14.2.6 Odor
Cut
Control
To reduce the odor released from the unit.
o
Start
Condition
AUTO FAN Speed is selected during COOL or DRY operation.
During freeze prevention control and timer preliminary operation, this control is not applicable.
o
Control
content
Depends on compressor conditions:
1. Compressor
OFF
→
Compressor ON.
The indoor unit fan stops temporarily and then starts to blow at minimum airflow for 30 seconds.
2. Compressor
ON
→
Compressor OFF.
The indoor unit fan stops for 90 seconds and then blows at minimum airflow for 20 seconds.
14.3 Protection Control For Heating Operation
14.3.1 Intake Air Temperature Control
Compressor will operate at limited freq., if indoor intake air temperature is 30°C or above.
14.3.2 Outdoor Air Temperature Control
The Max current value is regulated when the outdoor air temperature rise above 16°C (E7 ~ 15PK) and 14°C
(E18 ~ 28PK) in order to avoid compressor overloading.
14.3.3 Overload Protection Control
The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown
below.
If the heat exchanger temperature exceeds 60°C, compressor will stop.
14.3.4 Low Temperature Compressor Oil Return Control
In heating operation, if the outdoor temperature falls below -10°C (E7 ~ 12PK), -8°C (E15 ~ 24PK) and -6°C
(E28PK) when compressor starts, the compressor frequency will be regulated up to 600 seconds.
14.3.5 Cold Draught Prevention Control
When indoor pipe temperature is low, cold draught operation starts where indoor fan speed will be reduced.
Summary of Contents for CS-E12PKR
Page 30: ...30 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 31: ...31 5 Dimensions 5 1 Indoor Unit 5 1 1 CS E7PKR CS E9PKR CS E12PKR CS E15PKR ...
Page 32: ...32 5 1 2 CS E18PKR CS E21PKR CS E24PKR CS E28PKR ...
Page 34: ...34 5 2 3 CU E28PKR ...
Page 35: ...35 6 Refrigeration Cycle Diagram 6 1 CU E7PKR ...
Page 36: ...36 6 2 CU E9PKR CU E12PKR ...
Page 37: ...37 6 3 CU E15PKR CU E18PKR ...
Page 38: ...38 6 4 CU E21PKR CU E24PKR ...
Page 39: ...39 6 5 CU E28PKR ...
Page 40: ...40 7 Block Diagram 7 1 CU E7PKR CU E9PKR CU E12PKR INDOOR UNIT OUTDOOR UNIT ...
Page 41: ...41 7 2 CU E15PKR CU E18PKR INDOOR UNIT OUTDOOR UNIT ...
Page 42: ...42 7 3 CU E21PKR INDOOR UNIT OUTDOOR UNIT ...
Page 43: ...43 7 4 CU E24PKR INDOOR UNIT OUTDOOR UNIT ...
Page 44: ...44 7 5 CU E28PKR ...
Page 53: ...53 9 1 2 CS E28PKR ...
Page 58: ...58 9 2 5 CU E28PKR ...
Page 61: ...61 10 1 5 Human Activity Sensor Printed Circuit Board ...
Page 62: ...62 10 2 Outdoor Unit 10 2 1 CU E7PKR CU E9PKR CU E12PKR ...
Page 63: ...63 10 2 2 CU E15PKR CU E18PKR CU E21PKR CU E24PKR ...
Page 64: ...64 10 2 3 CU E28PKR ...
Page 65: ...65 10 2 4 Noise Filter Printed Board CU E28PKR 10 2 5 Demand Control Printed Circuit Board ...
Page 111: ...111 16 3 Error Code Table ...
Page 112: ...112 ...
Page 143: ...143 17 1 1 3 To remove discharge grille ...
Page 144: ...144 17 1 1 4 To remove control board 17 1 1 5 To remove cross flow fan and indoor fan motor ...
Page 145: ...145 ...
Page 147: ...147 17 2 1 3 To remove power electronic controller ...
Page 149: ...149 ...
Page 201: ...201 19 2 5 CU E28PKR ...
Page 202: ...202 ...