11 3-way Valve
CU-MC145KE / CU-MC185KE / CU-3MC205KE / CU-MC196KE
3-way Valve (Liquid Side)
3-way Valve (Gas Side)
Works
Shaft Position
Service Port
Shaft Position
Service Port
Shipping
Close
Closed
Closed
Closed
(With valve cap)
(With cap)
(With valve cap)
(With cap)
Evacuation
Closed
Open
Closed
Open
(Installation and
(Clockwise)
(Connected manifold
(Clockwise)
(Push-pin)
Re-installation)
gauge w/charging cylinder)
Operation
Open
Closed
Open
Closed
(With valve cap)
(With cap)
(With valve cap)
(With cap)
Pumping down
Closed
Closed
Open
Open
(Transferring)
(Clockwise)
(With cap)
(Counter-Clockwise)
(Connected manifold
gauge)
Evacuation
Open
Open
Open
Open
(Servicing)
(Counter-Clockwise)
(Connected manifold
gauge)
(Counter-Clockwise)
(Connected manifold
gauge)
Gas charging
Open
Open
Open
Open
(Servicing)
(Counter-Clockwise)
(Connected manifold
gauge)
(Counter-Clockwise)
(Connected manifold
gauge)
Pressure check
Open
Open
Open
Open
(Servicing)
(Counter-Clockwise)
(Connected manifold
gauge)
(Counter-Clockwise)
(Connected manifold
gauge)
Gas releasing
Open
Open
Open
Open
(Servicing)
(Counter-Clockwise)
(Connected manifold
gauge)
(Counter-Clockwise)
(Connected manifold
gauge)
76