Panasonic CS/CU-HU12AKY Series Operating & Installation Instructions Manual Download Page 8

8

4. Repair to intrinsically safe components

• Do not apply any permanent inductive or 

capacitance loads to the circuit without 

ensuring that this will not exceed the 

permissible voltage and current permitted for 

the equipment in use.

• Intrinsically safe components are the only 

types that can be worked on while live in the 

presence of a flammable atmosphere.

• The test apparatus shall be at the correct 

rating.

• Replace components only with parts 

specified by the manufacturer. Unspecified 

parts by manufacturer may result ignition of 

refrigerant in the atmosphere from a leak.

5. Cabling

• Check that cabling will not be subject 

to wear, corrosion, excessive pressure, 

vibration, sharp edges or any other adverse 

environmental effects.

• The check shall also take into account the 

effects of aging or continual vibration from 

sources such as compressors or fans.

6. Detection of flammable refrigerants

• Under no circumstances shall potential 

sources of ignition be used in the searching 

or detection of refrigerant leaks.

• A halide torch (or any other detector using a 

naked flame) shall not be used.

7. Leak detection methods

• Electronic leak detectors shall be used 

to detect flammable refrigerants, but the 

sensitivity may not be adequate, or may 

need re-calibration.

(Detection equipment shall be calibrated in a 

refrigerant-free area.)

• Ensure that the detector is not a potential 

source of ignition and is suitable for the 

refrigerant used.

• Leak detection equipment shall be set at 

a percentage of the LFL of the refrigerant 

and shall be calibrated to the refrigerant 

employed and the appropriate percentage of 

gas (25 % maximum) is confirmed.

• Leak detection fluids are suitable for use with 

most refrigerants but the use of detergents 

containing chlorine shall be avoided as the 

chlorine may react with the refrigerant and 

corrode the copper pipe-work.

• If a leak is suspected, all naked flames shall 

be removed/extinguished.

• If a leakage of refrigerant is found which 

requires brazing, all of the refrigerant shall 

be recovered from the system, or isolated 

(by means of shut off valves) in a part of the 

system remote from the leak. Oxygen free 

nitrogen (OFN) shall then be purged through 

the system both before and during the 

brazing process.

8. Removal and evacuation

• When breaking into the refrigerant circuit to make 

repairs – or for any other purpose – conventional 

procedures shall be used.

However, it is important that best practice is 

followed since flammability is a consideration.

The following procedure shall be adhered to:

remove refrigerant -> purge the circuit with inert 

gas -> evacuate -> purge again with inert gas -> 

open the circuit by cutting or brazing

• The refrigerant charge shall be recovered into 

the correct recovery cylinders.

• The system shall be “flushed” with OFN to 

render the unit safe.

• This process may need to be repeated several times.

• Compressed air or oxygen shall not be used 

for this task.

• Flushing shall be achieved by breaking the 

vacuum in the system with OFN and continuing 

to fill until the working pressure is achieved, 

then venting to atmosphere, and finally pulling 

down to a vacuum.

• This process shall be repeated until no 

refrigerant is within the system.

• When the final OFN charge is used, the system 

shall be vented down to atmospheric pressure 

to enable work to take place.

• This operation is absolutely vital if brazing 

operations on the pipe work are to take place.

• Ensure that the outlet for the vacuum pump is 

not close to any ignition sources and there is 

ventilation available.

9. Charging procedures

• In addition to conventional charging procedures, 

the following requirements shall be followed.

- Ensure that contamination of different 

refrigerants does not occur when using 

charging equipment.

- Hoses or lines shall be as short as possible to 

minimize the amount of refrigerant contained 

in them.

- Cylinders shall be kept upright.

- Ensure that the refrigeration system is earthed 

prior to charging the system with refrigerant.

- Label the system when charging is complete 

(if not already).

- Extreme care shall be taken not to over fill the 

refrigeration system.

• Prior to recharging the system it shall be 

pressure tested with OFN (refer to #7).

• The system shall be leak tested on completion 

of charging but prior to commissioning.

• A follow up leak test shall be carried out prior to 

leaving the site.

• Electrostatic charge may accumulate and 

create a hazardous condition when charging 

and discharging the refrigerant.

To avoid fire or explosion, dissipate static 

electricity during transfer by grounding and 

bonding containers and equipment before 

charging/discharging.

Safety precautions

Summary of Contents for CS/CU-HU12AKY Series

Page 1: ...then request the customer keep them for future reference Remove the remote control packed with the indoor unit Air conditioner Operating Installation Instructions Images are for Illustration purpose o...

Page 2: ...INVERTER leverages ECONAVI sensor data and varies compressor rotation speed This helps to optimize cooling operation and reduces wasteful cooling nanoe G nanoeX Purifies the air down to the smallest p...

Page 3: ...y FAN DRY 2 1 3 7m Accessories Remote control AAA or R03 batteries 2 Remote control holder Screws for remote control holder 2 Ag Clean PM 0 1 Filter Safety precautions 4 9 How to use 10 11 To learn mo...

Page 4: ...e internal parts repair install remove and reinstall the unit Improper installation and handling will cause leakage electric shock or fire Confirm with authorised dealer or specialist on usage of any...

Page 5: ...the same as conventional refrigerant R410A R22 models Since the working pressure is higher than that of refrigerant R22 models some of the piping and installation and service tools are special Especi...

Page 6: ...accredited assessment authority which authorizes their competence to handle refrigerants safely in accordance with an industry recognised assessment specification Servicing shall only be performed as...

Page 7: ...where they are unlikely to be exposed to any substance which may corrode refrigerant containing components unless the components are constructed of materials which are inherently resistant to being co...

Page 8: ...nd during the brazing process 8 Removal and evacuation When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be used However it is important...

Page 9: ...hat it has been de commissioned and emptied of refrigerant The label shall be dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant 12 Rec...

Page 10: ...AU18AKYF Model FAN To operate Air Con in Fan Only mode Indoor unit temp display will show set temp for AUTO COOL DRY mode and room temp for FAN mode Only indoor unit fan operates as per remote setting...

Page 11: ...operation stops automatically after 1 hour JETSTREAM To set the timer To turn ON and OFF the unit at a preset time To enjoy freshness and cleaner environment This is a combination operation together...

Page 12: ...g low activity to maximise energy saving Mode Human Low activity COOL Set temperature ECONAVI take advantage of the human nature that human being takes time to feel the temperature rise during low act...

Page 13: ...native to remove moisture left in the internal parts thoroughly to prevent mould growth Turn off the power supply and unplug Remove the remote control batteries nanoe G Generator For better efficiency...

Page 14: ...and some alpha numeric codes appear on IDU display Unit s Wi Fi connection with the router is activated Wi Fi LED stays ON during unit turn OFF Check unit s Wi Fi connection with router Wi Fi LED coun...

Page 15: ...Note 15 English Troubleshooting...

Page 16: ...condenser is not obstructed There should not be any animal or plant which could be affected by hot air discharged Keep the spaces indicated by arrows from wall ceiling fence or other obstacles Do not...

Page 17: ...checking for gas leaks and secure with vinyl tape Vinyl tape Insulation of piping connections Remote control holder Remote control holder fixing screws Remote control Attaching the remote control hold...

Page 18: ...ount the installation plate on the wall with 5 screws or more at least 5 screws If mounting the unit on the concrete wall consider using anchor bolts Always mount the installation plate horizontally b...

Page 19: ...left piping Right Rear piping Cover for piping How to keep the cover In case of the cover is cut keep the cover at the rear of chassis as shown in the illustration for future reinstallation Left right...

Page 20: ...ction cable Gas side piping Liquid side piping Drain hose Insert the connection cable This can be used for left rear piping and bottom piping also How to pull the piping and drain hose out in case of...

Page 21: ...oprene sheathed 4 x 1 0 mm2 1 5 1 8HP 4 x 1 5 mm2 2 0HP or 4 x 2 5mm2 2 5HP flexible cord type designation IS 694 or 60245 IEC 57 or heavier cord Bind all the indoor and outdoor connection cable with...

Page 22: ...n this area must follow to national wiring rules Do not joint wires Wire stripping No loose strand when inserted 10 1 mm Conductor fully inserted ACCEPT Conductor over inserted PROHIBITED Conductor no...

Page 23: ...orque wrench Spanner or Wrench Decide piping length and then cut by using pipe cutter Remove burrs from cut edge Make flare after inserting the flare nut locate at valve onto the copper pipe Align cen...

Page 24: ...unit and outdoor unit shall be approved polychloroprene sheathed 4 x 1 0 mm2 1 5 1 8HP 4 x 1 5 mm2 2 0HP or 4 x 2 5mm2 2 5HP flexible cord type designation IS 694 or 60245 IEC 57 or heavier cord Do n...

Page 25: ...as shown in the illustration 3 Then remove the 2 1 5HP or 4 2 0 2 5HP mounting screws 4 Pull the lower section of the front grille towards you to remove the front grille The below operations will be p...

Page 26: ...aterial with a new one Heat insulating material is required for both liquid side and gas side piping Most Important Process Purpose To make the oil refrigerant mix together They are in separated condi...

Page 27: ...or dwelling or room must be made by brazing orwelding Joint connection of indoor unit by flaring method can only be made at outdoor or at outside of a buidling or dwelling or room Flare connection ma...

Page 28: ...b 17 C for Half Load 50 For Full Load QUIET CLEAN Open the Front Panel by lifting Intake Grille Follow the below Instructions 4 Air Swing Horizontal Airflow Set vane position to be AUTO 5 Fan speed M...

Page 29: ...door Unit Control button while holding the indoor unit button Step b Within 5 second press once the Remote Step c After hearing a beep sound from the Indoor Unit immediately release the Auto OFF ON bu...

Page 30: ...ed above carries warranty for 3 years from the date of purchase Product ROOM AIR CONDITIONER Panasonic Life Solutions India Pvt Ltd Model No ODU SI No IDU SI No Customer Name Address Tel No Date of Pu...

Page 31: ...ject or living creature eg Rat lizard insect ants etc inside the Product unit f Use of harmful chemicals Improper heat load Usage of unit in an abnormally corrosive alkaline acidic atmosphere g Any ch...

Page 32: ...m in corporate sustainability panasonic india i recycle program html S No 1 All electrical and electronic products are required to be handed over only to the Authorized recycler 2 The product should b...

Reviews: