15.4.17. F11 (4-way valve Abnormality)
Malfunction Decision Conditions
• When heating operation, when indoor pipe temperature is below 10
°
C
• When cooling operation, when indoor pipe temperature is above 45
°
C
Malfunction Caused
• Connector in poor contact
• Faulty sensor
• Faulty outdoor unit PCB
• 4-way valve defective
Troubleshooting