13.6.
Compressor Reverse Rotation Protection Control
• If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and indoor
heat exchanger is 2.5
q
C or less for continuous 2 minutes, compressor will stop and restart automatically.
• Time Delay Safety Control is activated before the compressor restart.
• This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
13.7. Dew Prevention Control
• To prevent dew formation at indoor unit discharge area.
• This control starts if:
- Cooling mode or Quiet mode is activated.
- Remote Control setting temperature is less than 25
q
C.
- Fan speed is at Lo or QLo.
- Room temperature is constant (±1
q
C) for 30 minutes.
- Compressor is continuously running.
• Fan speed, angle of horizontal louver (vertical airflow angle) and angle of vertical louver (horizontal airflow angle) will be adjusted
accordingly in this control.
- Fan speed will be increased slowly if the unit is in quiet mode and Lo fan speed.
- The angle of horizontal louver will be changed as table below:
- The angle of vertical louver will be changed as table below:
• Dew prevention stop condition
- Remote control setting temperature is more than 25
q
C.
- Fan speed is not set to Lo or QLo.
- Select Powerful operation.
Airflow direction auto control
Airflow direction manual control
Airflow direction auto control
Airflow direction manual control
Summary of Contents for CS-C18HKD
Page 9: ...9 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 10: ...10 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS C18HKD CS C24HKD ...
Page 11: ...11 5 2 Outdoor Unit 5 2 1 CU C18HKD 5 2 2 CU C24HKD ...
Page 12: ...12 6 Refrigeration Cycle Diagram ...
Page 13: ...13 7 Block Diagram ...
Page 16: ...16 9 Electronic Circuit Diagram ...
Page 17: ...17 10 Printed Circuit Board 10 1 Indoor Unit Main Printed Circuit Board TOP VIEW ...
Page 18: ...18 BOTTOM VIEW ...
Page 19: ...19 10 2 Indoor Unit Power Printed Circuit Board ...
Page 20: ...20 10 3 Indicator panel TOP VIEW BOTTOM VIEW ...
Page 49: ...49 ...
Page 50: ...50 ...
Page 51: ...51 ...
Page 52: ...52 ...
Page 53: ...53 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry ...
Page 54: ...54 17 2 Operation Characteristics 17 2 1 CS C18HKD CU C18HKD ...
Page 55: ...55 ...
Page 56: ...56 17 2 2 CS C24HKD CU C24HKD ...
Page 57: ...57 ...