Panasonic CS-PU24XKH Operating Instructions Manual Download Page 10

10

 Safety Precautions

8. Removal and evacuation

• When breaking into the refrigerant circuit 

to make repairs – or for any other purpose 
– conventional procedures shall be used. 
However, it is important that best practice is 
followed since 

fl

 ammability is a consideration. 

The following procedure shall be adhered to: 
remove refrigerant -> purge the circuit with 
inert gas -> evacuate -> purge with inert gas 
-> open the circuit by cutting or brazing.

• The refrigerant charge shall be recovered into 

the correct recovery cylinders.

• The system shall be purged with OFN to 

render the appliance safe.

• This process may need to be repeated 

several times.

• Compressed air or oxygen shall not be used 

for this task.

• Purging shall be achieved by breaking 

the vacuum in the system with OFN and 
continuing to 

fi

ll until the working pressure is 

achieved, then venting to atmosphere, and 

fi

nally pulling down to a vacuum.

• This process shall be repeated until no 

refrigerant is within the system.

• When the 

fi

 nal OFN charge is used, the 

system shall be vented down to atmospheric 
pressure to enable work to take place.

• This operation is absolutely vital if brazing 

operations on the pipe work are to take place.

• Ensure that the outlet for the vacuum pump is 

not close to any potential ignition sources and 
there is ventilation available.

OFN = oxygen free nitrogen, type of inert gas.

9. Charging procedures

• In addition to conventional charging 

procedures, the following requirements shall 
be followed.

 

- Ensure that contamination of different 

refrigerants does not occur when using 
charging equipment.

 

- Hoses or lines shall be as short as possible 

to minimize the amount of refrigerant 
contained in them. 

 

- Cylinders shall be kept in an appropriate 

position according to the instructions.

 

- Ensure that the refrigerating system is 

earthed prior to charging the system with 
refrigerant.

 

- Label the system when charging is 

complete (if not already). 

 

- Extreme care shall be taken not to over 

fi

ll 

the refrigerating system.

• Prior to recharging the system it shall be 

pressure tested with OFN (refer to #7).

• The system shall be leak tested on completion 

of charging but prior to commissioning.

• A follow up leak test shall be carried out prior 

to leaving the site.

• Electrostatic charge may accumulate and 

create a hazardous condition when charging 
and discharging the refrigerant. To avoid 

fi

 re 

or explosion, dissipate static electricity during 
transfer by grounding and bonding containers 
and equipment before charging/discharging.

10. Decommissioning

• Before carrying out this procedure, it is 

essential that the technician is completely 
familiar with the equipment and all its details.

• It is recommended good practice that all 

refrigerants are recovered safely.

• Prior to the task being carried out, an oil 

and refrigerant sample shall be taken in 
case analysis is required prior to re-use of 
recovered refrigerant.

• It is essential that electrical power is available 

before the task is commenced.

a) Become familiar with the equipment and 

its operation.

b) Isolate system electrically.
c) Before attempting the procedure ensure 

that: 

• mechanical handling equipment is 

available, if required, for handling 
refrigerant cylinders; 

• all personal protective equipment is 

available and being used correctly;

• the recovery process is supervised at all 

times by a competent person;

• recovery equipment and cylinders conform 

to the appropriate standards.

d) Pump down refrigerant system, if possible.

Summary of Contents for CS-PU24XKH

Page 1: ...nditioner 2 20 Before operating the unit please read these operating instructions thoroughly and keep them for future reference Before installation the installer should Read the Installation Instructi...

Page 2: ...he back cover of remote control 2 Insert AAA or R03 batteries 3 Close the cover A Clock setting 1 Press then press to set the time Press for approximately 5 seconds to show the time as 12 hour am pm o...

Page 3: ...only and may differ from the actual unit They are subject to change without notice B Basic operation 2 Press MODE to select the desired mode DRY AUTO COOL 1 Press OFF ON OFF ON to start stop the oper...

Page 4: ...supervised to ensure that they do not play with the appliance Please consult an authorised dealer or specialist to clean the internal parts repair install remove disassemble and reinstall the unit Im...

Page 5: ...nit is not going to be used for a long period of time New batteries of the same type must be inserted following the polarity stated Power supply Do not disconnect the plug by pulling the cord to preve...

Page 6: ...l the opening by pinching taping etc Handling of R32 is similar to R410A Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use of...

Page 7: ...he precautions in 12 and comply with national regulations Always contact to local municipal offices for proper handling 2 Servicing 2 1 Service personnel The system is inspected regularly supervised a...

Page 8: ...ernally into the atmosphere 2 7 Checks to the refrigerating equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the...

Page 9: ...the atmosphere from a leak 5 Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also t...

Page 10: ...minimize the amount of refrigerant contained in them Cylinders shall be kept in an appropriate position according to the instructions Ensure that the refrigerating system is earthed prior to charging...

Page 11: ...employed Ensure that the correct number of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refri...

Page 12: ...operation Press to restore the remote control to default setting Indicators To adjust FAN SPEED and QUIET condition FAN SPEED When AUTO FAN is selected the fan speed is adjusted automatically accordin...

Page 13: ...en manually dimmed This operation is incorporated with the activation timer 0 5 1 2 3 4 5 6 7 8 or 9 hours This operation can be set together with timer Sleep operation has the priority over OFF timer...

Page 14: ...If the timer has been cancelled manually or due to power failure you can restore the timer again Press ON or OFF to select the respective setting or then press SET The nearest timer setting is displa...

Page 15: ...xed at middle position setting Once the temperature is achieved the horizontal flap swings up down automatically In COOL DRY mode The horizontal flap swings up down automatically Auto restart control...

Page 16: ...Aluminium fin Front panel Air filters Indoor unit Wipe the unit gently with a soft and dry cloth The coils and fans should be cleaned periodically by an authorised dealer Outdoor unit Clean the debri...

Page 17: ...g cooling operation the discharged cold air may condense to water vapour Outdoor unit emits water or steam During cooling operation condensation occurs on cold pipes and the condensed water may drip f...

Page 18: ...ct COOL mode For details refer The remote control is missing or a malfunction has occurred above After 15 minutes of operation it is normal to have the following temperature difference between the air...

Page 19: ...t sink temperature sensor abnormality H 35 Indoor outdoor water adverse current abnormality H 36 Outdoor gas pipe temperature sensor abnormality H 37 Outdoor liquid pipe temperature sensor abnormality...

Page 20: ...tion with a chemical symbol In this case it complies with the requirement set by the Directive for the chemical involved WARNING This symbol shows that this equipment uses a flammable refrigerant If t...

Page 21: ...21 Information Memo English...

Page 22: ...3 A 1 12 am pm 24 5 2 SET 8 m 2 AIR CONDITIONER ON OFF SET TIMER CANCEL OFF ON AIR SWING TEMP OFF ON MODE SLEEP FAN SPEED QUIET POWERFUL ECO AIR CONDITIONER ON OFF TIMER CANCEL AIR SWING SLEEP FAN SP...

Page 23: ...23 B 2 MODE DRY AUTO COOL 1 OFF ON OFF ON POWER ON 3 TEMP UP TEMP DOWN TEMP 16 0 C 30 0 C 60 F 86 F C F 10 24 35 36 38 39 40 41 42 46 47 AAA R03 2 2 Panasonic Burmese...

Page 24: ...24...

Page 25: ...25 ELCB RCD ELCB Trip Burmese...

Page 26: ...26 Ni Cd...

Page 27: ...27 R32 Amin m Amin m R32 R410A R22 R22 R22 R32 R32 R410A R32 R410A Flare Nut R32 R410A R22 R32 R410A 1 2 inch R32 R410A Burmese...

Page 28: ...28 AHU 5 1 04MPa 4 15MPa 0 25...

Page 29: ...29 1 Amin m 12 2 2 1 2 2 2 2 2 8 2 m 2 m Burmese...

Page 30: ...30 2 3 2 4 CO2 2 5 2 6 2 7...

Page 31: ...31 2 8 capacitors discharged 3 Burmese...

Page 32: ...32 4 5 6 7 5 1 04MPa 4 15MPa 0 25 LFL 25 8...

Page 33: ...33 8 OFN OFN OFN OFN 9 OFN 7 Burmese...

Page 34: ...34 10 Recover Machine Recover Machine 80 11...

Page 35: ...35 12 Burmese...

Page 36: ...AUTO FAN QUIET QUIET POWERFUL POWERFUL 4 ECO ECO FAN SPEED QUIET POWERFUL ECO FAN SPEED QUIET POWERFUL ECO AIR CONDITIONER ON OFF SET TIMER CANCEL OFF ON AIR SWING TEMP OFF ON MODE SLEEP FAN SPEED QU...

Page 37: ...37 Timer 0 5 1 2 3 4 5 6 7 8 9 Timer Timer OFF Timer 0 0h SLEEP SLEEP POWERFUL ECO FAN SPEED QUIET POWERFUL ECO POWERFUL QUIET FAN SPEED Burmese...

Page 38: ...38 ON OFF SET TIMER CANCEL CANCEL 1 2 3 1 TIMER ON TIMER OFF 22 00 OFF OFF 2 3 SET 2 Timer Timer Timer ON OFF CANCEL Timer Timer ON OFF SET Timer Timer Timer...

Page 39: ...39 AUTO COOL DRY COOL 26 0 C 28 0 C 79 F 82 F COOL DRY COOL DRY Timer C F DBT WBT DBT WBT COOL 32 89 6 23 73 4 46 114 8 26 78 8 16 60 8 11 51 8 16 60 8 11 51 8 DBT WBT Burmese...

Page 40: ...40 H 99 pH 7 40 C 104 F 2 A B 1 B A 2 1 3 4...

Page 41: ...41 2 Burmese...

Page 42: ...42 POWER Timer Timer ON Timer 15 Timer ON Timer Timer Cool mode UV...

Page 43: ...43 Cool Mode Timer Burmese...

Page 44: ...44 AUTO OFF ON 1 2 AUTO AUTO OFF ON 3 COOL 1 AUTO OFF ON 4 AUTO OFF ON 5 COOL AUTO OFF ON 15 8 C 14 4 F Power Supply cable...

Page 45: ...CANCEL 5 5 2 1 3 4 4 H 00 H 11 H 12 H 14 H 15 H 16 current transformer CT H 17 H 19 H 21 Float Switch H 23 1 H 24 2 H 25 H 26 Negative H 27 H 28 1 H 30 Discharge Pipe H 31 H 32 2 H 33 H 34 H 35 H 36...

Page 46: ...H 51 H 52 Limit Switch H 58 H 59 H 64 H 67 nanoe H 70 H 71 H 72 H 85 LAN H 97 H 98 H 99 F 11 4 way F 16 F 17 F 18 Dry Circuit F 87 PCB F 90 Power Factor F 91 F 93 F 94 F 95 Cooling Side F 96 F 97 F 98...

Page 47: ...47 Pb Burmese...

Page 48: ...Printed in Malaysia ACXF55 31050 FA0321 0 Panasonic Corporation 1006 Kadoma Kadoma City Osaka Japan Website http www panasonic com Panasonic Corporation 2021...

Reviews: