61
10.12.1.10 ECONAVI Demo Mode
To enable ECO DEMO mode, during unit is OFF (power standby):
SET
Transmit ECO demo code and
after 30 seconds return to normal
mode.
Press continously for 5s
Transmit check code
and after 30 seconds return to normal
mode.
Transmit sunlight sensor check code
and after 30 seconds return to normal
mode.
Remote control normal mode
To disable ECO Demo MODE:
o
Transmit ECO Demo signal again.
Operation details
Infrared sensor
Vane position
Fan speed
Sensor 1
Sensor 2
1
0
5
HI
1
1
Auto Swing
HI
0
1
2
HI
0
0
Auto Swing
LO
The target area will maintain for 5 seconds before changeover to next detection.
If no activity detection, the last action will maintain for 30 seconds before changeover to human absence status.
10.12.1.11 Human Activity Sensor Abnormality
Abnormality detection:
Connector disconnection / Wire cut abnormality
o
Sensor judge Hi level continuously for 25 seconds
Circuit abnormality
o
70 seconds after power ON, if human activity sensor judge Lo level continuously for 25 seconds
Error Code judgment
When abnormality happened, internal counter increase by 1 time.
Human activity sensor power OFF, retry after 5 seconds.
When the human activity sensor maintains normal condition for 120 seconds, the counter reset or AC reset.
When abnormality counter reached 4 times, H59 occurred – No TIMER indicator blinking.
When error code happened, the unit is able to operate without ECONAVI.