Settings
KW2M-A/X User's Manual
29
5.4 How to make settings using the keys
■
Set before measuring.
Select an setting item with <ITEM/
>
> and press <SET> and the value will be blinking. Set a new
value with the keys <ITEM/
>
> and <SHIFT/
∧
>.
When you select [Yes] in the confirmation window and press <SET>, the setting values are saved.
Setting items with (
※
) can be set for each CH and each unit individually.
5.4.1 Settings for power measurement
Phase/Wire system
(
※
)
Select phase/wire system to measure.
M
- 1
P o
w
e r
S y s t e m
1 P 2
W
Press <ITEM/
>
>, <SHIFT/
∧
>.
[Set list]
1P2W, 1P3W, 3P3W, 3P4W (initial: 1P2W)
* When the setting does not match the measured system,
the device will not measure correctly.
CT setting
(
※
)
Select the CT type used.
M
- 1
P o
w
e r
C T
P r
i m a r y
5 A
S e c o n d a r y
5 A
Press <SET> to select primary or secondary.
Press <ITEM/
>
>, <SHIFT/
∧
> to select the range.
[Set range]
Primary side: 1 to 65535 (initial: 5)
Secondary side: 5 (5A), 1 (1A) (initial: 5)
Increase
Decrease
For CT with secondary side current 5A: [5]
For CT with secondary side current 1A: [1]
Voltage setting
Set the rated voltage to measure.
M
- 1
P o
w
e r
V T
P r
i m a r y
2 3 0 V
S e c o n d a r y
2 3 0 V
Press <SET> to select primary or secondary.
Press <ITEM/
>
>, <SHIFT/
∧
> to set the voltage.
[Set range]
Primary side: 100 to 500000 (initial: 230)
Secondary side: 100 to 690 (initial: 230)
*Set the rated voltage when no VT is used.
Increase
Decrease
SHIF
T
>
ITE
M
>
SHIF
T
>
ITE
M
>