the atmosphere from a leak 5 Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also t...

Page 10: ...minimize the amount of refrigerant contained in them Cylinders shall be kept in an appropriate position according to the instructions Ensure that the refrigerating system is earthed prior to charging...

Page 11: ...employed Ensure that the correct number of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refri...

Page 12: ...operation Press to restore the remote control to default setting Indicators To adjust FAN SPEED and QUIET condition FAN SPEED When AUTO FAN is selected the fan speed is adjusted automatically accordin...

Page 13: ...en manually dimmed This operation is incorporated with the activation timer 0 5 1 2 3 4 5 6 7 8 or 9 hours This operation can be set together with timer Sleep operation has the priority over OFF timer...

Page 14: ...If the timer has been cancelled manually or due to power failure you can restore the timer again Press ON or OFF to select the respective setting or then press SET The nearest timer setting is displa...

Page 15: ...xed at middle position setting Once the temperature is achieved the horizontal flap swings up down automatically In COOL DRY mode The horizontal flap swings up down automatically Auto restart control...

Page 16: ...Aluminium fin Front panel Air filters Indoor unit Wipe the unit gently with a soft and dry cloth The coils and fans should be cleaned periodically by an authorised dealer Outdoor unit Clean the debri...

Page 17: ...g cooling operation the discharged cold air may condense to water vapour Outdoor unit emits water or steam During cooling operation condensation occurs on cold pipes and the condensed water may drip f...

Page 18: ...ct COOL mode For details refer The remote control is missing or a malfunction has occurred above After 15 minutes of operation it is normal to have the following temperature difference between the air...

Page 19: ...t sink temperature sensor abnormality H 35 Indoor outdoor water adverse current abnormality H 36 Outdoor gas pipe temperature sensor abnormality H 37 Outdoor liquid pipe temperature sensor abnormality...

Page 20: ...tion with a chemical symbol In this case it complies with the requirement set by the Directive for the chemical involved WARNING This symbol shows that this equipment uses a flammable refrigerant If t...

Page 21: ...21 Information Memo English...

Page 22: ...3 A 1 12 am pm 24 5 2 SET 8 m 2 AIR CONDITIONER ON OFF SET TIMER CANCEL OFF ON AIR SWING TEMP OFF ON MODE SLEEP FAN SPEED QUIET POWERFUL ECO AIR CONDITIONER ON OFF TIMER CANCEL AIR SWING SLEEP FAN SP...

Page 23: ...23 B 2 MODE DRY AUTO COOL 1 OFF ON OFF ON POWER ON 3 TEMP UP TEMP DOWN TEMP 16 0 C 30 0 C 60 F 86 F C F 10 24 35 36 38 39 40 41 42 46 47 AAA R03 2 2 Panasonic Burmese...

Page 24: ...24...

Page 25: ...25 ELCB RCD ELCB Trip Burmese...

Page 26: ...26 Ni Cd...

Page 27: ...27 R32 Amin m Amin m R32 R410A R22 R22 R22 R32 R32 R410A R32 R410A Flare Nut R32 R410A R22 R32 R410A 1 2 inch R32 R410A Burmese...

Page 28: ...28 AHU 5 1 04MPa 4 15MPa 0 25...

Page 29: ...29 1 Amin m 12 2 2 1 2 2 2 2 2 8 2 m 2 m Burmese...

Page 30: ...30 2 3 2 4 CO2 2 5 2 6 2 7...

Page 31: ...31 2 8 capacitors discharged 3 Burmese...

Page 32: ...32 4 5 6 7 5 1 04MPa 4 15MPa 0 25 LFL 25 8...

Page 33: ...33 8 OFN OFN OFN OFN 9 OFN 7 Burmese...

Page 34: ...34 10 Recover Machine Recover Machine 80 11...

Page 35: ...35 12 Burmese...

Page 36: ...AUTO FAN QUIET QUIET POWERFUL POWERFUL 4 ECO ECO FAN SPEED QUIET POWERFUL ECO FAN SPEED QUIET POWERFUL ECO AIR CONDITIONER ON OFF SET TIMER CANCEL OFF ON AIR SWING TEMP OFF ON MODE SLEEP FAN SPEED QU...

Page 37: ...37 Timer 0 5 1 2 3 4 5 6 7 8 9 Timer Timer OFF Timer 0 0h SLEEP SLEEP POWERFUL ECO FAN SPEED QUIET POWERFUL ECO POWERFUL QUIET FAN SPEED Burmese...

Page 38: ...38 ON OFF SET TIMER CANCEL CANCEL 1 2 3 1 TIMER ON TIMER OFF 22 00 OFF OFF 2 3 SET 2 Timer Timer Timer ON OFF CANCEL Timer Timer ON OFF SET Timer Timer Timer...

Page 39: ...39 AUTO COOL DRY COOL 26 0 C 28 0 C 79 F 82 F COOL DRY COOL DRY Timer C F DBT WBT DBT WBT COOL 32 89 6 23 73 4 46 114 8 26 78 8 16 60 8 11 51 8 16 60 8 11 51 8 DBT WBT Burmese...

Page 40: ...40 H 99 pH 7 40 C 104 F 2 A B 1 B A 2 1 3 4...

Page 41: ...41 2 Burmese...

Page 42: ...42 POWER Timer Timer ON Timer 15 Timer ON Timer Timer Cool mode UV...

Page 43: ...43 Cool Mode Timer Burmese...

Page 44: ...44 AUTO OFF ON 1 2 AUTO AUTO OFF ON 3 COOL 1 AUTO OFF ON 4 AUTO OFF ON 5 COOL AUTO OFF ON 15 8 C 14 4 F Power Supply cable...

Page 45: ...CANCEL 5 5 2 1 3 4 4 H 00 H 11 H 12 H 14 H 15 H 16 current transformer CT H 17 H 19 H 21 Float Switch H 23 1 H 24 2 H 25 H 26 Negative H 27 H 28 1 H 30 Discharge Pipe H 31 H 32 2 H 33 H 34 H 35 H 36...

Page 46: ...H 51 H 52 Limit Switch H 58 H 59 H 64 H 67 nanoe H 70 H 71 H 72 H 85 LAN H 97 H 98 H 99 F 11 4 way F 16 F 17 F 18 Dry Circuit F 87 PCB F 90 Power Factor F 91 F 93 F 94 F 95 Cooling Side F 96 F 97 F 98...

Page 47: ...47 Pb Burmese...

Page 48: ...Printed in Malaysia ACXF55 31050 FA0321 0 Panasonic Corporation 1006 Kadoma Kadoma City Osaka Japan Website http www panasonic com Panasonic Corporation 2021...

Reviews: