14.2 Heating Operation
14.2.1 Outdoor fan control
When heating operation is enabled, based on outdoor ambient temperature, fan motor control will be adjusted
according to figure below for Heating overload control:
14.2.2 Heating Room Temp Sampling Control
To improve the judgment accuracy, indoor room temperature sampling starts when any indoor unit has stopped
capability supplied (heating thermo-off) during heating operation with compressor ON, outdoor unit will send
signal to all thermo-off indoor units to ON fan motor and get room temperature sample.
To prevent discharge temperature drop at indoor units which is ON when sampling the room temperature of
heating thermo-off units, the compressor frequency is increased accordingly.
However, if indoor room temperature is much higher compare to remote control setting temperature, before
thermo-off, sampling of corresponding indoor unit will be cancelled.
14.2.3 Powerful Operation 2
During cooling / heating operation, this control is to provide fast cooling / heating operation compare to normal
operation.
Operation start if all condition below are complied:
o
Powerful operation ON for indoor unit.
o
Not under Annual Cooling control.
Operation
content:
o
Outdoor fan speed will adjust automatically.
o
Compressor
frequency
will adjust automatically.
Operation stop when comply either one of the follow conditions:
o
When the powerful operation is OFF for all indoor units.
o
When annual cooling control activated.
14.3 Outdoor Quiet Cooling Operation Control
Purpose
Provide quiet cooling operation when only 1 indoor in operation.
Start
Condition
o
Indoor fan speed is lower than Lo fan.
o
Only 1 operation indoor unit.
o
Not in any cooling overload zone.
o
Not during annual cooling
o
Not initial frequency operation.
o
Not during starting control.
o
Not during “Electronic part temperature rise protection by outdoor air & total current”
o
Not during “Electronic part temperature rise protection by total current”
o
Not during “IPM temperature rise prevention control”
o
During
cool
mode
All conditions above are satisfied and function selection enable.
Summary of Contents for CS-MRE7PKE
Page 15: ...15 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control...
Page 16: ...16 5 Dimensions 5 1 Indoor Unit...
Page 17: ...17 5 2 Outdoor Unit...
Page 18: ...18 6 Refrigeration Cycle Diagram...
Page 19: ...19 7 Block Diagram 7 1 Indoor Unit...
Page 20: ...20 7 2 Outdoor Unit...
Page 21: ...21 8 Wiring Connection Diagram 8 1 Indoor Unit...
Page 22: ...22 8 2 Outdoor Unit...
Page 23: ...23 9 Electronic Circuit Diagram 9 1 Indoor Unit...
Page 24: ...24 9 2 Outdoor Unit...
Page 26: ...26 10 2 Outdoor Unit...
Page 53: ...53 17 3 Self Diagnosis Function...
Page 54: ...54...
Page 87: ...87...
Page 88: ...88 19 1 1 2 CS MRE9PKE...
Page 89: ...89...
Page 90: ...90 19 1 2 Two Indoor Unit Operation 19 1 2 1 CS MRE7PKE x2...
Page 91: ...91...
Page 92: ...92 19 1 2 2 CS MRE9PKE CS MRE7PKE...
Page 93: ...93...
Page 95: ...95...
Page 96: ...96 19 2 1 2 CS MRE9PKE...
Page 97: ...97...
Page 98: ...98 19 2 1 3 CS MRE12PKE...
Page 99: ...99...
Page 100: ...100 19 2 2 Two Indoor Unit Operation 19 2 2 1 CS MRE7PKE x2...
Page 101: ...101...
Page 102: ...102 19 2 2 2 CS MRE9PKE x2...
Page 103: ...103...
Page 104: ...104 19 2 2 3 CS MRE12PKE x2...
Page 105: ...105...