8

2.  Servicing
2-1.  Service personnel

• The system is inspected, regularly supervised 

and maintained by a trained and certi

fi

 ed 

service personnel who is employed by the 
person user or party responsible.

• Ensure the actual refrigerant charge is in 

accordance with the room size within which 
the refrigerant containing parts are installed.

• Ensure refrigerant charge not to leak.
• Any quali

fi

 ed person who is involved with 

working on or breaking into a refrigerant 
circuit should hold a current valid certi

fi

 cate 

from an industry-accredited assessment 
authority, which authorizes their competence 
to handle refrigerants safely in accordance 
with an industry recognised assessment 
speci

fi

 cation.

• Servicing shall only be performed 

as recommended by the equipment 
manufacturer. Maintenance and repair 
requiring the assistance of other skilled 
personnel shall be carried out under the 
supervision of the person competent in the 
use of 

fl

 ammable refrigerants.

• Servicing shall be performed only as 

recommended by the manufacturer.

2-2.  Work

• Prior to beginning work on systems 

containing 

fl

 ammable refrigerants, safety 

checks are necessary to ensure that the 
risk of ignition is minimised. For repair to the 
refrigerating system, the precautions in #2-2 
to #2-8 must be followed before conducting 
work on the system.

• Work shall be undertaken under a controlled 

procedure so as to minimize the risk of a 

fl

 ammable gas or vapour being present while 

the work is being performed.

• All maintenance staff and others working 

in the local area shall be instructed and 
supervised on the nature of work being 
carried out.

• Avoid working in con

fi

 ned spaces. Always 

ensure away from source, at least 2 meter of 
safety distance, or zoning of free space area 
of at least 2 meter in radius.

• Wear appropriate protective equipment, 

including respiratory protection, as conditions 
warrant.

• Keep all sources of ignition and hot metal 

surfaces away.

2-3.  Checking for presence of refrigerant

• The area shall be checked with an 

appropriate refrigerant detector prior to and 
during work, to ensure the technician is aware 
of potentially 

fl

 ammable atmospheres.

• Ensure that the leak detection equipment 

being used is suitable for use with 

fl

 ammable 

refrigerants, i.e. non sparking, adequately 
sealed or intrinsically safe.

• In case of leakage/spillage happened, 

immediately ventilate area and stay upwind 
and away from spill/release.

• In case of leakage/spillage happened, do 

notify persons down wind of the leaking/
spill, isolate immediate hazard area and keep 
unauthorised personnel out.

2-4.  Presence of 

fi

 re extinguisher

• If any hot work is to be conducted on the 

refrigerating equipment or any associated 
parts, appropriate 

fi

 re extinguishing 

equipment shall be available at hand.

• Have a dry powder or CO

2

 

fi

 re extinguisher 

adjacent to the charging area.

2-5.  No ignition sources

• No person carrying out work in relation to a 

refrigerating system which involves exposing 
any pipe work that contains or has contained 

fl

 ammable refrigerant shall use any sources 

of ignition in such a manner that it may lead 
to the risk of 

fi

 re or explosion. They must not 

be smoking when carrying out such work.

• All possible ignition sources, including 

cigarette smoking, should be kept suf

fi

 ciently 

far away from the site of installation, 
repairing, removing and disposal, during 
which 

fl

 ammable refrigerant can possibly be 

released to the surrounding space.

• Prior to work taking place, the area around 

the equipment is to be surveyed to make 
sure that there are no 

fl

 ammable hazards or 

ignition risks.

• “No Smoking” signs shall be displayed.

2-6.  Ventilated area

• Ensure that the area is in the open or that it is 

adequately ventilated before breaking into the 
system or conducting any hot work.

• A degree of ventilation shall continue during 

the period that the work is carried out.

• The ventilation should safely disperse any 

released refrigerant and preferably expel it 
externally into the atmosphere.

 Safety Precautions

Summary of Contents for CS-MTZ16ZKE

Page 1: ...ZKE CU RZ35ZKE CU RZ50ZKE Multi Split CU 2Z35TBE CU 2Z41TBE CU 2Z50TBE CU 3Z52TBE CU 3Z68TBE CU 4Z68TBE CU 4Z80TBE CU 5Z90TBE CU 2TZ41TBE CU 2TZ50TBE CU 3TZ52TBE nanoeX ENGLISH Before operating the un...

Page 2: ...3 1 Pull out the back cover of remote control 2 Insert AAA or R03 batteries 3 Close the cover A Clock setting 1 Press CLOCK then press to set the time Press CLOCK for approximately 5 seconds to show t...

Page 3: ...nation purposes only and may differ from the actual unit They are subject to change without notice B Basic operation Thank you for purchasing Panasonic Air Conditioner 1 Press to start stop the operat...

Page 4: ...st to clean the internal parts repair install remove disassemble and reinstall the unit Improper installation and handling will cause leakage electric shock or fire Confirm with authorised dealer or s...

Page 5: ...ical shock or fire Prevent electric shock by switching off the power supply and unplug Before cleaning or servicing When extended non use or During abnormally strong lightning activity CAUTION Indoor...

Page 6: ...working pressure is higher than that of refrigerant R22 models some of the piping and installation and service tools are special Especially when replacing a refrigerant R22 model with a new refrigera...

Page 7: ...onmental effects such as the danger of water collecting and freezing in relief pipes or the accumulation of dirt and debris h Expansion and contraction of long runs piping in refrigerating systems sha...

Page 8: ...nition and hot metal surfaces away 2 3 Checking for presence of refrigerant The area shall be checked with an appropriate refrigerant detector prior to and during work to ensure the technician is awar...

Page 9: ...ode refrigerant containing components unless the components are constructed of materials which are inherently resistant to being corroded or are properly protected against being so corroded 2 8 Checks...

Page 10: ...in the atmosphere from a leak 5 Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall al...

Page 11: ...e pipe work are to take place Ensure that the outlet for the vacuum pump is not close to any potential ignition sources and there is ventilation available OFN oxygen free nitrogen type of inert gas 9...

Page 12: ...rdous condition when charging or discharging the refrigerant To avoid fire or explosion dissipate static electricity during transfer by grounding and bonding containers and equipment before charging d...

Page 13: ...cuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant The evacuation process shall be carried out prior to returning the compressor to the suppl...

Page 14: ...llow the remote control setting If nanoe X is activated before the unit is turned off the nanoe X operation will resume when the unit is turned on This includes when TIMER ON is set Press the button a...

Page 15: ...ll modes Cannot be selected at the same time This operation provides you with a comfortable environment while sleeping It will automatically adjust the sleep pattern temperature during the activation...

Page 16: ...art automatically with the last operation mode and airflow direction This control is not applicable when TIMER is set To Learn More Single Single split system Multi Multi split system Operation mode I...

Page 17: ...43 109 4 26 78 8 46 114 8 26 78 8 Min 16 60 8 11 51 8 10 14 0 10 14 0 HEAT Max 30 86 0 24 75 2 18 64 4 24 75 2 18 64 4 Min 16 60 8 15 5 0 16 3 2 15 5 0 16 3 2 DBT Dry bulb temperature WBT Wet bulb tem...

Page 18: ...rings etc Wipe the unit gently with a soft damp cloth The coils and fans should be cleaned periodically by an authorised dealer Outdoor unit Clean the debris that surround the unit Clear any blockage...

Page 19: ...n room temperature increase Indoor fan stops occasionally during heating operation To avoid unintended cooling effect Indoor fan stops occasionally during automatic fan speed setting This is to help r...

Page 20: ...rly Remote control does not work Display is dim or transmission signal is weak Insert the batteries correctly Replace weak batteries The unit does not work Check if the circuit breaker is tripped Chec...

Page 21: ...nts Use AUTO OFF ON on the unit to select COOL or HEAT mode For details refer The remote control is missing or a malfunction has occurred above After 15 minutes of operation it is normal to have the f...

Page 22: ...35 Indoor outdoor water adverse current abnormality H 36 Outdoor gas pipe temperature sensor abnormality H 37 Outdoor liquid pipe temperature sensor abnormality H 38 Indoor outdoor mismatch brand cod...

Page 23: ...ly valid in the European Union If you wish to discard these items please contact your local authority or dealer and ask for the correct method of disposal Note for the battery symbol bottom two symbol...

Page 24: ...a branch of Panasonic Marketing Europe GmbH Maxis 2 Western Road Bracknell Berkshire RG12 1RT Manufactured by Panasonic Corporation 1006 Oaza Kadoma Kadoma City Osaka 571 8501 Japan Importer Panasonic...

Reviews: