12.10 Cooling Overload Control
Pipe temperature limitation / restriction.
o
Detects the outdoor pipe temperature and carry out restriction / limitation below (Limit the compressor
operation frequency)
o
The compressor stops if outdoor pipe temperature exceeds 61°C (PS9, 12NK), 63°C (PS18, 24NK).
o
If the compressor stops 4 times in 20 minutes, Timer LED blinks (“F95” indicated: Outdoor high pressure rise
protection)
12.11 Freeze Prevention Control 1
When indoor hear exchanger temperature is lower than 0°C continuously for 6 minutes, compressor will stops
operation.
Compressor will resume its operation 3 minutes after the indoor heat exchanger is higher than 5°C.
At the same time, indoor fan speed will be higher than during its normal operation.
If indoor heat exchanger is higher than 5°C for 5 minutes, the fan speed will return to its normal operation.
12.12 Freeze Prevention Control 2
Control start conditions
o
During Cooling operation and soft dry operation
During Thermo OFF condition, Indoor intake temperature is less than 10°C or
Compressor stops for freeze prevention control
o
Either one of the conditions above occurs 5 times in 60 minutes.
Control
contents
o
Operation
stops
o
Timer LED blinks and “H99” indicated
12.13 Dew Prevention Control
To prevent dew formation at indoor unit discharge area.
This control will be activated if:
o
Outdoor air temperature and indoor pipe temperature judgment by microcontroller is fulfilled.
o
When COOL or DRY mode is operated more than 20 minutes or more.
This control stopped if
o
Compressor
stopped.
o
Remote Control setting changed (fan speed/ temperature).
o
Outdoor air temperature and indoor intake temperature changed.
Fan speed will be adjusted accordingly in this control.
12.14 Odor Cut Control
To reduce the odor released from the unit.
o
Start
Condition
AUTO FAN Speed is selected during COOL or DRY operation.
During freeze prevention control and timer preliminary operation, this control is not applicable.
o
Control
content
Depends on compressor conditions:
1. Compressor
OFF
→
Compressor ON.
The indoor unit fan stops temporarily and then starts to blow at minimum airflow for 30 seconds.
2. Compressor
ON
→
Compressor OFF.
The indoor unit fan stops for 90 seconds and then blows at minimum airflow for 20 seconds.
Summary of Contents for CS-PS9NKH
Page 13: ...13 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control...
Page 14: ...14 4 Dimensions 4 1 Indoor Unit 4 1 1 CS PS9NKH CS PS12NKH CS PS18NKH...
Page 15: ...15 4 1 2 CS PS24NKH...
Page 16: ...16 4 2 Outdoor Unit 4 2 1 CU PS9NKH CU PS12NKH 4 2 2 CU PS18NKH...
Page 17: ...17 4 2 3 CU PS24NKH...
Page 18: ...18 5 Refrigeration Cycle Diagram 5 1 CS PS9NKH CU PS9NKH CS PS12NKH CU PS12NKH...
Page 19: ...19 5 2 CS PS18NKH CU PS18NKH CS PS24NKH CU PS24NKH...
Page 20: ...20 6 Block Diagram 6 1 CS PS9NKH CU PS9NKH...
Page 21: ...21 6 2 CS PS12NKH CU PS12NKH...
Page 22: ...22 6 3 CS PS18NKH CU PS18NKH...
Page 23: ...23 6 4 CS PS24NKH CU PS24NKH...
Page 24: ...24 7 Wiring Connection Diagram 7 1 Indoor Unit 7 1 1 CS PS9NKH CS PS18NKH CS PS24NKH...
Page 25: ...25 7 1 2 CS PS12NKH...
Page 30: ...30 8 Electronic Circuit Diagram 8 1 Indoor Unit 8 1 1 CS PS9NKH CS PS18NKH CS PS24NKH...
Page 31: ...31 8 1 2 CS PS12NKH...
Page 32: ...32 8 2 Outdoor Unit 8 2 1 CU PS9NKH...
Page 33: ...33 8 2 2 CU PS12NKH...
Page 34: ...34 8 2 3 CU PS18NKH...
Page 35: ...35 8 2 4 CU PS24NKH...
Page 37: ...37 9 1 1 2 CS PS12NKH 9 1 2 Indicator Printed Circuit Board...
Page 38: ...38 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU PS9 12NKH...
Page 39: ...39 9 2 1 2 CU PS18NKH...
Page 40: ...40 9 2 1 3 CU PS24NKH...
Page 41: ...41 9 2 2 Noise Filter Printed Circuit Board 9 2 2 1 CU PS9NKH CU PS12NKH...
Page 47: ...47 10 2 5 Wire Stripping And Connecting Requirement...
Page 92: ...92 Figure 19 Figure 20...