58
13.2.5.
Dew Prevention Control 2
• To prevent dew formation at indoor unit discharge area.
• This control starts if all conditions continue for 20 minutes:
- Operated with Cooling or Soft Dry Mode.
- Indoor intake temperature is between 25
q
C and 29
q
C.
- Outdoor air temperature is less than 30
q
C.
- Quiet Lo fan speed.
• This control stopped if:
- When receive air swing change signal from Remote Control.
• The horizontal louver will be fixed at 24
q
(regardless of Auto or Manual Airflow Direction Setting).
13.3. Protection Control For Heating Operation
13.3.1.
Intake Air Temperature Control
Compressor will operate at Max freq. if either one of the below conditions occur:
1. When the indoor intake air temperature is 30
q
C or above.
13.3.2.
Outdoor Air Temperature Control
• The Max current value is regulated when the outdoor air temperature rise above 16
q
C in order to avoid compressor overloading.
13.3.3.
Overload Protection Control
• The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown below.
• If the heat exchanger temperature exceeds 60
q
C, compressor will stop.
13.3.4.
Low Temperature Compressor Oil Return Control
• In heating operation, if the outdoor temperature falls below -10
q
C when compressor starts, the compressor frequency will be
regulated up to 600 seconds.
13.3.5.
Cold Draught Operation
• When indoor pipe temperature is low, cold draught operation start where indoor fan speed will be reduced.
13.3.6.
Deice Operation
• When outdoor pipe temperature and outdoor air temperature is low, deice operation start where indoor fan motor and outdoor fan
motor stop and operation LED blinks.
Summary of Contents for CS-E7HKEW
Page 1: ... ...
Page 13: ...13 2 5 Outdoor Unit CU 2E15GBE ...
Page 14: ...14 2 6 Outdoor Unit 3E18EBE ...
Page 15: ...15 2 7 Outdoor Unit CU 3E23CBPG CU 4E27CBPG ...
Page 16: ...16 ...
Page 17: ...17 ...
Page 18: ...18 ...
Page 21: ...21 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 22: ...22 5 Dimensions 5 1 Indoor Unit ...
Page 23: ...23 5 2 Outdoor Unit 5 2 1 CU E7HKE CU E9HKE CU E12HKE 5 2 2 CU E15HKE ...
Page 26: ...26 7 Block Diagram 7 1 CS E7HKEW CU E7HKE CS E9HKEW CU E9HKE CS E12HKEW CU E12HKE ...
Page 27: ...27 7 2 CS E15HKEW CU E15HKE ...
Page 28: ...28 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 29: ...29 8 2 Outdoor Unit 8 2 1 CU E7HKE CU E9HKE CU E12HKE ...
Page 30: ...30 8 2 2 CU E15HKE ...
Page 31: ...31 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 32: ...32 9 2 Outdoor Unit 9 2 1 CU E7HKE CU E9HKE CU E12HKE ...
Page 33: ...33 9 2 2 CU E15HKE ...
Page 34: ...34 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 36: ...36 10 2 Outdoor Unit 10 2 1 CU E7HKE CU E9HKE CU E12HKE ...
Page 37: ...37 10 2 2 CU E15HKE ...
Page 67: ...67 16 1 3 To remove discharge grille ...
Page 68: ...68 16 1 4 To remove control board 16 1 5 To remove cross flow fan and indoor fan motor ...
Page 69: ...69 ...
Page 72: ...72 17 Technical Data 17 1 Operation Characteristics 17 1 1 CS E7HKEW CU E7HKE ...
Page 73: ...73 ...
Page 74: ...74 ...
Page 75: ...75 ...
Page 76: ...76 17 1 2 CS E9HKEW CU E9HKE ...
Page 77: ...77 ...
Page 78: ...78 ...
Page 79: ...79 ...
Page 80: ...80 17 1 3 CS E12HKEW CU E12HKE ...
Page 81: ...81 ...
Page 82: ...82 ...
Page 83: ...83 ...
Page 84: ...84 17 1 4 CS E15HKEW CU E15HKE ...
Page 85: ...85 ...
Page 86: ...86 ...
Page 87: ...87 ...