How to fix cable
Connecting with external device (optional)
All connections shall
follow to the local national wiring standard.
It is strongly recommended to use manufacturer-recommended parts and accessories for installation.
For connection to main PCB
1 Two-way valve shall be spring and electronic type, refer to “Field Supply Accessories” table for details. Valve
cable shall be (3 x min 1.5 mm
2
), of type designation 60245 IEC 57 or heavier, or similarly double insulation
sheathed cable.
* note: - Two-way Valve shall be CE marking compliance component.
- Maximum load for the valve is 9.8VA.
2 Room thermostat cable must be (4 or 3 x min 0.5 mm
2
), of type designation 60245 IEC 57 or heavier cord, or
similarly double insulation sheathed cable.
3 Extra pump cable shall be (2 x min 1.5 mm
2
), of type designation 60245 IEC 57 or heavier.
4 Boiler contact cable shall be (2 x min 0.5 mm
2
), of type designation 60245 IEC 57 or heavier.
5 External control shall be connected to 1-pole switch with min 3.0 mm contact gap. Its cable must be (2 x min
0.5 mm
2
), double insulation layer of PVC-sheathed or rubber-sheathed cable.
* note: - Switch used shall be CE compliance component.
- Maximum operating current shall be less than 3A
rms
.
6 Room sensor zone 1 cable shall be (2 x min 0.3 mm
2
) double insulation layer of PVC-sheathed or rubber-
sheathed.
7 Outdoor air sensor cable shall be (2 x min 0.3 mm
2
) double insulation layer of PVC-sheathed or rubber-
sheathed.
For connection to Optional PCB
1 By connecting Optional PCB, 2 Zone temperature control can be achieved. Please connect mixing valves,
water pumps and thermistors in zone 1 and zone 2 to each terminals in Optional PCB.
Temperature of each zone can be controlled independently by remote controller.
2 Pump zone 1 and zone 2 cable shall be (2 x min 1.5 mm
2
), of type designation 60245 IEC 57 or heavier.
3 Solar pump cable shall be (2 x min 1.5 mm
2
), of type designation 60245 IEC 57 or heavier.
4 Pool pump cable shall be (2 x min 1.5 mm
2
), of type designation 60245 IEC 57 or heavier.
5 Room thermostat zone 1 and zone 2 cable shall be (4 x min 0.5 mm
2
), of type designation 60245 IEC 57 or
heavier.
6 Mixing valve zone 1 and zone 2 cable shall be (3 x min 1.5 mm
2
), of type designation 60245 IEC 57 or
heavier.
7 Room sensor zone 1 and zone 2 cable shall be (2 x min 0.3 mm
2
), double insulation layer (with insulation
strength of minimum 30V) of PVC-sheathed or rubber-sheathed cable.
8 Buffer tank sensor, pool water sensor and solar sensor cable shall be (2 x min 0.3 mm
2
), double insulation
layer (with insulation strength of minimum 30V) of PVC-sheathed or rubber-sheathed cable.
9 Water sensor zone 1 and zone 2 cable shall be (2 x min 0.3 mm
2
), double insulation layer of PVC-sheathed
or rubber-sheathed cable.
Bind optional
cables with
these bands
Power Supply 1
RCCB
Power Supply 2
RCCB
Holder (Clamper)
Indoor terminal
for connecting
cables
Bind optional
cables with
these bands
Main PCB
4
How to guide the optional cables and power supply cord
(view without internal wiring)
Optional cables:
•
External control
cable
•
Room sensor
zone 1
•
Outdoor air sensor
cable
•
Remote controller
cable
Optional cables:
•
2-way valve
cable
•
Room thermostat zone
1 cable
•
Extra pump cable
•
Boiler contact cable
•
Power Supply 1 cord
•
Power Supply 2 cord
•
Indoor Unit/Outdoor Unit Connecting cable