33 

CUTTING AND FLARING THE PIPING 

1. Please cut using pipe cutter and then remove the burrs.
2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused.

Turn the piping end down to avoid the metal powder entering the pipe.

3. Please make flare after inserting the flare nut onto the copper pipes.

10.1.4  Evacuation Of The Equipment 

WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND 
PIPES in the following procedure. 

1. Connect a charging hose with a push pin to

the Low side of a charging set and the service
port of the gas side 3-way valve.

2. Connect the micron gauge between vacuum

pump and service port of outdoor units.

3. Turn on the power switch of the vacuum pump

and make sure that connect digital micron
gauge and to pull down to a value of 500
microns.

4. To make sure micron gauge a value 500

microns and close the low side valve of the
charging set and turn off the vacuum pump.

5. Disconnect the vacuum pump house from the

service port of the 3-way valve.

6. Tighten the service port caps of gas side

3-way valve at a torque of 13.3 Ibf•ft (18 N•m)
with a torque wrench.

7. Remove the valve caps of both of the 2-way

valve and 3-way valve. Position both of the 
valves to “Open” using a hexagonal wrench 
(5/32" (4 mm)). 

8. Mount valve caps onto the 2-way valve and

3-way valve.

o

Be sure to check for gas leakage.

š

If micron gauge value does not descend 500 microns, take the following measures:

-

If the leak stops when the piping connections are tightened further, continue working from step 

e

.

-

If the leak does not stop when the connections are retightened, repair location of leak.

-

Do not release refrigerant during piping work for installation and reinstallation.

-

Take care when handling the liquid refrigerant, it may cause frostbite.

Reamer

2. To remove burrs

Point down

Pipe

1. To cut

Bar

0 –

1

/

32

"

(0-0.5 mm)

Ŷ

Improper flaring

Ŷ

Copper pipe

Inclined Surface

damaged

Cracked Uneven

thickness

3. To flare

Bar

Red arrow mark

Handle

Core

Yoke

Clamp handle

When properly flared, the internal surface
of the flare will evenly shine and be of
even thickness. Since the flare part
comes into contact with the connections,
carefully check the flare finish.

Outdoor unit

Liquid side

Gas
side

Vacuum

pump

Liquid side 3-way valve

Gas side 3-way valve

Liquid side

Gas
side

Tube connector

Tube connector

Tube connector

Tube connector

Close

Close

Indoor Unit

Indoor Unit

Summary of Contents for CS-MKS7NKU

Page 1: ...laced with manufacturer s specified parts to prevent shock fire or other hazards Do not modify the original design without permission of manufacturer WARNING This service information is designed for e...

Page 2: ...YES YES YES YES YES YES YES YES YES YES NO YES YES CS MKS9NKU CS MKS12NKU CS MKS18NKU CS MKS24NKU Wall Mounted Type CU 3KS19NBU CU 4KS24NBU CU 4KS31NBU Multi Outdoor Unit Indoor Unit 3 Room 4 Room 4...

Page 3: ...connecting tube kit CZ 3F type Unit A Maximum pipe length 25 m 82 0 ft Unit B Maximum pipe length 25 m 82 0 ft Unit C Maximum pipe length 25 m 82 0 ft Indoor outdoor unit connection cables Flexible co...

Page 4: ...imum pipe length 25 m 82 0 ft Unit B Maximum pipe length 25 m 82 0 ft Unit C Maximum pipe length 25 m 82 0 ft Unit D Maximum pipe length 25 m 82 0 ft Indoor outdoor unit connection cables Flexible cor...

Page 5: ...ngth Outdoor Unit CU 3E19 Allowable piping length of each indoor unit min max 9 8 ft 82 0 ft 3 m 25 m Allowable total piping length of all indoor unit 164 0 ft 50 m or less Height difference between i...

Page 6: ...he copper pipe Align center of piping to valves and then tighten with torque wrench to the specified torque as stated in the table Do not over tighten over tightening may cause gas leakage Piping size...

Page 7: ...3 3 Ibf ft 18 N m with a torque wrench 7 Remove the valve caps of both of the 2 way valve and 3 way valve Position both of the valves to Open using a hexagonal wrench 5 32 4 mm 8 Mount valve caps onto...

Page 8: ...it A Unit C Terminal Terminal Indoor Unit B Indoor Unit A Disconnect Switch Field supply Grounding wire Grounding wire min AWG16 Grounding wire min AWG16 Grounding wire min AWG16 Power Supply Single P...

Page 9: ...terial shall withstand 248 F 120 C or higher Gas side pipes 10 1 7 Disposal Of Outdoor Unit Drain Water If a drain elbow is used the unit should be placed on a stand which is taller than 1 31 32 50 mm...

Page 10: ...Unit Installation Diagram Allowable piping length Outdoor Unit CU 4E24 Allowable piping length of each indoor unit min max 9 8 ft 82 0 ft 3 m 25 m Allowable total piping length of all indoor unit 229...

Page 11: ...ench to the specified torque as stated in the table Do not over tighten over tightening may cause gas leakage Piping size Torque 1 4 6 35 mm 13 3 Ibf ft 18 N m 1 8 kgf m 3 8 9 52 mm 31 0 Ibf ft 42 N m...

Page 12: ...of 13 3 Ibf ft 18 N m with a torque wrench 7 Remove the valve caps of both the 2 way valve and 3 way valve Position both of the valves to Open using a hexagonal wrench 5 32 4 mm 8 Mount valve caps ont...

Page 13: ...g wire Power Supply Single Phase 208 230V 60Hz min AWG12 Grounding wire min AWG16 208 230V min AWG16 208 230V min AWG16 208 230V min AWG16 Grounding wire min AWG16 208 230V min AWG16 208 230V min AWG1...

Page 14: ...terial shall withstand 248 F 120 C or higher Gas side pipes 10 2 7 Disposal Of Outdoor Unit Drain Water If a drain elbow is used the unit should be placed on a stand which is taller than 1 31 32 50 mm...

Reviews: