background image

9

10. Decommissioning

• Before carrying out this procedure, it is 

essential that the technician is completely 
familiar with the equipment and all its details.

• It is recommended good practice that all 

refrigerants are recovered safely.

• Prior to the task being carried out, an oil 

and refrigerant sample shall be taken in 
case analysis is required prior to re-use of 
reclaimed refrigerant.

• It is essential that electrical power is 

available before the task is commenced.
a)  Become familiar with the equipment and 

its operation.

b) Isolate system electrically.
c) Before attempting the procedure ensure 
that:
• mechanical handling equipment is 

available, if required, for handling 
refrigerant cylinders; 

• all personal protective equipment is 

available and being used correctly;

• the recovery process is supervised at all 

times by a competent person;

• recovery equipment and cylinders conform 

to the appropriate standards.

d)  Pump down refrigerant system, if 

possible.

e)  If a vacuum is not possible, make a 

manifold so that refrigerant can be 
removed from various parts of the system.

f)  Make sure that cylinder is situated on the 

scales before recovery takes place.

g)  Start the recovery machine and operate 

in accordance with manufacturer’s 
instructions.

h)  Do not over fi ll cylinders. (No more than 

80 % volume liquid charge).

i)  Do not exceed the maximum working 

pressure of the cylinder, even temporarily.

j)  When the cylinders have been fi lled 

correctly and the process completed, make 
sure that the cylinders and the equipment 
are removed from site promptly and all 
isolation valves on the equipment are 
closed off.

k)  Recovered refrigerant shall not be 

charged into another refrigeration system 
unless it has been cleaned and checked.

• Electrostatic charge may accumulate and 

create a hazardous condition when charging 
or discharging the refrigerant.
To avoid fi re or explosion, dissipate static 
electricity during transfer by grounding and 
bonding containers and equipment before 
charging/discharging.

11. Labelling

• Equipment shall be labelled stating that it 

has been de-commissioned and emptied of 
refrigerant.

• The label shall be dated and signed.
• Ensure that there are labels on the 

equipment stating the equipment contains 
fl ammable refrigerant.

12. Recovery

• When removing refrigerant from a system, 

either for servicing or decommissioning, 
it is recommended good practice that all 
refrigerants are removed safely.

• When transferring refrigerant into cylinders, 

ensure that only appropriate refrigerant 
recovery cylinders are employed.

• Ensure that the correct number of cylinders 

for holding the total system charge are 
available.

• All cylinders to be used are designated for 

the recovered refrigerant and labelled for 
that refrigerant (i.e. special cylinders for the 
recovery of refrigerant).

• Cylinders shall be complete with pressure 

relief valve and associated shut-off valves in 
good working order.

• Recovery cylinders are evacuated and, if 

possible, cooled before recovery occurs.

• The recovery equipment shall be in good 

working order with a set of instructions 
concerning the equipment that is at hand 
and shall be suitable for the recovery of 
fl ammable refrigerants.

• In addition, a set of calibrated weighing 

scales shall be available and in good 
working order.

• Hoses shall be complete with leak-free 

disconnect couplings and in good condition.

• Before using the recovery machine, check 

that it is in satisfactory working order, has 
been properly maintained and that any 
associated electrical components are 
sealed to prevent ignition in the event of a 
refrigerant release.
Consult manufacturer if in doubt.

• The recovered refrigerant shall be returned 

to the refrigerant supplier in the correct 
recovery cylinder, and the relevant Waste 
Transfer Note arranged.

• Do not mix refrigerants in recovery units and 

especially not in cylinders.

• If compressors or compressor oils are to 

be removed, ensure that they have been 
evacuated to an acceptable level to make 
certain that fl ammable refrigerant does not 
remain within the lubricant.

• The evacuation process shall be carried 

out prior to returning the compressor to the 
suppliers.

• Only electric heating to the compressor 

body shall be employed to accelerate this 
process.

• When oil is drained from a system, it shall be 

carried out safely.

ACXF55-1918̲OL.ai   9   6/1/2018   1:12:43 PM

ACXF55-1918̲OL.ai   9   6/1/2018   1:12:43 PM

Summary of Contents for CS-LU12UKYRN Series

Page 1: ...KYMNS series CU LU18UKYMNA series ACXF55 19180 AC English Operating Instructions Air Conditioner Thank you for purchasing Panasonic Air Conditioner Installation instructions attached Before operating the unit please read these operating instructions thoroughly and keep them for future reference C SLEEP SLEEP POWERFUL POWERFUL nanoe G nanoe G PURIFIER PURIFIER POWER POWER ACXF55 1918 OL ai 1 6 1 20...

Page 2: ...ACXF55 1918 OL ai 2 6 1 2018 1 12 42 PM ACXF55 1918 OL ai 2 6 1 2018 1 12 42 PM ...

Page 3: ...ontrol within 8 m from the remote control receiver of the indoor unit FAN DRY Safety precautions 4 9 How to use 10 11 Cleaning instructions 12 Troubleshooting 13 BEE Regulation 14 Information 15 To confirm Press SET or CLOCK again Please note that the OFF indication is as follows FAN nanoe G CHECK CHECK ACXF55 1918 OL ai 3 6 1 2018 1 12 42 PM ACXF55 1918 OL ai 3 6 1 2018 1 12 42 PM ...

Page 4: ...liances etc Refer to Table A of Installation instructions table for Amin m Be aware that refrigerant may not contain an odour highly recommended to ensure suitable flammable refrigerant gas detectors are present operating and able to warn of a leak Please consult authorised dealer or specialist to clean the internal parts repair install remove and reinstall the unit Improper installation and handi...

Page 5: ...R410A R22 models Since the working pressure is higher than that of refrigerant R22 models some of the piping and installation and service tools are special Especially when replacing a refrigerant R22 model with a new refrigerant R32 model always replace the conventional piping and flare nuts with the R32 and R410A piping and flare nuts on the outdoor unit side For R32 and R410A the same flare nut ...

Page 6: ...authorizes their competence to handle refrigerants safely in accordance with an industry recognised assessment specification Servicing shall only be performed as recommended by the equipment manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants Servicing shall b...

Page 7: ...o any substance which may corrode refrigerant containing components unless the components are constructed of materials which are inherently resistant to being corroded or are properly protected against being so corroded 2 8 Checks to electrical devices Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures Initial safety checks shall...

Page 8: ... and evacuation When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be used However it is important that best practice is followed since flammability is a consideration The following procedure shall be adhered to remove refrigerant purge the circuit with inert gas evacuate purge again with inert gas open the circuit by cutting or brazin...

Page 9: ...tied of refrigerant The label shall be dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant 12 Recovery When removing refrigerant from a system either for servicing or decommissioning it is recommended good practice that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrig...

Page 10: ... Con in Fan Only mode Unit operates without running compressor with IDU fan running as per remote setting fan speed and air flow direction Indoor unit temp display will show set temp for AUTO COOL DRY mode and room temp for FAN mode SLEEP Room temperature 23 C above Below 23 C 25 C 22 C Standard setting temperature ACXF55 1918 OL ai 10 6 1 2018 1 12 43 PM ACXF55 1918 OL ai 10 6 1 2018 1 12 43 PM ...

Page 11: ...o cancel ON or OFF timer press or then press If timer is cancelled manually or due to power failure you can restore the timer again by pressing or then press The nearest timer setting will be displayed and will activate in sequence When ON Timer is set the unit may start earlier up to 15 minutes before the actual set time in order to achieve the desired temperature on time Timer operation is based...

Page 12: ...ith water For seasonal inspection after extended non use Checking of remote control batteries No obstruction at air inlet and air outlet vents Use Auto OFF ON button to select COOL operation After 15 minutes of operation it is normal to have the following temperature difference between air inlet and air outlet vents COOL 8 C For extended non use Activate nanoe G operation for 2 3 hours as an alter...

Page 13: ...sh 13 Troubleshooting Cleaning instructions Troubleshooting The unit stops and some alpha numeric codes appear on IDU display ACXF55 1918 OL ai 13 6 1 2018 1 12 45 PM ACXF55 1918 OL ai 13 6 1 2018 1 12 45 PM ...

Page 14: ...ow for Full Load and for Half Load Setting Testing Guidelines Cooling Test Mode for Full Load 100 and Half Load 50 1 Mode Select COOL 2 Temperature a 16 ºC for Full Load 100 3 Air Swing S 4 Fan speed et vane position to 3rd step from top b 17 ºC for Half Load 50 POWER TIMER nanoe G PURIFIER SLEEP POWERFUL POWER TIMER nanoe G PURIFIER SLEEP POWERFUL Auto OFF ON Button Indication for Half load Indic...

Page 15: ...r http www panasonic com in corporate sustainability panasonic india i recycle program html S No 1 All electrical and electronic products are required to be handed over only to the Authorized recycler 2 The product should be handed over only to authorized recycler for disposal 3 4 5 6 Keep the product in isolated area after it becomes non functional un repairable so as to prevent its accidental br...

Page 16: ...al ignition source there is a possibility of ignition This symbol shows that the Operation Instructions should be read carefully This symbol shows that a service personnel should be handling this equipment with reference to the Installation Instructions This symbol shows that there is information included in the Operation Instructions and or Installation Instructions ACXF55 1918 OL ai 16 6 1 2018 ...

Reviews: