2-way Valve (Liquid Side)
3-way Valve (Gas Side)
Gas releasing
Open
(Servicing)
Open
Open
(Connected
manifold
11.1. Air Purging of the Piping and Indoor Unit
11.1.1. Air purging (Installation)
Required tools: hexagonal wrench, adjustable wrench, torque wrenches, wrench to hold the
joints and gas leak detector. / The additional gas for air purging has been charged in the
outdoor unit. / However, if the flare connections have not been done correctly and there gas
leaks, a gas cylinder and the charge set will be needed.
The air in the indoor unit and in the piping must be purged. If air remains in the refrigeration
pipings, it will affect the compressor, reduce the cooling capacity, and could lead to a
malfunction.
Service port cap / Be sure, using a torque wrench to tighten the service port cap (after using the
service port), so that it prevents the gas leakage from the refrigeration cycle.
Procedure:
1. Recheck the piping connections.
2. Open the valve stem of the 2-way valve counter-clockwise
approximately 90°, wait 10 seconds, and then set it to closed
position.
- Be sure to use a hexagonal wrench to operate the valve stem.
44
Summary of Contents for CS-C9BKNG
Page 7: ...4 Dimensions 7 ...
Page 8: ...5 Refrigeration Cycle Diagram 8 ...
Page 9: ...6 Block Diagram 9 ...
Page 10: ...7 Wiring Diagram 10 ...
Page 31: ...3 For the embedded piping 31 ...
Page 32: ... This can be used for left rear piping left bottom piping also 32 ...
Page 59: ...14 Technical Data 59 ...
Page 60: ...15 Exploded View 60 ...
Page 66: ...How to use electronic circuit diagram 66 ...
Page 69: ...20 3 PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD BOTTOM VIEW 69 ...
Page 70: ... MACC Printed in Malaysia 70 ...