
79
12.3 Outdoor Unit
12.3.1 Install the Outdoor Unit
After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram.
1 If installing the unit to a concrete base or other solid base, use M10 or W3/8 bolts and nuts to secure the unit,
and ensure that the unit is fully upright and level.
(The anchor bolt positions are shown in the diagram at the right side.)
In particular, install the unit at a distance from the neighbouring building which conforms to regulations
specified by local noise emission regulation standards.
2 Do not install the outdoor unit to the building’s roof.
3 If there is a possibility that vibration may be transmitted to the rooms of the building, place rubber insulation
between the unit and the installation surface.
12.3.2 Connect the Piping
Connecting the piping to indoor
Please make flare after inserting flare nut (locate at
joint portion of tube assembly) onto the copper pipe.
(In case of using long piping)
Connect the piping
Align the center of piping and sufficiently tighten
the flare nut with fingers.
Further tighten the flare nut with torque wrench in
specified torque as stated in the table.
Connecting the piping to outdoor
Decide piping length and then cut by using pipe cutter.
Remove burrs from cut edge. Make flare after
inserting the flare nut (locates abnormal at valve) onto
the copper pipe.
Align center of piping to valves and then tighten with
torque wrench to the specified torque as stated in the
table.
Local pipes can project in any of four directions.
Make holes in the pipe panels for the pipes to
pass through.
Be sure to install the pipe panels to prevent rain
from getting inside the outdoor unit.
[Removing the service panel].
(1) Remove the two mounting screws.
(2) Slide the service panel downward to release
the pawls.
After this, pull the service panel toward you to
remove it.
Do not overtighten, overtightening may cause gas leakage.
Piping size
Torque
6.35 mm (1/4”)
[18 N•m (1.8 kgf.m)]
9.52 mm (3/8”)
[42 N•m (4.3 kgf.m)]
12.7 mm (1/2”)
[55 N•m (5.6 kgf.m)]
15.88 mm (5/8”)
[65 N•m (6.6 kgf.m)]
19.05 mm (3/4”)
[100 N•m (10.2 kgf.m)]
Summary of Contents for CS-E12PKR
Page 30: ...30 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 31: ...31 5 Dimensions 5 1 Indoor Unit 5 1 1 CS E7PKR CS E9PKR CS E12PKR CS E15PKR ...
Page 32: ...32 5 1 2 CS E18PKR CS E21PKR CS E24PKR CS E28PKR ...
Page 34: ...34 5 2 3 CU E28PKR ...
Page 35: ...35 6 Refrigeration Cycle Diagram 6 1 CU E7PKR ...
Page 36: ...36 6 2 CU E9PKR CU E12PKR ...
Page 37: ...37 6 3 CU E15PKR CU E18PKR ...
Page 38: ...38 6 4 CU E21PKR CU E24PKR ...
Page 39: ...39 6 5 CU E28PKR ...
Page 40: ...40 7 Block Diagram 7 1 CU E7PKR CU E9PKR CU E12PKR INDOOR UNIT OUTDOOR UNIT ...
Page 41: ...41 7 2 CU E15PKR CU E18PKR INDOOR UNIT OUTDOOR UNIT ...
Page 42: ...42 7 3 CU E21PKR INDOOR UNIT OUTDOOR UNIT ...
Page 43: ...43 7 4 CU E24PKR INDOOR UNIT OUTDOOR UNIT ...
Page 44: ...44 7 5 CU E28PKR ...
Page 53: ...53 9 1 2 CS E28PKR ...
Page 58: ...58 9 2 5 CU E28PKR ...
Page 61: ...61 10 1 5 Human Activity Sensor Printed Circuit Board ...
Page 62: ...62 10 2 Outdoor Unit 10 2 1 CU E7PKR CU E9PKR CU E12PKR ...
Page 63: ...63 10 2 2 CU E15PKR CU E18PKR CU E21PKR CU E24PKR ...
Page 64: ...64 10 2 3 CU E28PKR ...
Page 65: ...65 10 2 4 Noise Filter Printed Board CU E28PKR 10 2 5 Demand Control Printed Circuit Board ...
Page 111: ...111 16 3 Error Code Table ...
Page 112: ...112 ...
Page 143: ...143 17 1 1 3 To remove discharge grille ...
Page 144: ...144 17 1 1 4 To remove control board 17 1 1 5 To remove cross flow fan and indoor fan motor ...
Page 145: ...145 ...
Page 147: ...147 17 2 1 3 To remove power electronic controller ...
Page 149: ...149 ...
Page 201: ...201 19 2 5 CU E28PKR ...
Page 202: ...202 ...