6.1 Installation
67
1
2
3
4
5
1
Upside-down
2
Air duct blocked
3
Input and output connectors face down
4
Input and output connectors on top
5
Horizontal installation of the unit
•
Do not install the unit above devices which generate heat such as heaters,
transformers or large scale resistors.
Installation space
•
Leave at least 50mm of space between the wiring ducts of the unit and other devices
to allow heat radiation and unit replacement.
≥
50mm
≥
50mm
•
Maintain a minimum of 100mm between devices to avoid adverse affects from noise
and heat when installing a device or panel door to the front of the unit.
1
PLC
2
Other device
3
Panel door
≥
100mm
•
Keep the first 100 mm from the unit's front surface clear of objects to allow wiring and
the connection of the programming tool.
Summary of Contents for AFPG951T34
Page 7: ......
Page 17: ......
Page 18: ...Chapter 1 Safety Measures ...
Page 21: ......
Page 22: ...Chapter 2 Overview ...
Page 32: ...Chapter 3 CPU Types ...
Page 47: ...CPU Types FPΣ User s Manual 30 LD Body ...
Page 51: ...CPU Types FPΣ User s Manual 34 POU Header and LD Body ...
Page 55: ...CPU Types FPΣ User s Manual 38 LD Body ...
Page 57: ......
Page 58: ...Chapter 4 Expansion ...
Page 73: ......
Page 74: ...Chapter 5 I O Allocation ...
Page 81: ......
Page 82: ...Chapter 6 Installation and Wiring ...
Page 115: ......
Page 116: ...Chapter 7 High Speed Counter and Pulse Output ...
Page 169: ......
Page 170: ...Chapter 8 Communication ...
Page 227: ...Communication FPΣ User s Manual 210 LD Body ST Body ...
Page 233: ...Communication FPΣ User s Manual 216 POU Header LD Body ...
Page 236: ...FPΣ User s Manual 8 6 Program Controlled Communication 219 POU Header LD Body 1 2 ...
Page 237: ...Communication FPΣ User s Manual 220 2 2 ST Body ...
Page 266: ...Chapter 9 Security Functions ...
Page 273: ......
Page 274: ...Chapter 10 Other Functions ...
Page 277: ......
Page 278: ...Chapter 11 Troubleshooting ...
Page 289: ......
Page 290: ...Chapter 12 Appendix ...