87
14. Protection
Control
14.1 Protection Control For All Operations
14.1.1 Restart
Control
(Time Delay Safety Control)
The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on
again by pressing OFF/ON button at remote control within this period.
This control is not applicable if the power supply is cut off and on again.
This phenomenon is to balance the pressure inside the refrigerant cycle.
14.1.2 Total Running Current
1 When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor
operation will be decreased.
2 If the running current does not exceed X value for 5 seconds, the frequency instructed will be increased.
3 However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for
3 minutes.
Model E7NKE/E-3
E9NKE/E-3
E12NKE E12NKE-3 E15NKE E18NKE E21NKE
Operation Mode
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
Cooling
/
Soft
Dry
(A) 3.78 15.06 4.62 15.06 6.64 15.06 6.93 15.06 8.25 15.06 11.81 14.75 12.27 14.75
Cooling
/
Soft
Dry
(B) 3.33 15.06 4.20 15.06 6.20 15.06 6.42 15.06 7.74 15.06 8.91 14.75 11.10 14.75
Heating
4.46 15.06 5.57 15.06 7.30 15.06 8.10 15.06 8.40 15.06 10.07 14.75 11.58 14.75
4 The first 30 minutes of cooling operation, (A) will be applied.
14.1.3 IPM (Power transistor) Prevention Control
Overheating Prevention Control
1 When the IPM temperature rises to 120°C, compressor operation will stop immediately.
2 Compressor operation restarts after 3 minutes the temperature decreases to 110°C.
3 If this condition repeats continuously 4 times within 20 minutes, timer LED will be blinking (“F96” is indicated).
DC Peak Current Control
1 When electric current to IPM exceeds set value of 18.5 A (E7 ~ 15NK) and 30.0 ± 5.0A (E18 ~ 21NK), the
compressor will stop operate. Then, operation will restart after 3 minutes.
2 If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will
restart after 1 minute.
3 If the set value exceeded again within 30 seconds after the compressor starts, the operation will restart after
1 minute. If this condition repeats continuously for 7 times, all indoor and outdoor relays will be cut off, timer
LED will be blinking (“F99” is indicated).
Summary of Contents for CS-E12NKEW
Page 21: ...21 Outdoor Unit CU 2E15LBE Outdoor Unit CU 2E18LBE ...
Page 22: ...22 Outdoor Unit CU 3E18LBE ...
Page 23: ...23 Outdoor Unit CU 4E23LBE ...
Page 24: ...24 ...
Page 25: ...25 Outdoor Unit CU 4E27CBPG ...
Page 26: ...26 ...
Page 28: ...28 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 30: ...30 5 1 2 CS E18NK CS E21NK CS XE18NK CS XE21NK ...
Page 32: ...32 5 2 3 CU E18NKE CU E21NKE ...
Page 33: ...33 6 Refrigeration Cycle Diagram 6 1 CU E7NKE CU E9NKE CU E12NKE CU E15NKE ...
Page 34: ...34 6 2 CU E7NKE 3 CU E9NKE 3 CU E12NKE 3 ...
Page 35: ...35 6 3 CU E18NKE ...
Page 36: ...36 6 4 CU E21NKE ...
Page 37: ...37 7 Block Diagram 7 1 CU E7NKE CU E9NKE ...
Page 38: ...38 7 2 CU E12NKE ...
Page 39: ...39 7 3 CU E15NKE ...
Page 40: ...40 7 4 CU E7NKE 3 CU E9NKE 3 CU E12NKE 3 ...
Page 41: ...41 7 5 CU E18NKE CU E21NKE ...
Page 42: ...42 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 43: ...43 8 2 Outdoor Unit 8 2 1 CU E7NKE CU E9NKE ...
Page 44: ...44 8 2 2 CU E12NKE ...
Page 45: ...45 8 2 3 CU E15NKE ...
Page 46: ...46 8 2 4 CU E7NKE 3 CU E9NKE 3 CU E12NKE 3 ...
Page 47: ...47 8 2 5 CU E18NKE CU E21NKE ...
Page 48: ...48 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 49: ...49 9 2 Outdoor Unit 9 2 1 CU E7NKE CU E9NKE ...
Page 50: ...50 9 2 2 CU E12NKE ...
Page 51: ...51 9 2 3 CU E15NKE ...
Page 52: ...52 9 2 4 CU E7NKE 3 CU E9NKE 3 CU E12NKE 3 ...
Page 53: ...53 9 2 5 CU E18NKE CU E21NKE ...
Page 54: ...54 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 56: ...56 10 1 5 Human Activity Sensor Printed Circuit Board ...
Page 57: ...57 10 2 Outdoor Unit 10 2 1 CU E7NKE CU E9NKE CU E7NKE 3 CU E9NKE 3 CU E12NKE 3 ...
Page 58: ...58 10 2 2 CU E12NKE CU E15NKE ...
Page 59: ...59 10 2 3 CU E18NKE CU E21NKE ...
Page 96: ...96 16 3 Error Codes Table ...
Page 97: ...97 ...
Page 127: ...127 17 1 1 3 To remove discharge grille ...
Page 128: ...128 17 1 1 4 To remove control board 17 1 1 5 To remove cross flow fan and indoor fan motor ...
Page 129: ...129 ...
Page 131: ...131 17 2 1 3 To remove power electronic controller ...
Page 133: ...133 ...